R5-PC2 [MSYSTEM]

Remote I/O R5 Series;
R5-PC2
型号: R5-PC2
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R5 Series

文件: 总3页 (文件大小:116K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R5-PC2  
RUN indicator: Bi-color (red/green) LED;  
Remote I/O R5 Series  
Red when the bus A operates normally;  
Green when the bus B operates normally;  
Amber when both buses operate normally.  
Output status indicator: Red LED; turns on with the outputs  
ON.  
PULSE OUTPUT MODULE  
(photo MOSFET relay output, 2 points)  
18 (.71)  
Pulse width adjustment: 5 msec., 10 msec., 50 msec., 100  
msec., 500 msec., 1 sec., 1.5 sec., 2 sec. (Side DIP SW)  
Count reset: Via DIP switches on the side  
90  
(3.54)  
OUTPUT SPECIFICATIONS  
Output: Photo MOSFET relay contact, 2 points  
96.5  
(3.80)  
Common: Each point independent  
mm (inch)  
Rated load: 125 V AC/DC @ 50 mA (resistive load)  
Maximum ON resistance: 50 Ω  
Maximum frequency: 100 Hz (DIP SW selectable)  
Totalized pulse range: 1 – 10000 (‘0’ at reset)  
(Max. pulse range selectable from 100 to 60000 using the  
R5CON PC Configurator Software. Refer to the R5CON Users  
Manual for detailed information.)  
MODEL: R5–PC2[1][2]  
ORDERING INFORMATION  
• Code number: R5-PC2[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. R5-PC2W/Q)  
Count at overflow: Reset and restart at ‘1.’  
• Specify the specification for option code /Q  
(e.g. /C01)  
INSTALLATION  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R5-BS)  
Weight: 100 g (0.22 lb)  
NO. OF CHANNELS  
2: 2-point outputs  
[1] COMMUNICATION MODE  
S: Single  
PERFORMANCE  
Data allocation: 2  
W: Dual  
Response time: ≤ 0.1 sec.  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute  
(Po 1 to Po 2 to internal bus or internal power)  
2000 V AC @ 1 minute (power input to FG;  
isolated on the power supply module)  
[2] OPTIONS  
blank: none  
/Q: With options (specify the specification)  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
/C02: Polyurethane coating  
/C03: Rubber coating  
GENERAL SPECIFICATIONS  
Connection  
Internal bus: Via the Installation Base (model: R5-BS)  
Output: Euro type connector terminal  
(Applicable wire size: 0.2 – 2.5 mm  
2
(AWG24 - 12),  
stripped length 7 mm)  
Internal power: Via the base (model: R5-BS)  
Isolation: Po 1 to Po 2 to internal bus or internal power  
R5-PC2 SPECIFICATIONS  
ES-6140 Rev.11 Page 1/3  
https://www.m-system.co.jp/  
MODEL: R5-PC2  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
Low Voltage Directive  
EN 61010-1, EN 61010-2-201  
Measurement Category II (output)  
Pollution Degree 2  
Output to internal bus or internal power – Basic insulation  
(300 V)  
RoHS Directive  
FUNCTIONS  
Counter reset  
1) Remove Network Module or its cables and interrupt  
communication with other devices.  
2) Turn ON the Counter Reset SW (SW8) on the module.  
3) Return the module to the base and turn the power supply  
on.  
4) Red RUN LED turns on and the module starts resetting its  
counter. When the resetting is complete, the LED light turns  
to green. DO NOT remove the power while the red light is  
on.  
5) After the green LED is confirmed, turn the power supply  
off.  
6) Turn OFF the Counter Reset SW (SW8).  
7) Return the Network module onto the base and turn the  
power supply on.  
Note: Counter Reset SW must be turned OFF after this  
procedure because the module does not start counting with  
ON state.  
EXTERNAL VIEW  
SIDE VIEW  
FRONT VIEW  
RUN LED  
RUN  
1
2
3
4
Status Indicator LED  
1 2 3 4 5 6 7 8  
ON  
OFF  
Counter  
Reset  
Pulse Width  
4
1
5
2
6
3
Unused  
Euro Type  
Connector Terminals  
Note: Counter Reset SW is normally OFF during operation.  
R5-PC2 SPECIFICATIONS  
ES-6140 Rev.11 Page 2/3  
https://www.m-system.co.jp/  
MODEL: R5-PC2  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]  
LOCKING CLAMP  
18 (.71)  
6.5  
90 (3.54)  
(.26)  
4
1
5
2
6
3
POSITIONING GUIDE  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
RUN OUTPUT STATUS  
LED INDICATOR LED  
• • • •  
Isolation  
INTERNAL BUS A  
1
3
Communication  
Circuit  
1
3
4
6
2
5
Po 1  
*INTERNAL BUS B  
Control  
Circuit  
COM1  
Po 2  
Isolation  
INTERNAL POWER  
COM2  
DIP SW  
*For dual redundant communication.  
Note: Italic typed numbers correspond to the LEDs on the front panel.  
Specifications are subject to change without notice.  
R5-PC2 SPECIFICATIONS  
ES-6140 Rev.11 Page 3/3  
https://www.m-system.co.jp/  

相关型号:

R5-PC2S

Remote I/O R5 Series
MSYSTEM

R5-PC2S/Q

Remote I/O R5 Series
MSYSTEM

R5-PC2W

Remote I/O R5 Series
MSYSTEM

R5-PC2W/Q

Remote I/O R5 Series
MSYSTEM

R5-PS

Remote I/O R5 Series
MSYSTEM

R5-PSK

Remote I/O R5 Series
MSYSTEM

R5-PSK/Q

Remote I/O R5 Series
MSYSTEM

R5-PSL

Remote I/O R5 Series
MSYSTEM

R5-PSL/Q

Remote I/O R5 Series
MSYSTEM

R5-PSR

Remote I/O R5 Series
MSYSTEM

R5-PSR/Q

Remote I/O R5 Series
MSYSTEM

R5-RS

Remote I/O R5 Series
MSYSTEM