R3-NM3-L3/Q [MSYSTEM]

Remote I/O R3 Series MODBUS INTERFACE MODULE;
R3-NM3-L3/Q
型号: R3-NM3-L3/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R3 Series MODBUS INTERFACE MODULE

文件: 总7页 (文件大小:221K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R3-NM3  
Remote I/O R3 Series  
PACKAGE INCLUDES...  
• Terminating resistor (110 Ω, 0.25 W)  
MODBUS INTERFACE MODULE  
(For temperature control module)  
GENERAL SPECIFICATIONS  
Connection  
27.5 (1.08)  
Modbus: Euro type connector terminal  
(applicable wire size: 0.2 to 2.5 mm , stripped length 7 mm)  
2
Internal bus: Via the Installation Base  
(model: R3-BSx)  
130  
(5.12)  
Internal power: Via the Installation Base (model: R3-BSx)  
Power input, RUN contact output: M3 separable screw  
terminal (torque 0.5 N·m)  
109  
(4.29)  
Screw terminal: Nickel-plated steel  
mm (inch)  
Isolation: Modbus to internal bus or internal power to power  
input to RUN contact output to FG  
Input error data: Input value setting at input module error  
with side DIP SW  
MODEL: R3-NM3-[1][2]  
Main/Sub switching control in dual communication mode:  
Selectable with the side DIP SW (refer to the manual)  
Dual communication setting: Set with the side DIP switch  
Data allocation setting: Set with the side DIP switch  
RUN indicator: Bi-color (green/red) LED; Green ON in normal  
communication; Red ON when receiving data (Function  
selected with DIP SW)  
ORDERING INFORMATION  
• Code number: R3-NM3-[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. R3-NM3-R/Q)  
• Specify the specification for option code /Q  
(e.g. /C01/SET)  
ERR indicator: Bi-color (green/red) LED; Green blinking / ON  
(0.1 sec.) at communication or setting error; Red ON at  
transmitting data (Function selected with DIP SW)  
RUN CONTACT OUTPUT  
[1] POWER INPUT  
N: No power supply  
AC Power  
RUN contact: Turns ON while the green RUN LED is ON  
(Modbus in normal communication).  
K3: 100 – 120 V AC  
(Operational voltage range 85 - 132 V, 47 - 66 Hz) *  
L3: 200 – 240 V AC  
Rated load: 250 V AC @ 0.5 A (cos ø = 1)  
30 V DC @ 0.5 A (resistive load)  
(Operational voltage range 170 - 264 V, 47 - 66 Hz) *  
DC Power  
Maximum switching voltage: 250 V AC or 30 V DC  
Maximum switching power: 250 VA or 150 W  
Minimum load: 1 V DC @ 1 mA  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) *  
* Not selectable for use with independent power modules or  
network modules with the internal power input options.  
Mechanical life: 2 × 10 cycles (300 cycles/min.)  
7
When driving an inductive load, external contact protection  
and noise quenching recommended.  
[2] OPTIONS  
blank: none  
MODBUS COMMUNICATION  
RS-485  
/Q: With options (specify the specification)  
Standard: Conforms to TIA/EIA-485-A  
Transmission distance: 500 meters max.  
Transmission media: Shielded twisted-pair cable  
(CPEV-S 0.9 dia.)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
Transmission setting: DIP switch (front)  
Data: RTU (Binary) or ASCII  
/C02: Polyurethane coating  
Parity: None, even or odd  
/C03: Rubber coating  
Baud rate: 4800, 9600, 19.2 k, 38.4 k (bps)  
Node address: Rotary switch; 01 – F7  
EX-FACTORY SETTING  
/SET: Preset according to the Ordering Information Sheet  
(No. ESU-8354)  
R3-NM3 SPECIFICATIONS  
ES-8330 Rev.7 Page 1/7  
http://www.m-system.co.jp/  
MODEL: R3-NM3  
INSTALLATION  
Power consumption  
AC: Approx. 20 VA  
