R3-NL1-K3/Q [MSYSTEM]

Remote I/O R3 Series LonWorks INTERFACE MODULE;
R3-NL1-K3/Q
型号: R3-NL1-K3/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R3 Series LonWorks INTERFACE MODULE

文件: 总5页 (文件大小:152K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R3-NL1  
Remote I/O R3 Series  
RELATED PRODUCTS  
• XIF File (Device Interface File)  
XIF file is used to define a LonWorks device when  
programmed on LonMaker.  
LonWorks INTERFACE MODULE  
(analog I/O 16 points, discrete I/O 48 points)  
27.5 (1.08)  
GENERAL SPECIFICATIONS  
Connection  
LonWorks: Euro type connector terminal  
130  
(5.12)  
(applicable wire size: 0.2 to 2.5 mm , stripped length 7 mm)  
2
Internal bus: Via the Installation Base  
(model: R3-BSx)  
Internal power: Via the Installation Base (model: R3-BSx)  
Power input, RUN contact output: M3 separable screw  
terminal (torque 0.5 N·m)  
109  
(4.29)  
mm (inch)  
Screw terminal: Nickel-plated steel  
Isolation: LonWorks to internal bus or internal power to  
power input to RUN contact output to FG  
Input error data setting: Input value setting at input module  
error with side DIP SW  
MODEL: R3–NL1–[1][2]  
ORDERING INFORMATION  
• Code number: R3-NL1-[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. R3-NL1-R/Q)  
Dual communication setting: Set with the side DIP switch  
Data allocation setting: Set with the side DIP switch  
RUN indicator: Bi-color (green/red) LED; Green ON in  
communications with another device online or changing the  
output data (turns off after 25 seconds of no  
communication); Red ON when receiving data (function  
selected with DIP SW)  
• Specify the specification for option code /Q  
(e.g. /C01)  
[1] POWER INPUT  
N: No power supply  
ERR indicator: Bi-color (green/red) LED; Green ON or  
blinking at communication error; Red ON at transmitting  
data (Function selected with DIP SW)  
AC Power  
K3: 100 – 120 V AC  
RUN CONTACT OUTPUT  
(Operational voltage range 85 - 132 V, 47 - 66 Hz) *  
L3: 200 – 240 V AC  
RUN contact: Turns on while the green RUN LED is ON  
(LonWorks in normal communication)  
(Operational voltage range 170 - 264 V, 47 - 66 Hz) *  
DC Power  
Rated load: 250 V AC @ 0.5 A (cos ø = 1)  
30 V DC @ 0.5 A (resistive load)  
R: 24 V DC  
Maximum switching voltage: 250 V AC or 30 V DC  
Maximum switching power: 250 VA or 150 W  
Minimum load: 1 V DC @ 1 mA  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) *  
* Not selectable for use with independent power modules or  
network modules with the internal power input options.  
Mechanical life: 2 × 10 cycles (rate 300 cycles/min.) When  
7
driving an inductive load, external contact protection and  
noise quenching recommended.  
[2] OPTIONS  
blank: none  
/Q: With options (specify the specification)  
LonWorks COMMUNICATION  
Neuron Chip: FT3120 (NeuronID printed in numbers and bar  
code [peel-off code 39 format])  
Transceiver: FT-X1 (equivalent to FTT10A)  
Transmission speed: 78 kbps  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
Twisted-pair cable  
/C02: Polyurethane coating  
Distance, free topology: 500 meters  
Max. 64 nodes/channel  
/C03: Rubber coating  
LNS: Ver. 3.0 Service Pack 8 or higher  
Network variable type  
R3-NL1 SPECIFICATIONS  
ES-8427 Rev.10 Page 1/5  
http://www.m-system.co.jp/  
MODEL: R3-NL1  
Analog: SNVT_lev_percent or SNVT_temp (selectable)  
Discrete: SNVT_switch  
ONLINE indicator: Red LED  
ON: Off-line or no network information (decommissioned)  
Blinking in approx. 0.5 Hz: On-line  
(ready to communicate network variables)  
Blinking in approx. 5 Hz for 30 sec.: Wink message received  
SERVICE indicator: Green LED  
OFF: Normal operations  
Blinking in approx. 0.5 Hz: No network information  
ON: Internal program error  
SERVICE switch: Used to identify the node in LonWorks  
network configuration  
RESET switch: Resetting the Neuron Chip  
Numbers of data (*factory setting)  
Analog Input  
Analog Output  
16  
0
12  
4
8 (*)  
8 (*)  
4
12  
0
16  
Discrete Input  
Discrete Output  
0
48  
0
48  
INSTALLATION  
Power consumption  
AC: Approx. 20 VA  
DC: Approx. 12 W  
