R3Y-PA16 [MSYSTEM]

Remote I/O R3 Series TOTALIZED PULSE INPUT MODULE;
R3Y-PA16
型号: R3Y-PA16
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R3 Series TOTALIZED PULSE INPUT MODULE

输入元件
文件: 总6页 (文件大小:146K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R3Y-PA16  
/C03: Rubber coating  
Remote I/O R3 Series  
EX-FACTORY SETTING  
/SET: Preset according to the Ordering Information Sheet  
(No. ESU-8389)  
TOTALIZED PULSE INPUT MODULE  
(Pi 16 points, connector type)  
27.5 [1.08]  
RELATED PRODUCTS  
• Connector terminal block (model: CNT)  
• Special cable with 40-pin connector (model: FCN)  
• Interface module (model: R3-NC1, R3-NC3, R3-NE1,  
R3-NM1, R3-NDx, R3-NFL1, R3-NP1, R3-NFx, R3-NML3.  
R3-NF2: Firmware version V0.05 or later)  
Note:  
130  
[5.12]  
109  
[4.29]  
• Count reset by host PC/PLC:  
mm [inch]  
Available with this unit and the above mentioned interface  
modules of firmware version V2.00 or later, except R3-NFx.  
Notice that Count reset by host PC/PLC via R3-NFx or  
interface module of previous versions of firmware is unable.  
• Count preset by host PC/PLC:  
MODEL: R3Y–PA16[1][2]  
ORDERING INFORMATION  
• Code number: R3Y-PA16[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. R3Y-PA16W/A/CE/PRS/Q)  
It is only available in combination with this unit displayed  
'SW3-4 RESET/PRESET' on the right side panel and the  
interface module R3-NM1 or R3-NE1 of firmware version  
V2.00 or later. Count preset is not available for other  
combination.  
• Specify the specification for option code /Q  
(e.g. /C01/SET)  
Notice that this function is not available in the same time as  
count preset by host PC/PLC.  
NO. OF CHANNELS  
16: 16  
GENERAL SPECIFICATIONS  
Connection  
Internal bus: Via the Installation Base (model: R3-BSx)  
Input: 40-pin connector (Fujitsu Model FCN-365P040-AU)  
Internal power: Via the Installation Base (model: R3-BSx)  
Isolation: Input to internal bus or internal power  
RUN indicator: Bi-color (red/green) LED;  
Red when the bus A operates normally;  
Green when the bus B operates normally;  
Amber when both buses operate normally.  
ERR indicator: Bi-color (red/green) LED;  
Red with excitation abnormality;  
[1] COMMUNICATION MODE  
S: Single  
W: Dual  
[2] OPTIONS (multiple selections)  
Excitation  
Blank: Internal (negative common)  
/A: External (24 V DC, negative common)  
Standards & Approvals  
blank: Without CE  
Green in normal operating conditions.  
/CE: CE marking  
Input status indicator: Red LED; turns on with the input ON.  
Count reset: Via DIP switch on the side or one pulse to reset  
input  
EX-FACTORY SETTING  
blank: Enable count reset by host PC/PLC  
/PRS: Enable count preset by host PC/PLC  
Other Options  
Count setting from host PC/PLC: Count reset/count preset is  
changeable via DIP switch on the side.  
blank: none  
/Q: Option other than the above (specify the specification)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
/C02: Polyurethane coating  
R3Y-PA16 SPECIFICATIONS  
ES-8962 Rev.7 Page 1/6  
https://www.m-system.co.jp/  
MODEL: R3Y-PA16  
INPUT SPECIFICATIONS  
FUNCTIONS  
Number of input: 16 points  
MANUAL COUNT RESET  
Input resistance: 6 kΩ  
1) Remove Network Module or its cables and interrupt  
communication with other devices.  
Common: Negative commons, all points  
Maximum frequency: 100 Hz (ON/OFF time ≥ 5 msec.)  
This unit is designed to be able to accept a frequency up to  
100 Hz, however, ‘chattering’ contact must be avoided for  
accurate measuring of such high frequency. Use mercury  
relays or similar ones that do not cause any chattering.  
Totalized pulse range: 1 – 10000 (‘0’ at reset)  
Max. pulse range selectable from 1 to 65535 using the  
R3CON PC Configurator Software. Refer to the R3CON Users  
Manual for detailed information.  
2) Turn ON the Count Reset SW (SW3-1).  
3) Return the module to the base and turn the power supply  
on.  
4) ERR LED turns on and the module starts resetting its  
counter. When the resetting is complete, the LED turns to  
green. DO NOT remove the power while the red LED is  
on.The RUN LED starts blinking at the same time.  
5) After the green LED is confirmed, turn the power supply  
off.  
Count at overflow: Reset and restart at ‘1.’  
R3Y-PA16x (internal excitation)  
6) Turn OFF the Count Reset SW (SW3-1).  
7) Return the Network module onto the base and turn the  
power supply on.  
Sensing voltage: 13 V DC (max. 24 V with no load)  
ON current: ≥ 1.5 mA (≤ 1.5 kΩ)  
Note: Count Reset SW must be turned OFF after this  
procedure because the module does not start counting with  
ON state.  
OFF current: ≤ 0.75 mA (≥ 18 kΩ)  
R3Y-PA16x/A (external excitation)  
Sensing voltage: 24 V DC  
REMOTE COUNT RESET INPUT  
ON current: ≥ 1.5 mA (≤ 12 kΩ)  
With the Count Reset Input SW (SW3-3) turned ON, the  
count reset signal value becomes effective.  
SW3-3 = OFF: unused  
OFF current: ≤ 0.75 mA (≥ 36 kΩ)  
SW3-3 = ON: reset signal.  
INSTALLATION  
