R9CWTU-2001-AD4 [MSYSTEM]

Remote I/O R9 Series MULTI POWER MONITORING UNIT;
R9CWTU-2001-AD4
型号: R9CWTU-2001-AD4
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R9 Series MULTI POWER MONITORING UNIT

监视器
文件: 总7页 (文件大小:279K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R9CWTU  
Remote I/O R9 Series  
EXTENSION UNIT  
1: With connection  
MULTI POWER MONITORING UNIT  
(Clamp-on current sensor CLSE, CC-Link)  
Functions & Features  
AUXILIARY POWER SUPPLY  
AD4: universal  
• Multi Power Monitoring Unit for CC-Link.  
• By using clamp-on current sensors, there is no need of  
current transformers.  
100 – 240 V AC (Operational range 85 – 264 V, 50 / 60 Hz) /  
110 – 240 V DC (Operational range 99 – 264 V,  
ripple 10 %p-p max)  
• Up to 8 circuits can be measured. (Common voltage  
measurement)  
[1] OPTIONS (multiple selections)  
CC-Link Version  
• Current sensors are easy to install in existing systems.  
Wide input range of 5 to 600 A is availabe.  
• All measured values, counter values, display mode,  
setting data are stored in the non-volatile memory when  
power is off.  
blank: Ver.1.10  
/2: Ver.2.0  
Other Options  
blank: none  
• By using SD card, data logging of current and power etc.  
with calendar is available.  
/Q: With options (specify the specification)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
125 (4.92)  
/C02: Polyurethane coating  
/C03: Rubber coating  
140 (5.51)  
EX-FACTORY SETTING  
/SET: Preset according to the Ordering Information Sheet  
(No. ESU-6222)  
80 (3.15)  
mm (inch)  
RELATED PRODUCTS  
• Discrete I/O extension unit (model: R9WTU-ED)  
• Multi power monitoring extension unit (model: R9WTU-EP)  
• PC configurator software (model: PMCFG)  
Downloadable at M-System’s web site.  
MODEL: R9CWTU–2001–AD4[1]  
ORDERING INFORMATION  
• Code number: R9CWTU-2001-AD4[1]  
Specify a code from below for [1].  
(e.g. R9CWTU-2001-AD4/2/Q)  
A dedicated cable is required to connect the module to the  
PC. Please refer to the internet software download site or  
the users manual for the PC configurator for applicable  
cable types.  
• Specify the specification for option code /Q  
(e.g. /C01/SET)  
• Clamp-on current sensor (model: CLSE)  
The clamp-on current sensors, not included in this product  
package, must be ordered separately. Required number  
depends upon the system configuration.  
• SD card  
CONFIGURATION  
2: Single-phase/2-wire, 3-phase/3-wire, single-phase/3-wire; 8 circuits  
A SD card is required to store data in the unit.  
Use the specified model number of memory card.  
Available for purchase from M-System. Consult M-System.  
- Hagiwara Solutions NSD6-004GH(B21SEI  
(NSD6-004GH(A00SDI, NSDA-004GT,  
CONNECTION  
0: Terminal block  
NSDA-004GL ... discontinued)  
I/O  
- Apacer Technology AP-ISD04GIS4B-3T  
(AP-ISD04GIS4B-T ... discontinued)  
0: Without  
R9CWTU SPECIFICATIONS  
ES-6222 Rev.8 Page 1/7  
http://www.m-system.co.jp/  
MODEL: R9CWTU  
GENERAL SPECIFICATIONS  
Construction: Stand-alone  
CC-Link COMMUNICATION  
CC-Link: Ver.1.10/Ver.2.0  
Degree of protection: IP20  
Station Type: Remote device  
Connection  
Connector: M3 screw terminal  
Auxiliary power or voltage input: M3.5 screw terminals  
(torque 0.8 N·m)  
Network cable: CC-Link cable designated by Mitsubishi  
Electric  
Current input: M3 screw terminals (torque 0.5 N·m)  
CC-Link: M3 screw terminals (torque 0.5 N·m)  
Solderless terminal: Refer to the drawing at the end of the  
section.  