DC: Approx. 12 W  
Current consumption (no power supply): 100 mA  
Output current (power supply): 250 mA continuous at 20 V  
DC; 400 mA for 10 minutes  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R3-BSx)  
Weight: 200 g (0.44 lb)  
PERFORMANCE  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute (Modbus to  
internal bus or internal power to power input to RUN contact  
output to FG)  
EXTERNAL VIEW  
FRONT VIEW  
SIDE VIEW  
C
SA1  
SA2  
4
C
Node Address (MSD)  
Node Address (LSD)  
4
RUN LED  
ERR LED  
DIP SW  
SW3  
ON  
SW2  
SW1  
FG  
SLD  
DG  
DB  
DA  
DIP SW  
SW6  
4
3
2
1
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
Configuration Jack  
Euro Type  
8
7
6
5
4
3
2
1
Connector Terminal  
1
2
3
4
ON  
ON  
5
6
ON  
COMMUNICATION CABLE CONNECTIONS  
MODBUS  
INTERFACE  
MODULE  
MODBUS  
INTERFACE  
MODULE  
HOST PC  
TERMINATOR  
Tx+ / Rx+  
DA  
DB  
DA  
DB  
Tx– / Rx–  
SG  
DG  
SLD  
FG  
DG  
SLD  
FG  
Rx+  
Rx–  
FG  
FG  
R3-NM3 SPECIFICATIONS  
ES-8330 Rev.7 Page 2/7  
http://www.m-system.co.jp/  
MODEL: R3-NM3  
MODBUS FUNCTION CODES & SUPPORTED CODES  
Data & Control Functions  
CODE NAME  
01  
02  
03  
04  
05  
06  
07  
08  
09  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
Read Coil Status  
X
X
X
X
X
X
Digital output from the slave (read/write)  
Read Input Status  
Read Holding Registers  
Read Input Registers  
Force Single Coil  
Status of digital inputs to the slave (read only)  
General purpose register within the slave (read/write)  
Collected data from the eld by the slave (read only)  
Digital output from the slave (read/write)  
Preset Single Register  
Read Exception Status  
Diagnostics  
General purpose register within the slave (read/write)  
X
Program 484  
Poll 484  
Fetch Comm. Event Counter  
Fetch Comm. Event Log  
Program Controller  
Poll Controller  
X
X
Fetch a status word and an event counter  
A status word, an event counter, a message count and a eld of event bytes  
Force Multiple Coils  
Preset Multiple Registers  
Report Slave ID  
X
X
X
Digital output from the slave (read/write)  
General purpose register within the slave (read/write)  
Slave type / ‘RUN’ status  
Program 884/M84  
Reset Comm. Link  
Read General Reference  
Write General Reference  
Mask Write 4X Register  
Read/Write 4X Register  
Read FIFO Queue  
Exception Codes  
CODE NAME  
01  
02  
03  
04  
05  
06  
07  
08  
Illegal Function  
X
X
X
Function code is not allowable for the slave  
Address is not available within the slave  
Data is not valid for the function  
Illegal Data Address  
Illegal Data Value  
Slave Device Failure  
Acknowledge  
Slave Device Busy  
Negative Acknowledge  
Memory Parity Error  
Diagnostic Subfunctions  
CODE NAME  
00  
01  
02  
03  
04  
Return Query Data  
X
X
X
X
X
Loop back test  
Restart Comm. Option  
Return Diagnostic Register  
Change ASCII Input Delimiter  
Force Listen Only Mode  
Reset the slave and clear all counters  
Contents of the diagnostic data (2 bytes)  
Delimiter character of ASCII message  
Force the slave into Listen Only Mode  
R3-NM3 SPECIFICATIONS  
ES-8330 Rev.7 Page 3/7  
http://www.m-system.co.jp/  
MODEL: R3-NM3  
MODBUS I/O ASSIGNMENT  
ADDRESS  
1 – 1024  
DATA FORMAT NAME  
Digital Output (discrete output)  
Coil (0X)  
1025  
Main / Sub Switching Command (valid only with SW3-3 set to ON)  
Inputs (1X)  
1 – 1024  
