MODEL: R3S-RR8
/C03: Rubber coating
Remote I/O R3 Series
RELATED PRODUCTS
• Interface Module (model: R3-NC1, NC3, NE1, NM1, NDx,
REMOTE CONTROL RELAY CONTROL MODULE
(Do 8 points, tension clamp terminal block)
Functions & Features
NF2, NFL1)
Firmware version V2.00 or higher.
• Controls remote control relays for lighting control with
Fieldbus
R3-NF2 is available with firmware version V0.04 or higher.
• Applicable to the remote control relays already installed
• Monitors status of remote control relays with feedback
inputs from signal lines
GENERAL SPECIFICATIONS
Connection
Internal bus: Via the Installation Base (model: R3-BSx)
Output: Separable tension clamp terminal (applicable wire
Typical Applications
• Monitors and controls of lighting in buildings
size: 0.2 to 1.5 mm , stripped length 10 mm)
2
Internal power: Via the Installation Base (model: R3-BSx)
Isolation: Output to internal bus or internal power
Input Data Length: 8 bit, 16 bit selectable with DIP switch
Output data length: 8 bit, 16 bit selectable with DIP switch
RUN indicator: Bi-color (red/green) LED;
27.5 (1.08)
130 (5.12)
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Green LED;
120 (4.72)
mm (inch)
OFF in abnormality; ON in normal operating conditions.
Input output status indicator: Red LED;
1 to 8: Output bit status, turns on with bit set ON.
9 to 16: Feedback input status, turns on with the input ON.
MODEL: R3S-RR8[1][2]
OUTPUT SPECIFICATIONS
Number of output: 8 points
ORDERING INFORMATION
• Code number: R3S-RR8[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3S-RR8W/Q)
Common: All 8 points (12 terminal)
Rated load voltage: 24 V AC ±10 % (supplied by the remote
control transformer)
• Specify the specification for option code /Q
(e.g. /C01)
Load voltage frequency: 50 / 60 Hz
Maximum outputs provided at once: No limit
Output ON duration: 100 msec.
NO. OF CHANNELS
8: 8
INSTALLATION
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)
[1] COMMUNICATION MODE
S: Single
W: Dual
[2] OPTIONS
blank: none
PERFORMANCE
Data allocation: 1
/Q: Options other than the above (specify the specification)
Current consumption: 40 mA
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(output to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
R3S-RR8 SPECIFICATIONS
ES-8934 Rev.3 Page 1/5
http://www.m-system.co.jp/
MODEL: R3S-RR8
power supply module)
EXTERNAL VIEW
■
FRONT VIEW
■ SIDE VIEW
RUN LED
Status Indicator LED
ERR LED
Functions
1
SW3
Output Data Bit
Input Data Bit
4
3
2
1
ON
20
EXTERNAL DIMENSIONS unit: mm (inch)
120 (4.72)
109 (4.29)
27.5 (1.08)
POSITIONING
GUIDE
1
20
R3S-RR8 SPECIFICATIONS
ES-8934 Rev.3 Page 2/5
http://www.m-system.co.jp/
MODEL: R3S-RR8
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
RUN LED ERR LED STATUS
INDICATOR LED
DIP SW
Output Circuit
1
2
3
4
5
6
7
8
1
3
red
OUTPUT 1
OUTPUT 2
OUTPUT 3
OUTPUT 4
OUTPUT 5
OUTPUT 6
OUTPUT 7
OUTPUT 8
COM
Remote Control
Relay
blue
INTERNAL BUS A
Comm.
Circuit
red
Remote Control
Relay
5
INTERNAL BUS B*
blue
7
red
Remote Control
Relay
9
INTERNAL POWER
blue
11
13
15
2
red
Remote Control
Relay
blue
red
Remote Control
Relay
Control
Circuit
blue
red
Remote Control
Relay
4
blue
COM
6
COM
red
Remote Control
Relay
blue
8
COM
red
Remote Control
Relay
10
12
14
16
18
20
17
19
COM
blue
COM
COM
blue
Remote Control
Transformer
COM
white
COM
blue
Remote Control
Transformer
COM
white
COM
COM
Numbers in italic indicate LED No.s assigned to the front panel LEDs.
* For dual redundant communication.
OUTPUT TERMINAL ASSIGNMENT
PIN No.
1
FUNCTION
Do 1
2
COM
Do 2
3
4
COM
Do 3
5
6
COM
Do 4
7
8
COM
Do 5
9
10
11
12
13
14
15
16
17
18
19
20
COM
Do 6
COM
Do 7
COM
Do 8
COM
COM
COM
COM
COM
R3S-RR8 SPECIFICATIONS
ES-8934 Rev.3 Page 3/5
http://www.m-system.co.jp/
MODEL: R3S-RR8
INPUT OUTPUT DATA BIT & DATA ALLOCATION
■ OUTPUT DATA BIT: 16 BITS (SW3-4: OFF)
When output data bit is 16 bits, set each output with 2
bits.