Current consumption (no power supply): 100 mA  
Output current (power supply): 250 mA continuous at 20 V  
DC; 400 mA for 10 minutes  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R3-BSx)  
Weight: 200 g (0.44 lb)  
PERFORMANCE  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute (LonWorks or  
internal bus or internal power to power input to RUN contact  
output to FG)  
R3-NL1 SPECIFICATIONS  
ES-8427 Rev.10 Page 2/5  
http://www.m-system.co.jp/  
MODEL: R3-NL1  
EXTERNAL VIEW  
FRONT VIEW  
SIDE VIEW  
ONLINE LED  
SERVICE LED  
SERVICE SW  
RESET SW  
RUN LED  
ERR LED  
DIP SW  
SW3  
ON  
SW2  
SW1  
1
2
3
4
5
4
3
2
1
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
Configuration Jack  
Euro Type  
Connector Terminal  
1
2
3
4
5
6
ON  
ON  
COMMUNICATION CABLE CONNECTIONS  
HOST PC  
R3-NLx  
R3-NLx  
LONWORKS  
LONWORKS  
LONWORKS  
Terminator  
TRANSMISSION DATA DESCRIPTIONS  
The DIP SW located at the side of the module specifies each I/O module's data allocation (occupied data area).  
Data are assigned in turn from Slot 1, in order of Functional Blocks (Input or GetValue/R3Di first, followed by Output or  
SetValue/R3Do).  
The 1st output must be the 1st transmitted data in the slot next to the one with the last input data.  
[Example 1]  
Data Area  
Module 1  
Module 2  
Module 3  
Module 4  
Module 5  
Module 6  
Module 7  
Module 8  
Module 9  
Module 10  
4
4
4
1
1
1
1
1
1
1
GetValue [0 – 3]  
GetValue [4 – 7]  
SetValue [0]  
SetValue [1]  
SetValue [2]  
SetValue [3]  
SetValue [4]  
SetValue [5]  
SetValue [6]  
SetValue [7]  
[Example 2]  
Data Area  
Module 1  
Module 2  
Module 3  
Module 4  
Module 5  
Module 6  
1
4
4
1
4
4
GetValue [0]  
GetValue [1 – 4]  
GetValue [5 – 7] The 4th data, Slot 3 is invalid.  
SetValue [0]  
SetValue [1 – 4]  
SetValue [5 – 7] The 4th data, Slot 6 is invalid.  
When the data consist of only inputs or outputs, data for the total of 16 Functional Blocks (GetValue [0 – 15] or R3Di [0 – 2], or  
SetValue [0 – 15] or R3Do [0 – 2]) are assigned to each module position from Slot 1.  
R3-NL1 SPECIFICATIONS  
ES-8427 Rev.10 Page 3/5  
http://www.m-system.co.jp/  
MODEL: R3-NL1  
I/O COMBINATIONS  
A dedicated Device File for each I/O device depending upon I/O combinations is required using an integration tool such as Lon  
Maker.  
On-line download is available for Device Image files at M-System's homepage.  
Functional Blocks usable for respective files are not identical to all. Refer to the manual.  
ANALOG INPUT / OUTPUT  
NO. of DATA  
DEVICE IMAGE  
(APB FILE)  
USABLE FUNCTIONAL BLOCKS  
INPUT OUTPUT  
16  
12  
8
0
4
R3NL1_1_101.APB NodeObjet, GetValue [0 ... 15] (Can be defined from 0 to 15)  
R3NL1_2_101.APB NodeObjet, GetValue [0 ... 11], SetValue [0 ... 3]  
R3NL1_3_101.APB NodeObjet, GetValue [0 ... 7], SetValue [0 ... 7]  
R3NL1_4_101.APB NodeObjet, GetValue [0 ... 3], SetValue [0 ... 11]  
R3NL1_5_101.APB NodeObjet, SetValue [0 ... 15]  
8
4
12  
16  
0
DISCRETE INPUT / OUTPUT  
NO. of DATA  
DEVICE IMAGE  
(APB FILE)  
USABLE FUNCTIONAL BLOCKS  
INPUT OUTPUT  
0
48  
0
R3NL1_6_101.APB NodeObjet, R3Do [0 ... 2] (One (1) block can handle 16 contacts.)  
R3NL1_7_101.APB NodeObjet, R3Di [0 ... 2]  
48  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
27.5 (1.08)  
109 (4.29)  
POSITIONING  
GUIDE  
1
2
3
4
5
6–M3  
SCREW  
1
4
2
5
3
6
TERMINAL  
COVER  
R3-NL1 SPECIFICATIONS  
ES-8427 Rev.10 Page 4/5  
http://www.m-system.co.jp/  
MODEL: R3-NL1  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
Caution: FG terminal is NOT a protective conductor terminal.  
ONLINE/SERVICE LED RUN/ERR LED  
LONWORKS  
Control  
Circuit  
Communication  
Circuit  
1
2
3
4
5
INTERNAL BUS  
Transceiver  
FT-X1  
Neuron  
Chip  
FT3120  
DIP SW  
SERVICE SW  
RESET SW  
INTERNAL POWER  
1
4
2
3
6
RUN +  
RUN CONTACT OUTPUT  
5
RUN –  
*
U (+)  
*
POWER INPUT  
V (–)  
*
FG  
JACK  
*Not provided with ‘No Power Supply’ type module.  
CONFIGURATION JACK  
Specifications are subject to change without notice.  
R3-NL1 SPECIFICATIONS  
ES-8427 Rev.10 Page 5/5  
http://www.m-system.co.jp/  

