R5-MS1S/Q [MSYSTEM]

Remote I/O R5 Series POTENTIOMETER INPUT MODULE;
R5-MS1S/Q
型号: R5-MS1S/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R5 Series POTENTIOMETER INPUT MODULE

输入元件
文件: 总3页 (文件大小:112K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R5-MS  
Zero/Span adj. mode selector: Rotary switch; run mode and  
adj. mode selectable  
Remote I/O R5 Series  
RUN indicator: Bi-color (red/green) LED;  
Red when the bus A operates normally;  
Green when the bus B operates normally;  
Amber when both buses operate normally.  
POTENTIOMETER INPUT MODULE  
18 (.71)  
2
3
4
1
5
0
8
7 6  
9
INPUT SPECIFICATIONS  
Total resistance: 100 Ω – 10 kΩ  
Minimum span: 50 % of the total resistance range  
Excitation: 0.5 V DC  
90  
(3.54)  
96.5  
(3.80)  
mm (inch)  
INSTALLATION  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R5-BS)  
Weight: 100 g (3.53 oz)  
MODEL: R5-MS[1][2][3]  
ORDERING INFORMATION  
• Code number: R5-MS[1][2][3]  
Specify a code from below for each [1] through [3].  
(e.g. R5-MS2W/Q)  
PERFORMANCE  
Conversion accuracy: ±0.1 %  
• Specify the specification for option code /Q  
(e.g. /C01)  
Data range: 0 – 10000 of the input range  
Data allocation: 1 (2 for 2-channel type)  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Resolution: 1/10000 of the total resistance range  
(Reduced by the actual range determined zero/ span  
positions. Minimum 50 % of the total resistance range must  
be maintained.)  
[1] NO. OF CHANNELS  
1: 1 channel  
2: 2 channels  
[2] COMMUNICATION MODE  
S: Single  
Response time: ≤ 0.1 sec. (0 – 90 %)  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute (input 1 to input  
2 to internal bus or internal power)  
W: Dual  
2000 V AC @ 1 minute (power input to FG; isolated on the  
power supply module)  
[3] OPTIONS  
blank: none  
/Q: With options (specify the specification)  
STANDARDS & APPROVALS  
EU conformity:  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
RoHS Directive  
/C02: Polyurethane coating  
/C03: Rubber coating  
EN 50581  
GENERAL SPECIFICATIONS  
Connection  
Internal bus: Via the Installation Base (model: R5-BS)  
Input: Euro type connector terminal  
(Applicable wire size: 0.2 – 2.5 mm  
2
(AWG24 - 12),  
stripped length 7 mm)  
Internal power: Via the base (model: R5-BS)  
Isolation: Input 1 to input 2 to internal bus or internal power  
R5-MS SPECIFICATIONS  
ES-6146 Rev.6 Page 1/3  
http://www.m-system.co.jp/  
MODEL: R5-MS  
FUNCTIONS  
Zero/Span Adjustment Modes  
Run Mode  
Normal operating mode  
Input 0 % Adjustment Mode  
Apply the actual 0% input and press SET.  
Input 100 % Adjustment Mode  
Apply the actual 100 % input and press SET.  
• How to Operate  
1) Start up in Monitor Mode (SW position = 0) and wait for 2  
or 3 seconds.  
2) Switch to another mode and go through the adjustments.  
3) Reset the switch to the position ‘0’ so that the new  
setting is stored in the internal memory.  
• Cautions on the LEDs  
1) Mode switching from Run to another mode becomes  
effective when SET button is touched and the LED for the  
respective mode starts blinking after the rotary switch  
setting has been changed.  
2) Mode switching back to Monitor becomes effective  
automatically in a few seconds after the switch is reset to  
‘0’ and is confirmed with the LED stopping blinking.  
EXTERNAL VIEW  
RUN  
RUN LED  
Zero/Span Adj.  
Mode Selector  
SET  
SET Button  
4
1
5
2
6
3
Euro Type  
Connector Terminals  
R5-MS SPECIFICATIONS  
ES-6146 Rev.6 Page 2/3  
http://www.m-system.co.jp/  
MODEL: R5-MS  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
LOCKING CLAMP  
18 (.71)  
6.5  
90 (3.54)  
(.26)  
4
1
5
2
6
3
POSITIONING GUIDE  
*
*Euro type connector terminals (4, 5 and 6) provided only with 2-ch. option.  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
POTENTIOMETER  
RUN LED  
max.  
Excitation Volt.  
Generator  
+
1
2
3
3
2
1
Isolation  
INTERNAL BUS A  
Communication  
Circuit  
INPUT 1  
INTERNAL BUS B*  
min.  
Control  
Circuit  
POTENTIOMETER  
max.  
INTERNAL POWER  
Excitation Volt.  
Generator  
+
4
5
6
3
2
1
Isolation  
INPUT 2  
min.  
SET  
BUTTON  
ROTARY SW  
*For dual redundant communication.  
Note: The section enclosed by broken line is with 2-ch. option.  
Specifications are subject to change without notice.  
R5-MS SPECIFICATIONS  
ES-6146 Rev.6 Page 3/3  
http://www.m-system.co.jp/  

相关型号:

R5-MS1W

Remote I/O R5 Series POTENTIOMETER INPUT MODULE
MSYSTEM

R5-MS1W/Q

Remote I/O R5 Series POTENTIOMETER INPUT MODULE
MSYSTEM

R5-MS2S

Remote I/O R5 Series POTENTIOMETER INPUT MODULE
MSYSTEM

R5-MS2S/Q

Remote I/O R5 Series POTENTIOMETER INPUT MODULE
MSYSTEM

R5-MS2W

Remote I/O R5 Series POTENTIOMETER INPUT MODULE
MSYSTEM

R5-MS2W/Q

Remote I/O R5 Series POTENTIOMETER INPUT MODULE
MSYSTEM

R5-PA2

Remote I/O R5 Series
MSYSTEM

R5-PA2S

Remote I/O R5 Series
MSYSTEM

R5-PA2S/Q

Remote I/O R5 Series
MSYSTEM

R5-PA2W

Remote I/O R5 Series
MSYSTEM

R5-PA2W/Q

Remote I/O R5 Series
MSYSTEM

R5-PC2

Remote I/O R5 Series
MSYSTEM