R3Y-YV8 [MSYSTEM]

Remote I/O R3 Series DC VOLTAGE OUTPUT MODULE;
R3Y-YV8
型号: R3Y-YV8
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R3 Series DC VOLTAGE OUTPUT MODULE

输出元件
文件: 总4页 (文件大小:119K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R3Y-YV8  
Remote I/O R3 Series  
RELATED PRODUCTS  
• Connector terminal block (model: CNT)  
• Special cable with 40-pin connector (model: FCN)  
DC VOLTAGE OUTPUT MODULE  
(8 points, isolated, connector type)  
GENERAL SPECIFICATIONS  
Connection  
27.5 [1.08]  
Internal bus: Via the Installation Base (model: R3-BSx)  
Output: 40-pin connector (Fujitsu FCN-365P040-AU)  
Internal power: Via the Installation Base (model: R3-BSx)  
Isolation: Output 1 to output 2 to output 3 to output 4 to  
output 5 to output 6 to output 7 to output 8 to internal bus  
or internal power  
130  
[5.12]  
110  
[4.33]  
Output range: Selectable with the side DIP SW per 4 points  
Output hold function: Setting for communication error with  
side DIP SW  
mm [inch]  
RUN indicator: Bi-color (red/green) LED;  
Red when the bus A operates normally;  
Green when the bus B operates normally;  
Amber when both buses operate normally.  
ERR indicator: Green LED turns on in normal operating  
conditions.  
MODEL: R3Y–YV8[1][2]  
ORDERING INFORMATION  
• Code number: R3Y-YV8[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. R3Y-YV8W/CE/Q)  
OUTPUT SPECIFICATIONS  
Narrow Span: -1 – +1 V, 0 – 1 V DC  
Load resistance: 10 kΩ min.  
• Specify the specification for option code /Q  
(e.g. /C01/SET)  
Wide Span: -10 – +10 V, -5 – +5 V, 0 – 10 V, 0 – 5 V, 1 – 5  
V DC  
NO. OF CHANNELS  
8: 8  
Load resistance: 10 kΩ min.  
Output Range  
Except -10 to +10 V DC: -15 to +115 % of output range  
-10 to +10 V DC: Approx. -11.5 to +11.5 V DC  
[1] COMMUNICATION MODE  
S: Single  
W: Dual  
INSTALLATION  
[2] OPTIONS (multiple selections)  
Standards & Approvals  
blank: Without CE  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R3-BSx)  
Weight: 250 g (0.55 lb)  
/CE: CE marking  
Other Options  
blank: none  
/Q: Option other than the above (specify the specification)  
PERFORMANCE  
Conversion accuracy: ±0.1 %  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
(±0.2 % with 0 – 5 V or 1 – 5 V range)  
Data range: 0 – 10000 of the output range  
Data allocation: 8  
/C02: Polyurethane coating  
Current consumption: 200 mA  
/C03: Rubber coating  
Temp. coefficient: ±0.015 % /°C (±0.008 %/°F)  
(±0.03 % /°C [±0.02 %/°F] with 0 – 5 V or 1 – 5 V range)  
Response time: ≤ 0.2 sec. (0 – 90 %)  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
EX-FACTORY SETTING  
/SET: Preset according to the Ordering Information Sheet  
(No. ESU-8396)  
R3Y-YV8 SPECIFICATIONS  
ES-8953 Rev.8 Page 1/4  
https://www.m-system.co.jp/  
MODEL: R3Y-YV8  
Dielectric strength: 1000 V AC @ 1 minute  
(output 1 to output 2 to output 3 to output 4 to output 5 to  
output 6 to output 7 to output 8 to internal bus or internal  
power)  
2000 V AC @ 1 minute (power input to FG;  
isolated on the power supply module)  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
RoHS Directive  
FUNCTIONS  
■OUTPUT HOLD or OUTPUT OFF  
In normal conditions, the module outputs the signal from  
the preferred bus A. When an error is detected, the output  
is switched to the data from the bus B.  
Output Hold  
If both are in error, the module holds the signal and stands  
by until one of the communications recovers.  
Output OFF  
If both are in error, the module outputs -15 % (or approx.  
-11.5 V) and stands by until one of the communications  
recovers.  
At the startup, it outputs -15 % (or approx. -11.5 V) until the  
communication is established and normal data is received.  
EXTERNAL VIEW  
SIDE VIEW  
FRONT VIEW  
RUN LED  
ERR LED  
• Pin Assignment  
B A  
20 20  
SW1  
SW2  
SW3  
ON  
Range  
Output  
Hold  
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
Output 1-4 (SW1)  
or  
Output 5-8 (SW2)  
ON  
ON  
Output Connector  
B
A
1
1
R3Y-YV8 SPECIFICATIONS  
ES-8953 Rev.8 Page 2/4  
https://www.m-system.co.jp/  
MODEL: R3Y-YV8  
EXTERNAL DIMENSIONS unit: mm [inch]  
27.5 [1.08]  
110 [4.33]  
POSITIONING  
GUIDE  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
RUN LED ERR LED DIP SW  
Output Circuit  
INTERNAL BUS A  
Communication  
Circuit  
19B  
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
INTERNAL BUS B*  
WIDE SPAN  
18B  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
OUTPUT 5  
OUTPUT 6  
OUTPUT 7  
OUTPUT 8  
NARROW SPAN  
Control  
Circuit  
17B  
15B  
14B  
13B  
11B  
10B  
9B  
Output Circuit  
Output Circuit  
Output Circuit  
Output Circuit  
Output Circuit  
Output Circuit  
Output Circuit  
INTERNAL POWER  
WIDE SPAN  
NARROW SPAN  
WIDE SPAN  
NARROW SPAN  
7B  
WIDE SPAN  
NARROW SPAN  
6B  
5B  
19A  
18A  
17A  
15A  
14A  
13A  
11A  
10A  
9A  
WIDE SPAN  
NARROW SPAN  
WIDE SPAN  
NARROW SPAN  
WIDE SPAN  
NARROW SPAN  
7A  
WIDE SPAN  
NARROW SPAN  
6A  
5A  
*For dual redundant communication.  
NOTE: Connect either wide or narrow span terminals for each channel.  
R3Y-YV8 SPECIFICATIONS  
ES-8953 Rev.8 Page 3/4  
https://www.m-system.co.jp/  
MODEL: R3Y-YV8  
OUTPUT CONNECTOR (40-pin)  
PIN NO.  
ASSIGNMENT  
PIN NO.  
ASSIGNMENT  
1A  
2A  
3A  
NC  
NC  
NC  
1B  
2B  
3B  
NC  
NC  
NC  
4A  
5A  
6A  
NC  
4B  
5B  
6B  
NC  
– OUT8  
+ OUT8L  
– OUT4  
+ OUT4L  
7A  
8A  
9A  
+ OUT8H  
NC  
7B  
8B  
9B  
+ OUT4H  
NC  
– OUT7  
– OUT3  
10A  
11A  
12A  
+ OUT7L  
+ OUT7H  
NC  
10B  
11B  
12B  
+ OUT3L  
+ OUT3H  
NC  
13A  
14A  
15A  
– OUT6  
+ OUT6L  
+ OUT6H  
13B  
14B  
15B  
– OUT2  
+ OUT2L  
+ OUT2H  
16A  
17A  
18A  
NC  
16B  
17B  
18B  
NC  
– OUT5  
+ OUT5L  
– OUT1  
+ OUT1L  
19A  
20A  
+ OUT5H  
NC  
19B  
20B  
+ OUT1H  
NC  
Specifications are subject to change without notice.  
R3Y-YV8 SPECIFICATIONS  
ES-8953 Rev.8 Page 4/4  
https://www.m-system.co.jp/  

