R7FN-RS4 [MSYSTEM]
Remote I/O R7 Series FLEX NETWORK I/O MODULE;型号: | R7FN-RS4 |
厂家: | M-SYSTEM |
描述: | Remote I/O R7 Series FLEX NETWORK I/O MODULE |
文件: | 总6页 (文件大小:176K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R7FN-RS4
EX-FACTORY SETTING
Remote I/O R7 Series
/SET: Preset according to the Ordering Information Sheet
(No. ESU-7808-RS4)
FLEX NETWORK I/O MODULE
(RTD input, 4 points, isolated)
RELATED PRODUCTS
Functions & Features
• PC configurator software (model: R7CON)
The configurator software is downloadable at M-System’s
web site.
• 4 points RTD input module for FLEX NETWORK
• Input sensor type can be selected with the front DIP
switches for all channels.
A dedicated cable is required to connect the module to the
PC. Please refer to the users manual for the PC configurator
for applicable cable types.
• Easy parameter setting of individual channels with M-
System's configurator software
• Screen editor software (model: GP-Pro EX)
Screen editor software GP-Pro EX (Ver.2.70 or higher) is
available.
FLEX NETWORK is registered trademark of Digital
Electronics Corporation in Japan.
For versions between 2.60 and 2.70, the driver must be
installed. The driver is downloadable at Digital Electronics
Corporation's web site. http://www.proface.co.jp/
115 (4.53)
53 (2.09)
GENERAL SPECIFICATIONS
Connection: M3 separable screw terminal (torque 0.5 N·m)
Solderless terminal: Refer to the drawing at the end of the
section.
54 (2.13)
mm (inch)
• Communication cable
Recommended manufacture: Japan Solderless Terminal
MFG.Co.Ltd
MODEL: R7FN–RS4-R[1]
Applicable wire size: 0.2 to 0.5 mm
2
(AWG 26 to 22)
ORDERING INFORMATION
• Code number: R7FN-RS4-R[1]
Specify a code from below for [1].
(e.g. R7FN-RS4-R/Q)
• Others
Recommended manufacture: Japan solderless terminal
MFG.Co.Ltd, Nichifu Co.,ltd
Applicable wire size: 0.25 to 1.65 mm
2
(AWG 22 to 16)
• Specify the specification for option code /Q
(e.g. /C01/SET)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (gray)
Isolation: Input 0 to input 1 to input 2 to input 3 to FLEX
NETWORK to power to FG
I/O TYPE
Zero adjustments: Configurable via R7CON
Span adjustments: Configurable via R7CON
Conversion rate: Configurable via R7CON
Burnout setting: Selectable between upscale (*) and
downscale with the front DIP switch
(*) Factory default setting
RS4: RTD input, 4 points
POWER INPUT
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
Linearization: Standard
RTD Setting: Selectable with front DIP SW or PC
programming.
[1] OPTIONS
Status indicator LED: PWR, RUN
blank: none
(Refer to the instruction manual)
/Q: Options other than the above (specify the specification)
■Recommended solderless terminal
3.3 (.13) max
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
mm (inch)
/C03: Rubber coating
R7FN-RS4 SPECIFICATIONS
ES-7808-C Rev.0 Page 1/6
http://www.m-system.co.jp/
MODEL: R7FN-RS4
FLEX NETWORK COMMUNICATION
Communication configuration: 1: N
Connection method: Multi-drop Connection
Communication method: Cyclic Time Division, half-duplex
Communication I/F: Differential, pulse transfer isolation
Error Check: Format, bit, CRC-12 verification
Max. Number of Nodes: 63 (1008 I/O points)
Required node: 4
PERFORMANCE
Conversion accuracy: ±1°C (±1°F)
(±3°C [±5.4°F] for Cu 10)
Conversion rate: 250 msec. (*) or 500 msec. selectable
(*) Factory default setting
Converted data range:
• Engineering unit value (°C, K) × 10 (integer)
• Engineering unit value (°F)
Network cable: Pro-face’s following cable
FN-CABLE2010-31-MS (10 m)
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) of max. span
Response time: Conversion rate × 2 + 50 msec. (0 – 90 %)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input 0 to input
1 to inpu 2 to input 3 to FLEX NETWORK to power to FG)
FN-CABLE2050-31-MS (50 m)
FN-CABLE2200-31-MS (200 m)
Transmission distance: 12 Mbps: 100 meters (328 ft)(*)
6 Mbps: 200 meters (656 ft)
(*) Factory default setting
STANDARDS & APPROVALS
EU conformity:
Station address: Rotary switch
(Refer to the instruction manual)
EMC Directive
Terminating resistor: Built-in
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
INPUT SPECIFICATIONS
Input resistance: ≥ 1 MΩ
EN 50581
Maximum leadwire resistance: 100 Ω per wire
Sensing current: ≤ 1 mA
BURNOUT INDICATION (°C) CONFORMANCE
RTD
Downscale
-240
-240
-236
-236
-100
Upscale
+900
+900
+560
+700
+252
+312
+200
RANGE (°C)
-200 to +850
-200 to +660
-200 to +510
-200 to +649
-80 to +250
-50 to +250
-50 to +150
Pt 100 (JIS ’97, IEC)
Pt 100 (JIS ’89)
JPt 100 (JIS ’89)
Pt 50 Ω (JIS ’81)
Ni 100
Cu 10 @ 25°C
Cu 50
-212
-100
BURNOUT INDICATION (°F) CONFORMANCE
RTD
Downscale
-400
-400
-393
-393
-148
Upscale
+1652
+1652
+1040
+1292
+486
RANGE (°F)
-328 to +1562
-328 to +1220
-328 to +950
-328 to +1200
-112 to +482
-58 to +482
Pt 100 (JIS ’97, IEC)
Pt 100 (JIS ’89)
JPt 100 (JIS ’89)
Pt 50 Ω (JIS ’81)
Ni 100
Cu 10 @ 25°C
Cu 50
-350
-148
+594
+392
-58 to +302
INSTALLATION
Current consumption
•DC: Approx. 90 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail (35 mm rail)
Weight: 200 g (0.44 lb)
R7FN-RS4 SPECIFICATIONS
ES-7808-C Rev.0 Page 2/6
http://www.m-system.co.jp/
MODEL: R7FN-RS4
EXTERNAL VIEW
Operating Mode Setting DIP SW (SW1)
PC Configurator Jack
Station Address Setting Rotary SW
Status Indicator LED
ON
2 3 4 5 6 7 8
1
X10
8
X1
8
PWR RUN
CNFG.