One pulse supplied at the Count reset input terminal will be  
recognized as a reset signal.  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R3-BSx)  
Weight: 200 g (0.44 lb)  
REMOTE COUNT RESET OPERATION  
1) ERR LED turns on (red color) when the reset signal is  
received.  
2) In 1 second, the module starts resetting its counter.  
When the resetting is complete, the LED turns to green.  
3) After 1 second, ERR LED turns back to the state before  
the reset signal has been received.  
PERFORMANCE  
Data allocation: 16  
Current consumption:  
Note: Reset signals received while the module is processing  
(1) through (3) are ignored.  
R3Y-PA16x: 100 mA  
R3Y-PA16x/A: 80 mA  
COUNT RESET FROM HOST PC/PLC  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @ 1 minute  
(input to internal bus or internal power)  
2000 V AC @ 1 minute (power input to FG; isolated on the  
power supply module)  
Refer to “COUNTER SETTING FROM HOST PC/PLC” section  
hereafter.  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
RoHS Directive  
R3Y-PA16 SPECIFICATIONS  
ES-8962 Rev.7 Page 2/6  
https://www.m-system.co.jp/  
MODEL: R3Y-PA16  
EXTERNAL VIEW  
FRONT VIEW  
SIDE VIEW  
RUN LED  
ERR LED  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
Input Status Indicator LEDs  
• Pin Assignment  
Functions  
B A  
20 20  
Input Connector  
SW3  
Count Setting  
from Host PC/PLC  
4
Count Reset Input  
3
2
1
Count Reset  
ON  
Set the Count Reset SW to OFF to start counting.  
B
A
1
1
R3Y-PA16 SPECIFICATIONS  
ES-8962 Rev.7 Page 3/6  
https://www.m-system.co.jp/  
MODEL: R3Y-PA16  
COUNTER SETTING FROM HOST PC/PLC  
COUNTER RESET  
(Available for R3-NC1, R3-NC3, R3-NE1, R3-NM1, R3-NDx, R3-NFL1, R3-NP1, R3-NML3 (Firmware version 2.00 or later))  
Setting SW3-4 OFF and turning power on enable the function.  
The bits indicating the channels to reset counter are allocated in the rst word from host PC/PLC.  
When these bits are changed from 0 to 1, the counter is reset. When it is conrmed that the counter is reset, return to 0.  
Notice that if the bit remains at 1, the next reset will not work.  
15  
0
Count reset CH.1  
Count reset CH.2  
Count reset CH.3  
Count reset CH.4  
Count reset CH.16  
COUNTER PRESET  
(Available in combination with R3-NE1, R3-NM1 (Firmware version 2.00 or later), and R3Y-PA16 displayed ‘SW3-4 RESET/PRESET’  
on the right side)  
Setting SW3-4 ON and turning power on enable the function.  
Write the preset value to the Holding Resisters, which has same address as the Input Resisters.  
• Input Resisters  
• Holding Resisters  
Address  
n+0  
Address  
n+0  
Preset value of Input 1  
Preset value of Input 2  
Preset value of Input 3  
Preset value of Input 4  
Input 1  
Input 2  
Input 3  
n+1  
n+1  
n+2  
n+2  
n+3  
Input 4  
n+3  
n+14  
n+15  
n+14  
n+15  
Preset value of Input 15  
Preset value of Input 16  
Input 15  
Input 16  
R3Y-PA16 SPECIFICATIONS  
ES-8962 Rev.7 Page 4/6  
https://www.m-system.co.jp/  
MODEL: R3Y-PA16  
EXTERNAL DIMENSIONS unit: mm [inch]  
27.5 [1.08]  
109 [4.29]  
POSITIONING  
GUIDE  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
INTERNAL POWER  
EXTERNAL EXCITATION (OPTION /A)  
STATUS  
RUN LED ERR LED INDICATOR LED  
Input Circuit  
Input Circuit  
INTERNAL  
BUS A  
1
2
1
2
Communication  
Circuit  
Pi 1 20A/20B  
Pi 2 18A/18B  
Pi 3 16A/16B  
Pi 4 14A/14B  
Pi 5 12A/12B  
Pi 6 10A/10B  
Pi 7 8A/8B  
Pi 8 6A/6B  
Pi 9 19A/19B  
Pi 10 17A/17B  
Pi 11 15A/15B  
Pi 12 13A/13B  
Pi 13 11A/13B  
Pi 14 9A/9B  
Pi 15 7A/7B  
Pi 16 5A/5B  
4A/4B  
Pi 1 20A/20B  
Pi 2 18A/18B  
Pi 3 16A/16B  
Pi 4 14A/14B  
Pi 5 12A/12B  
Pi 6 10A/10B  
Pi 7 8A/8B  
INTERNAL  
BUS B*  
Control  
Circuit  
3
3
INTERNAL  
POWER  
4
4
5
5
DIP SW  
6
6
7
7
8
8
Pi 8 6A/6B  
9
9
Pi 9 19A/19B  
Pi 10 17A/17B  
Pi 11 15A/15B  
Pi 12 13A/13B  
Pi 13 11A/13B  
Pi 14 9A/9B  
Pi 15 7A/7B  
Pi 16 5A/5B  
10  
11  
12  
13  
14  
15  
16  
10  
11  
12  
13  
14  
15  
16  
COM(+)  
4A/4B  
+24V  
**  
3A/3B  
3A/3B  
2A/2B  
1A/1B  
0V  
0V  
2A/2B  
1A/1B  
Numbers in italic indicate LED No.s assigned to the front panel LEDs.  
For dual redundant communication.  
*
**DO NOT use the pin No. 4A/4B and 3A/3B.  
R3Y-PA16 SPECIFICATIONS  
ES-8962 Rev.7 Page 5/6  
https://www.m-system.co.jp/  
MODEL: R3Y-PA16  
INPUT CONNECTOR (40-pin)  
PIN NO.  
ASSIGNMENT  
PIN NO.  
ASSIGNMENT  
1A  
2A  
3A  
0V  
0V  
1B  
2B  
3B  
0V  
0V  
+24V  
+24V  
4A  
5A  
6A  
+24V  
Pi 16  
Pi 8  
4B  
5B  
6B  
+24V  
Pi 16  
Pi 8  
7A  
8A  
9A  
Pi 15  
Pi 7  
7B  
8B  
9B  
Pi 15  
Pi 7  
Pi 14  
Pi 14  
10A  
11A  
12A  
Pi 6  
Pi 13  
Pi 5  
10B  
11B  
12B  
Pi 6  
Pi 13  
Pi 5  
13A  
14A  
15A  
Pi 12  
Pi 4  
13B  
14B  
15B  
Pi 12  
Pi 4  
Pi 11  
Pi 11  
16A  
17A  
18A  
Pi 3  
Pi 10  
Pi 2  
16B  
17B  
18B  
Pi 3  
Pi 10  
Pi 2  
19A  
20A  
Pi 9  
Pi 1  
19B  
20B  
Pi 9  
Pi 1  
Specifications are subject to change without notice.  
R3Y-PA16 SPECIFICATIONS  
ES-8962 Rev.7 Page 6/6  
https://www.m-system.co.jp/  