相关型号:

R3Y-YV8S

Remote I/O R3 Series DC VOLTAGE OUTPUT MODULE
MSYSTEM

R3Y-YV8S/CE

Remote I/O R3 Series DC VOLTAGE OUTPUT MODULE
MSYSTEM

R3Y-YV8S/Q

Remote I/O R3 Series DC VOLTAGE OUTPUT MODULE
MSYSTEM

R3Y-YV8W

Remote I/O R3 Series DC VOLTAGE OUTPUT MODULE
MSYSTEM

R3Y-YV8W/CE

Remote I/O R3 Series DC VOLTAGE OUTPUT MODULE
MSYSTEM

R3Y-YV8W/Q

Remote I/O R3 Series DC VOLTAGE OUTPUT MODULE
MSYSTEM

R4-C-BLK-BLK-F-F-0

Rocker Switch, SPDT, Latched, Quick Connect Terminal, Rocker Actuator, Panel Mount
E-SWITCH

R4-C-BLK-BLK-G-F-0

Rocker Switch, SPDT, Latched, Quick Connect Terminal, Rocker Actuator, Panel Mount
E-SWITCH

R4-C-BLK-BLK-I-F-0

Rocker Switch, SPDT, Latched, Quick Connect Terminal, Rocker Actuator, Panel Mount
E-SWITCH

R4-D-BLK-BLK-D-F-0

Rocker Switch, SPDT, Latched, Quick Connect Terminal, Rocker Actuator, Panel Mount
E-SWITCH

R4-D-BLK-BLK-F-F-0

Rocker Switch, SPDT, Latched, Quick Connect Terminal, Rocker Actuator, Panel Mount
E-SWITCH

R4-D-BLK-BLK-G-F-0

Rocker Switch, SPDT, Latched, Quick Connect Terminal, Rocker Actuator, Panel Mount
E-SWITCH