Digital Input (discrete input)  
Module Status  
Error Status  
1025 – 1040  
1041 – 1056  
1057 – 1072  
1 – 256  
Data Error Status  
Analog Input  
Input Registers (3X)  
I
F
I
257 – 768  
1 – 256  
Analog Input  
Holding Registers (4X)  
Analog Output  
Analog Output  
Extension I/O  
257 – 768  
2001 – 50000  
F
I: Integer, 0 – 10000 (0 – 100%)  
F: Floating (32-bit data cannot be accessed using floating addresses.)  
Note: DO NOT access addresses other than mentioned above. Such access may cause problems such as inadequate operation.  
• Module Status indicates whether individual I/O modules are mounted or not. The bit corresponding to the mounted slot turns to  
“1,and the unmounted slot to “0.”  
• Error Status indicates error status for each module as described below. The bit corresponding to such module turns to “1.”  
R3-TSx, R3-RSx, R3-US4: Input burnout  
R3-DA16A:  
R3-YSx:  
R3-PC16A:  
Power input in error or disconnected  
Output current error (e.g. load unconnected)  
External power supply in error or disconnected  
• Data Error Status indicates overrange (R3-US4: out of -10% to +110%; the other types: out of -15% to +115%) status for each  
module. The bit corresponding to such module turns to “1.”  
• Main / Sub Switching Commands given to the network modules result as follows:  
‘MAIN’ MODULE  
‘SUB’ MODULE  
OUTPUT MODE  
1
0
1
0
0
1
1
0
Main bus is used; Red light turns on at RUN LED of the I/O modules.  
Sub bus is used; Green light turns on at RUN LED of the I/O modules.  
Main bus is used; Amber light turns on at RUN LED of the I/O modules.  
Output is invalid; RUN LED of the I/O modules turns off.  
• For Extension I/O, the mapping of 3000 words per each I/O module is available as shown in the table below.  
The mapping contents depends on each module characteristics; refer to each instruction manual.  
SLOT  
ADDRESS  
200 1 – 5000  
500 1 – 8000  
800 1 – 11000  
1100 1 – 14000  
:
1
2
3
4
:
14  
15  
4400 1 – 47000  
4700 1 – 50000  
R3-NM3 SPECIFICATIONS  
ES-8330 Rev.7 Page 4/7  
http://www.m-system.co.jp/  
MODEL: R3-NM3  
TRANSMISSION DATA DESCRIPTIONS  
The DIP SW located at the side of the module species each I/O module’s data allocation (occupied data area).  
For example, when the data areas are assigned as shown below:  
Module 1  
Module 2  
Module 3  
Module 4  
Module 5  
Module 6  
Module 7  
4
4
4
1
1
1
1
Then the I/O data are assigned as in the table below:  
ADDRESS POSITION  
1 – 4,  
ADDRESS  
1 – 64  
POSITION  
Slot 1  
Input Registers (3X)  
257 – 264  
265 – 272  
273 – 280  
281 – 282  
283 – 284  
285 – 286  
287 – 288  
Slot 1  
Slot 2  
Slot 3  
Slot 4  
Slot 5  
Slot 6  
Slot 7  
Coil (0X)  
Holding Registers (4X)  
Inputs (1X)  
5 – 8,  
9 – 12,  
13,  
65 – 128  
129 – 192  
193 – 208  
209 – 224  
225 – 240  
241 – 256  
Slot 2  
Slot 3  
Slot 4  
14,  
Slot 5  
15,  
Slot 6  
16,  
Slot 7  
For Coil (0X) and Inputs (1X), addresses 16 times assigned data  
areas (Data Allocation Type) are allotted with the Data Allocation  
Type ‘1’ and ‘4. With ‘8’ and ‘16,’ 64 (4 × 16) are automatically al-  
lotted.  
MODULE STATUS, ERROR STATUS, DATA ERROR STATUS  
Shows each module's availability and error status.  
15  
0
Module 1  
Module 2  
Module 3  
:
Module 16  
I/O DATA DESCRIPTIONS  
The data allocations for typical I/O modules are shown below.  
Refer to the manual for each module for detailed data allocations.  