相关型号:

R3-NL1-L3

Remote I/O R3 Series LonWorks INTERFACE MODULE
MSYSTEM

R3-NL1-L3/Q

Remote I/O R3 Series LonWorks INTERFACE MODULE
MSYSTEM

R3-NL1-R

Remote I/O R3 Series LonWorks INTERFACE MODULE
MSYSTEM

R3-NL1-R/Q

Remote I/O R3 Series LonWorks INTERFACE MODULE
MSYSTEM

R3-NL2

Remote I/O R3 Series LonWorks INTERFACE MODULE
MSYSTEM

R3-NL2-K3

Remote I/O R3 Series LonWorks INTERFACE MODULE
MSYSTEM

R3-NL2-K3/Q

Remote I/O R3 Series LonWorks INTERFACE MODULE
MSYSTEM

R3-NL2-L3

Remote I/O R3 Series LonWorks INTERFACE MODULE
MSYSTEM

R3-NL2-L3/Q

Remote I/O R3 Series LonWorks INTERFACE MODULE
MSYSTEM

R3-NL2-R

Remote I/O R3 Series LonWorks INTERFACE MODULE
MSYSTEM

R3-NL2-R/Q

Remote I/O R3 Series LonWorks INTERFACE MODULE
MSYSTEM

R3-NM1

Remote I/O R3 Series MODBUS INTERFACE MODULE
MSYSTEM