STATION ADD.
4
5
6
7
10 11 12 13 14 15 16 17 18
1
2
3
1
2
3
4
5
6
7
8
9
FLEX NETWORK,
Power Supply Terminals
Input Terminals
CONNECTION DIAGRAMS
■ MASTER CONNECTION
Master Station
Slave Station
Slave Station
+
–
+
–
+
–
TR
TR
TR
Terminating
Resistor
TR
TR
TR
+
+
SHIELD
JP
JP
JP
JP
Terminating
Short Bar
–
–
FG
FG
Note: Be sure to use the terminator(s) located at both ends of the modules.
TERMINAL ASSIGNMENTS
■ INPUT TERMINAL ASSIGNMENT
10
11
12
13
14
NC
15
16
17
18
INA0 INb0 INA1 INb1
INA2 INb2 INA3 INb3
1
2
3
4
5
6
7
8
9
NC
INB0
NC
INB1
NC
NC
INB2
NC
INB3
NO. ID
FUNCTION
NO. ID
FUNCTION
1
2
3
4
5
6
7
8
9
NC No connection
INB0 RTD 0-B
10 INA0 RTD 0-A
11 INb0 RTD 0-b
12 INA1 RTD 1-A
13 INb1 RTD 1-b
NC No connection
INB1 RTD 1-B
NC No connection
NC No connection
INB2 RTD 2-B
14
NC No connection
15 INA2 RTD 2-A
16 INb2 RTD 2-b
17 INA3 RTD 3-A
18 INb3 RTD 3-b
NC No connection
INB3 RTD 3-B
R7FN-RS4 SPECIFICATIONS
ES-7808-C Rev.0 Page 3/6
http://www.m-system.co.jp/
MODEL: R7FN-RS4
■ NETWORK, POWER SUPPLY TERMINAL ASSIGNMENT
4
5
6
7
-
TR+ TR +24V 0V
1
2
3
-
JP+ JP
FG
NO.
1
ID
JP+
JP–
FG
FUNCTION, NOTES
Terminating resistor
Terminating resistor
FG
2
3
4
TR+
TR–
+24V
0V
Network
5
Network
6
Power input (24V DC)
Power input (0V)
7
DATA CONVERSION
■ INPUT RANGE AND DATA CONVERSION (FACTORY DEFAULT SETTING)
Engineering unit value °C or K is multiplied by 10 and expressed in 16 bits. °F data is represented in engineering unit
value, without multiplication. Negative value is represented in 2’s complements.
• Input TYPE K Thermocouple
Converted Data, Decimal
Converted Data, Hex
Input Value
≤ -272°C
-150°C
-2720
-1500
13700
14720
F560
FA24
3584
3980
1370°C
≥ 1472°C
14720 (3980)
13700 (3584)
-272 -150
1370
1472
(°C)
-1500 (FA24)
-2720 (F560)
R7FN-RS4 SPECIFICATIONS
ES-7808-C Rev.0 Page 4/6
http://www.m-system.co.jp/
MODEL: R7FN-RS4
I/O DATA DESCRIPTIONS
■ ANALOG INPUT
• Di
• Do
15
0
0
15
0
0
ADD.n
CH0
CH1
Unused
Unused
15
15
ADD.n+1
15
0
0
15
15
0
0
ADD.n+2
CH2
CH3
Unused
Unused
15
ADD.n+3
The data is 16-bit binary.
Negative value is represented in 2’s complements.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
115 (4.53)
17 (.66)
54 (2.13)
DIN RAIL
35mm wide
4
5
6
7
10 11 12 13 14 15 16 17 18
1
2
3
1
2
3
4
5
6
7
8
9
30 (1.18)
[5 (.20)]
6 (.24)
6 (.24)
7–M3 SCREW
TERMINALS
for FLEX NETWORK, POWER
18–M3 SCREW
TERMINALS
for INPUT
R7FN-RS4 SPECIFICATIONS
ES-7808-C Rev.0 Page 5/6
http://www.m-system.co.jp/
MODEL: R7FN-RS4
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.
Isolation
Input Circuit
10
2
INA0
INB0
INb0
4
5
TR+
TR–
Comm.
Circuit
INPUT 0
INPUT 1
INPUT 2
INPUT 3
11
1
2
3
6
7
JP+
JP–
Input Circuit
Input Circuit
12
4
INA1
INB1
INb1
FG
13
24V DC
0V
Control
Circuit
15
7
INA2
INB2
INb2
16
Input Circuit
17
9
INA3
INB3
INb3
18
1
3
5
6
8
14
■ Input Connection Example
RTD
A
B
B
INAn
INBn
INbn
Specifications are subject to change without notice.
R7FN-RS4 SPECIFICATIONS
ES-7808-C Rev.0 Page 6/6
http://www.m-system.co.jp/
相关型号: