R5T-CTA1W/Q [MSYSTEM]

Remote I/O R5 Series;
R5T-CTA1W/Q
型号: R5T-CTA1W/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R5 Series

文件: 总3页 (文件大小:115K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R5T-CTA  
•Clamp-on current sensor (model: CLSA-30)  
Remote I/O R5 Series  
•Clamp-on current sensor (model: CLSA-50)  
•Special cable (model: CLSA-08C)  
AC CURRENT INPUT MODULE  
(clamp-on current sensor type CLSA use;  
screw terminal block; true RMS sensing)  
The clamp-on current sensor, not included in the product  
package, must be ordered separately.  
Refer to the data sheet for the sensor for more information  
such as applicable wire diameter.  
18 (.71)  
GENERAL SPECIFICATIONS  
Connection  
90  
(3.54)  
Internal bus: Via the Installation Base (model: R5-BS)  
Input: M3.5 screw terminal block (torque 0.8 N·m)  
Internal power: Via the base (model: R5-BS)  
Screw terminal: Nickel-plated steel (standard) or stainless  
steel  
137  
(5.39)  
mm (inch)  
Isolation: Input 1 to input 2 to internal bus or internal power  
Input waveform  
MODEL: R5T-CTA[1][2][3]  
RMS sensing: Up to 15 % of 3rd harmonic content  
Input range: Selectable with the side DIP SW  
RUN indicator: Bi-color (red/green) LED;  
Red when the bus A operates normally;  
Green when the bus B operates normally;  
Amber when both buses operate normally.  
Low-end cutout: Converted as 0 % for the input below 2 %  
ORDERING INFORMATION  
Code number: R5T-CTA[1][2][3]  
Specify a code from below for each [1] through [3].  
(e.g. R5T-CTA2W/Q)  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
INPUT SPECIFICATIONS  
Frequency: 50 or 60 Hz  
[1] NO. OF CHANNELS  
1: 1 channel  
Operational range: 5 – 115 % of rating  
Max. working voltage: 440 V AC (primary side)  
Sensor & range:  
2: 2 channels  
CLSA-08: 0 – 80 A AC  
[2] COMMUNICATION MODE  
S: Single  
CLSA-12: 0 – 120 A AC  
CLSA-30: 0 – 300 A AC  
W: Dual  
CLSA-50: 0 - 500 A AC  
[3] OPTIONS  
blank: none  
INSTALLATION  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R5-BS)  
Weight: 110 g (0.24 lb)  
/Q: With options (specify the specification)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
/C02: Polyurethane coating  
/C03: Rubber coating  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
RELATED PRODUCTS  
•Clamp-on current sensor (model: CLSA-08)  
•Clamp-on current sensor (model: CLSA-12)  
R5T-CTA SPECIFICATIONS  
ES-7554 Rev.3 Page 1/3  
http://www.m-system.co.jp/  
MODEL: R5T-CTA  
PERFORMANCE  
Conversion accuracy: ±0.5 % (at 5 – 100 % input) except  
the sensor accuracy  
Data range: Engineering unit value × 100 (binary without  
sign)  
Data allocation: 1 (2 for 2-channel type)  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Response time: ≤ 0.5 sec. (0 – 90 %)  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute (input 1 to input  
2 to internal bus or internal power)  
2000 V AC @ 1 minute (power input to FG; isolated on the  
power supply module)  
EXTERNAL VIEW  
SIDE VIEW  
FRONT VIEW  
1 2 3 4 5 6 7 8  
RUN  
RUN LED  
Input 1  
Input 2  
5
2
6
3
INPUT DATA DESCRIPTIONS  
■ ANALOG DATA (AC CURRENT DATA.)  
16-bit binary data.  
Integer obtained by multiplying unit value (A) by 100.  
15  
0
R5T-CTA SPECIFICATIONS  
ES-7554 Rev.3 Page 2/3  
http://www.m-system.co.jp/  
MODEL: R5T-CTA  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
LOCKING CLAMP  
18 (.71)  
38.5 (1.52)  
98.5 (3.88)  
TERMINAL COVER  
4–M3.5  
TERMINAL  
SCREWS  
5
2
6
3
7.2 (.28)  
POSITIONING GUIDE  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
RUN LED DIP SW  
SOURCE  
Input Circuit  
CONNECTOR  
*
INTERNAL BUS A  
k
2
3
Communication  
Circuit  
INTERNAL BUS B**  
INPUT 1  
CLAMP-ON SENSOR  
l
Control  
Circuit  
LOAD  
INTERNAL POWER  
SOURCE  
Input Circuit  
CONNECTOR  
*
k
5
6
INPUT 2  
CLAMP-ON SENSOR  
l
LOAD  
* Connector provided only for the CLSA-08 and CLSA-12.  
**For dual redundant communication.  
Note: The section enclosed by broken line is with 2-ch. option.  
Specifications are subject to change without notice.  
R5T-CTA SPECIFICATIONS  
ES-7554 Rev.3 Page 3/3  
http://www.m-system.co.jp/  

相关型号:

R5T-CTA2S

Remote I/O R5 Series
MSYSTEM

R5T-CTA2S/Q

Remote I/O R5 Series
MSYSTEM

R5T-CTA2W

Remote I/O R5 Series
MSYSTEM

R5T-CTA2W/Q

Remote I/O R5 Series
MSYSTEM

R5T-CTB1S

Remote I/O R5 Series
MSYSTEM

R5T-CTB1S/Q

Remote I/O R5 Series
MSYSTEM

R5T-CTB1W

Remote I/O R5 Series
MSYSTEM

R5T-CTB1W/Q

Remote I/O R5 Series
MSYSTEM

R5T-CTB2S

Remote I/O R5 Series
MSYSTEM

R5T-CTB2S/Q

Remote I/O R5 Series
MSYSTEM

R5T-CTB2W

Remote I/O R5 Series
MSYSTEM

R5T-CTB2W/Q

Remote I/O R5 Series
MSYSTEM