■ OUTPUT DATA BIT: 8 BITS (SW3-4: ON)
When output data bit is 8 bits, set each output with 1 bit.
The table below shows data allocation.
The table below shows data allocation.
BIT
SETTING
0
OPERATION
Output 1 OFF
BIT
SETTING
0, 0
OPERATION
0
No operation
Output 1 ON
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
-
Output 1 ON
Output 2 OFF
Output 2 ON
Output 3 OFF
Output 3 ON
Output 4 OFF
Output 4 ON
Output 5 OFF
Output 5 ON
Output 6 OFF
Output 6 ON
Output 7 OFF
Output 7 ON
Output 8 OFF
Output 8 ON
Unused
1, 0
0, 1
1, 1
0, 0
1, 0
0, 1
1, 1
0, 0
1, 0
0, 1
1, 1
0, 0
1, 0
0, 1
1, 1
0, 0
1, 0
0, 1
1, 1
0, 0
1, 0
0, 1
1, 1
0, 0
1, 0
0, 1
1, 1
0, 0
1, 0
0, 1
1, 1
0, 1
1
2
3
4
5
6
7
Output 1 OFF
Output 1 RESET
No operation
Output 2 ON
2, 3
Output 2 OFF
Output 2 RESET
No operation
Output 3 ON
4, 5
Output 3 OFF
Output 3 RESET
No operation
Output 4 ON
6, 7
Output 4 OFF
Output 4 RESET
No operation
Output 5 ON
8
-
Unused
9
-
Unused
10
11
12
13
14
15
8, 9
Output 5 OFF
Output 5 RESET
No operation
Output 6 ON
-
Unused
-
Unused
-
Unused
-
Unused
10, 11
12, 13
14, 15
Output 6 OFF
Output 6 RESET
No operation
Output 7 ON
-
Unused
ON (or OFF) cannot be set consecutively, because when each
bit is “1”, ON is set and when each bit is “0”, OFF is set.
Output 7 OFF
Output 7 RESET
No operation
Output 8 ON
Output 8 OFF
Output 8 RESET
By set t ing wi th 2 bi ts, the module operates as shown above.
ON or OFF can be set consecutively. To output ON twice
successively, set ON (1, 0), RESET (1, 1), and then set ON
(1, 0) again.
R3S-RR8 SPECIFICATIONS
ES-8934 Rev.3 Page 4/5
http://www.m-system.co.jp/
MODEL: R3S-RR8
■ INPUT DATA BIT: 16 BITS (SW3-3: ON)
When output data bit is 16 bits, display the status of feedback
input for each output with 2 bits.
■ INPUT DATA BIT: 8 BITS (SW3-3: OFF)
When output data bit is 8 bits, display the status of feedback
input for each output with 1 bit.
The table below shows data allocation.
The table below shows data allocation.
BIT
DISPLAY
0
OPERATION
BIT
DISPLAY
0
OPERATION
Feedback input for output 1 OFF
Feedback input for output 1 OFF
0
0
1
-
Feedback input for output 1 ON
Reserved
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
-
Feedback input for output 1 ON
Feedback input for output 2 OFF
Feedback input for output 2 ON
Feedback input for output 3 OFF
Feedback input for output 3 ON
Feedback input for output 4 OFF
Feedback input for output 4 ON
Feedback input for output 5 OFF
Feedback input for output 5 ON
Feedback input for output 6 OFF
Feedback input for output 6 ON
Feedback input for output 7 OFF
Feedback input for output 7 ON
Feedback input for output 8 OFF
Feedback input for output 8 ON
Unused
1
1
2
3
4
5
6
7
0
1
-
Feedback input for output 2 OFF
Feedback input for output 2 ON
Reserved
2
3
0
1
-
Feedback input for output 3 OFF
Feedback input for output 3 ON
Reserved
4
5
0
1
-
Feedback input for output 4 OFF
Feedback input for output 4 ON
Reserved
6
7
0
1
-
Feedback input for output 5 OFF
Feedback input for output 5 ON
Reserved
8
9
0
1
-
Feedback input for output 6 OFF
Feedback input for output 6 ON
Reserved
10
11
12
13
14
15
8
-
Unused
9
0
1
-
Feedback input for output 7 OFF
Feedback input for output 7 ON
Reserved
-
Unused
10
11
12
13
14
15
-
Unused
-
Unused
0
1
-
Feedback input for output 8 OFF
Feedback input for output 8 ON
Reserved
-
Unused
-
Unused
-
Unused
Specifications are subject to change without notice.
R3S-RR8 SPECIFICATIONS
ES-8934 Rev.3 Page 5/5
http://www.m-system.co.jp/
相关型号:
SI9130DB
5- and 3.3-V Step-Down Synchronous ConvertersWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1-E3
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135_11
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9136_11
Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130CG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130LG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130_11
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137DB
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137LG
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9122E
500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification DriversWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
©2020 ICPDF网 联系我们和版权申明