相关型号:

R3Y-PA16S

Remote I/O R3 Series TOTALIZED PULSE INPUT MODULE
MSYSTEM

R3Y-PA16S/A

Remote I/O R3 Series TOTALIZED PULSE INPUT MODULE
MSYSTEM

R3Y-PA16S/CE

Remote I/O R3 Series TOTALIZED PULSE INPUT MODULE
MSYSTEM

R3Y-PA16S/Q

Remote I/O R3 Series TOTALIZED PULSE INPUT MODULE
MSYSTEM

R3Y-PA16W

Remote I/O R3 Series TOTALIZED PULSE INPUT MODULE
MSYSTEM

R3Y-PA16W/A

Remote I/O R3 Series TOTALIZED PULSE INPUT MODULE
MSYSTEM

R3Y-PA16W/CE

Remote I/O R3 Series TOTALIZED PULSE INPUT MODULE
MSYSTEM

R3Y-PA16W/Q

Remote I/O R3 Series TOTALIZED PULSE INPUT MODULE
MSYSTEM

R3Y-RS8

Remote I/O R3 Series RTD INPUT MODULE
MSYSTEM

R3Y-RS8S

Remote I/O R3 Series RTD INPUT MODULE
MSYSTEM

R3Y-RS8S/CE

Remote I/O R3 Series RTD INPUT MODULE
MSYSTEM

R3Y-RS8S/Q

Remote I/O R3 Series RTD INPUT MODULE
MSYSTEM