■ ANALOG DATA (16-bit data, models: R3-SV4, YV4, DS4, YS4, US4, etc.)  
16-bit binary data.  
Basically, 0 to 100% of the selected I/O range is converted into 0 to 10000 (binary).  
-15 to 0 % is a negative range represented in 2’s complement.  
In case of R3-US4, -10 to 0% is a negative range represented in 2's complement.  
15  
0
R3-NM3 SPECIFICATIONS  
ES-8330 Rev.7 Page 5/7  
http://www.m-system.co.jp/  
MODEL: R3-NM3  
■ TEMPERATURE DATA (16-bit data, models: R3-RS4, TS4, US4, etc.)  
16-bit binary data.  
With °C temperature unit, raw data is multiplied by 10. For example, 25.5°C is converted into 255.  
With °F temperature unit, the integer section of raw data is directly converted into the data.  
For example, 135.4°F is converted into 135.  
Minus temperature is converted into negative values, represented in 2’s complements.  
15  
0
■ ANALOG DATA (16-bit data, models: R3-CT4A, CT4B, etc.)  
16-bit binary data.  
Integer obtained by multiplying unit value (A) by 100.  
In case of CLSE-R5, integer obtained by multiplying unit value (A) by 1000.  
15  
0
■ ACCUMULATED COUNT DATA (32-bit data, models: R3-PA2, PA4A, WT1, WT4, etc.)  
32-bit binary data is used for accumulated counts and encoder positions.  
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.  
32-bit data cannot be accessed using oating addresses.  
15  
0
+0  
+1  
Lower 16 bits  
Higher 16 bits  
15  
0
■ BCD DATA (32-bit data, models: R3-BA32A, BC32A, etc.)  
32-bit binary data is used for BCD.  
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.  
32-bit data cannot be accessed using oating addresses.  
15  
0
+0  
+1  
Lower 16 bits  
Higher 16 bits  
15  
0
■ 16-POINT DISCRETE DATA (models: R3-DA16, DC16, etc.)  
15  
0
Input 1 (Output 1)  
Input 2 (Output 2)  
Input 3 (Output 3)  
:
:
Input 16 (Output 16)  
0 : OFF  
1 : ON  
R3-NM3 SPECIFICATIONS  
ES-8330 Rev.7 Page 6/7  
http://www.m-system.co.jp/  
MODEL: R3-NM3  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
27.5 (1.08)  
109 (4.29)  
POSITIONING  
GUIDE  
6–M3  
SCREW  
1
4
2
5
3
6
TERMINAL  
COVER  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
Caution: FG terminal is NOT a protective conductor terminal.  
LED ROTARY SW  
FG  
Isolation  
SLD  
To Other  
Modbus  
Devices  
Control  
Circuit  
Communication  
Circuit  
DG  
DB  
DA  
INTERNAL BUS  
DIP SW  
RUN +  
1
INTERNAL POWER  
RUN CONTACT OUTPUT  
RUN –  
4
*
U (+) 2  
V (–) 3  
*
5
*
POWER INPUT  
FG  
6
JACK  
CONFIGURATION JACK  
*Not provided with ‘No Power Supply’ type module.  
Specifications are subject to change without notice.  
R3-NM3 SPECIFICATIONS  
ES-8330 Rev.7 Page 7/7  
http://www.m-system.co.jp/  

相关型号:

SI9130DB

5- and 3.3-V Step-Down Synchronous Converters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1-E3

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135_11

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9136_11

Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130CG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130LG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130_11

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137DB

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137LG

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9122E

500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification Drivers

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY