R3S-SS8NS/Q [MSYSTEM]

Remote I/O R3 Series DC CURRENT INPUT MODULE;
R3S-SS8NS/Q
型号: R3S-SS8NS/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R3 Series DC CURRENT INPUT MODULE

输入元件
文件: 总4页 (文件大小:146K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R3S-SS8N  
Remote I/O R3 Series  
CAUTION  
UNUSED INPUT CHANNELS  
Set the unused channels to “Unused” with PC Configurator  
software: R3CON. Unused channels left open may be equal  
to the input lower than -15%, which sets a data abnormality  
at the PLC or the host device.  
DC CURRENT INPUT MODULE  
(8 points, non-isolated, tension clamp terminal block)  
27.5 (1.08)  
GENERAL SPECIFICATIONS  
Connection  
130 (5.12)  
Internal bus: Via the Installation Base (model: R3-BSx)  
Input: Separable tension clamp terminal (applicable wire  
size: 0.2 to 1.5 mm , stripped length 10 mm)  
2
120 (4.72)  
Internal power: Via the Installation Base (model: R3-BSx)  
Isolation: Input 1 or input 2 or input 3 or input 4 or input 5  
or input 6 or input 7 or input 8 to internal bus or internal  
power  
mm (inch)  
MODEL: R3S-SS8N[1][2]  
Conversion rate: Selectable with the side DIP SW  
RUN indicator: Bi-color (red/green) LED;  
Red when the bus A operates normally;  
Green when the bus B operates normally;  
Amber when both buses operate normally.  
ERR indicator: Bi-color (red/green) LED;  
Red with input circuit abnormality (AD converter response  
failure);  
ORDERING INFORMATION  
• Code number: R3S-SS8N[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. R3S-SS8NW/Q)  
• Specify the specification for option code /Q  
(e.g. /C01/SET)  
Green in normal operating conditions.  
NO. OF CHANNELS  
8: 8  
INPUT SPECIFICATIONS  
DC Current: 4 – 20 mA DC  
Input resistance: 250 Ω resistor incorporated  
ISOLATION  
N: Non-isolated between inputs  
INSTALLATION  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R3-BSx)  
Weight: 200 g (0.44 lb)  
[1] COMMUNICATION MODE  
S: Single  
W: Dual  
[2] OPTIONS  
blank: none  
PERFORMANCE  
Conversion accuracy: Refer to the table at the end of this  
/Q: With options (specify the specification)  
section.  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
Conversion rate: 160 / 80 / 40 / 20 msec. selectable  
Data range: 0 – 10000  
Data allocation: 8  
/C02: Polyurethane coating  
Current consumption: 60 mA  
/C03: Rubber coating  
Temp. coefficient: ±0.02 %/°C (±0.01 %/°F)  
Response time: ≤ 0.2 sec. (0 – 90 %)  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute  
(input 1 or input 2 or input 3 or input 4 or input 5 or input 6  
or input 7 or input 8 to internal bus or internal power)  
EX-FACTORY SETTING  
/SET: Preset according to the Ordering Information Sheet  
(No. ESU-8406)  
R3S-SS8N SPECIFICATIONS  
ES-8938 Rev.4 Page 1/4  
http://www.m-system.co.jp/  
MODEL: R3S-SS8N  
2000 V AC @ 1 minute (power input to FG; isolated on the  
power supply module)  
Conversion accuracy  
RATE  
160 msec. 80 msec. 40 msec. 20 msec.  
RANGE  
4 – 20mA  
0.05%  
0.1%  
0.2%  
0.4%  
EXTERNAL VIEW  
FRONT VIEW  
SIDE VIEW  
RUN LED  
ERR LED  
21  
1
SW3  
4
3
2
Conv.  
Rate  
1
ON  
40  
20  
EXTERNAL DIMENSIONS unit: mm (inch)  
120 (4.72)  
109 (4.29)  
27.5 (1.08)  
POSITIONING  
GUIDE  
21  
1
40  
20  
R3S-SS8N SPECIFICATIONS  
ES-8938 Rev.4 Page 2/4  
http://www.m-system.co.jp/  
MODEL: R3S-SS8N  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
RUN LED ERR LED  
DIP SW  
Input Circuit  
1
2
+
INTERNAL BUS A  
Comm.  
Circuit  
INPUT 1  
INPUT 2  
INPUT 3  
INPUT 4  
INPUT 5  
INPUT 6  
INPUT 7  
INPUT 8  
250Ω  
250Ω  
250Ω  
250Ω  
250Ω  
250Ω  
250Ω  
250Ω  
INTERNAL BUS B*1  
3
4
+
INTERNAL POWER  
9
5
6
+
10  
19  
20  
21  
23  
25  
27  
29  
30  
31  
33  
35  
37  
40  
7
8
+
Control  
Circuit  
11  
12  
+
13  
14  
+
15  
16  
+
17  
18  
+
22  
24  
26  
28  
32  
34  
36  
38  
39  
SLD  
SLD  
SLD  
SLD  
SLD  
SLD  
SLD  
SLD  
SLD  
*2  
*1. For dual redundant communication.  
*2. To use shield line, connect it to SLD terminal and ground the terminal 39.  
Note: Do not use void terminals.  
R3S-SS8N SPECIFICATIONS  
ES-8938 Rev.4 Page 3/4  
http://www.m-system.co.jp/  
MODEL: R3S-SS8N  
INPUT TERMINAL ASSIGNMENT  
PIN No.  
21  
FUNCTON  
NC  
PIN No.  
1
FUNCTON  
I1  
22  
SLD  
NC  
2
COM  
I2  
23  
3
24  
SLD  
NC  
4
COM  
I3  
25  
5
26  
SLD  
NC  
6
COM  
I4  
27  
7
28  
SLD  
NC  
8
COM  
NC  
NC  
29  
9
30  
NC  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
31  
NC  
I5  
32  
SLD  
NC  
COM  
I6  
33  
34  
SLD  
NC  
COM  
I7  
35  
36  
SLD  
NC  
COM  
I8  
37  
38  
SLD  
SLD  
NC  
COM  
NC  
39  
40  
NC  
Specifications are subject to change without notice.  
R3S-SS8N SPECIFICATIONS  
ES-8938 Rev.4 Page 4/4  
http://www.m-system.co.jp/  

相关型号:

R3S-SS8NW

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM

R3S-SS8NW/Q

Remote I/O R3 Series DC CURRENT INPUT MODULE
MSYSTEM

R3S-SV8NS

Remote I/O R3 Series DC VOLTAGE INPUT MODULE
MSYSTEM

R3S-SV8NS/Q

Remote I/O R3 Series DC VOLTAGE INPUT MODULE
MSYSTEM

R3S-SV8NW

Remote I/O R3 Series DC VOLTAGE INPUT MODULE
MSYSTEM

R3S-SV8NW/Q

Remote I/O R3 Series DC VOLTAGE INPUT MODULE
MSYSTEM

R3S-YS4S

Remote I/O R3 Series DC CURRENT OUTPUT MODULE
MSYSTEM

R3S-YS4S/H

Remote I/O R3 Series DC CURRENT OUTPUT MODULE
MSYSTEM

R3S-YS4S/Q

Remote I/O R3 Series DC CURRENT OUTPUT MODULE
MSYSTEM

R3S-YS4W

Remote I/O R3 Series DC CURRENT OUTPUT MODULE
MSYSTEM

R3S-YS4W/H

Remote I/O R3 Series DC CURRENT OUTPUT MODULE
MSYSTEM

R3S-YS4W/Q

Remote I/O R3 Series DC CURRENT OUTPUT MODULE
MSYSTEM