Station number: 1 - 64 (set by rotary switch)  
Baud rate setting: 156 kbps (default), 625 kbps, 2.5 Mbps,  
5 Mbps, 10 Mbps (selected by rotary switch)  
CC-Link LED: Run, RD, SD, ERR  
Ver.1.10  
Recommended manufacturer: Japan Solderless Terminal  
MFG.Co.Ltd, Nichifu Co.,ltd  
No.of occupied stations: 1  
Applicable wire size  
Configuration: Via PC configurator software or CC-Link  
Data acquisition: Data is read by command-driven  
program  
M3 screw terminal: 0.25 to 1.65 mm  
2
(AWG 22 to 16)  
(AWG 16 to 14)  
M3.5 screw terminal: 1.04 to 2.63 mm  
2
Configuration: Single-phase/2-wire, single-phase/3-wire, 3-  
phase/3-wire  
Ver.2.0  
No.of occupied stations: 4 (Extended cyclic: 8)  
Configuration: Via PC configurator software  
Data acquisition: Max. 62 points of data can be  
designated and read  
Screw terminal: Nickel-plated steel  
Housing material: Flame-resistant resin (black)  
Isolation: Sensor core to sensor output or current input or  
voltage input to CC-Link to auxiliary power to FE1  
■ Measured variables  
Terminating resistor: Built-in (Set by DIP SW; disabled at  
default)  
Voltage: R – N, S – N, T – N, R – S, S – T, T – R  
Current: R, S, T, N  
INPUT SPECIFICATIONS  
Frequency: 50 / 60 Hz (45 – 65 Hz)  
Voltage Input  
Active / reactive / apparent power: R, S, T, Σ  
Power factor: R, S, T, Σ  
Frequency  
Rated voltage  
Active energy: Incoming  
Between lines: 400 V AC  
Reactive energy: Incoming lag  
Line-neutral (phase voltage): 230 V (single-phase / 2-wire  
and 3-wire)  
Active / reactive / apparent power intervals (demand)  
Average (demand) current: R, S, T, N  
Harmonic contents: Σ  
Input burden: ≤ ULN2 / 300 kΩ / phase  
Overload capacity: 200 % of rating for 10 sec., 120 %  
continuous  
Voltage: R - N, S - N, T - N, R - S, S - T, T - R  
Current: R, S, T, N  
Selectable primary voltage range: 50 – 400 000 V  
Current Input  
Max. and min. values  
Calendar log (inserting SD card): Voltage, Current, power,  
electric energy, power factor  
CLSE-R5: 0 – 5 A AC  
CLSE-05: 0 – 50 A AC  
Operating mode setting: Connection, clamp-on sensor  
selection  
CLSE-10: 0 – 100 A AC  
CLSE-20: 0 – 200 A AC  
Status indicators: Power, SD Card  
■Recommended solderless terminal size - M3  
CLSE-40: 0 – 400 A AC  
CLSE-60: 0 – 600 A AC  
3.3 (.13) max  
Overload capacity: 120 % continous, 500 % for 10 sec.  
Note: Use for the circuit not exceed 480 V  
Selectable primary current range: 1 – 20 000 A (Using CLSE-  
R5 the unit is configurable only with configurator software.)  
Operational range  
mm (inch)  
■Recommended solderless terminal size - M3.5  
Current: 0 – 120 % of the rating  
Voltage: 10 – 120 % of the rating  
Apparent power: ≤ 120 % of the rating  
Active/reactive power: ±120 % of the rating  
Frequency: 45 – 65 Hz  
3. (.1 ) max  
mm (inch)  
Power factor: ±1  
R9CWTU SPECIFICATIONS  
ES-6222 Rev.8 Page 2/7  
http://www.m-system.co.jp/  
MODEL: R9CWTU  
INSTALLATION  
Auxiliary power supply  
AC: < 9 VA  
DC: < 3 W  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Surface or DIN rail  
Weight: 500 g (1.1 lb)  
PERFORMANCE  
Accuracy (at 10 - 35°C or 50 - 95°F, 45 – 65 Hz)*1  
Add the accuracy of the current sensor for overall values.  
Voltage: ±0.5 % of the rating*2  
Current: ±0.5 % of the rating*2  
Power: ±0.5 % of the rating*2  
Power factor: ±1.5 %  
Frequency: ±0.1 % of the rating*2  
Energy: ±1 %  
Harmonic contents: ±2 % of the rating*2  
*1. Sensor error margin not included  
*2. The described accuracy levels are ensured at the input  
1% or more for neutral current in a 1-phase/3-wire circuit  
and phase-S current in an unbalanced 3-phase/3-wire  
circuit.  
Data update period:  
Harmonic contents and frequency: ≤ 1 sec.  
Other: ≤ 500 msec.  
Calendar clock: (with battery backup)  
Accuracy: Monthly deviation 3 minutes at 25°C  
Back up period: Approx. 2 years at 25°C without power  
With the power on, no battery drain  
Battery: Primary lithium battery (non-removable)  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @ 1 minute (current input or  
voltage input to CC-Link to auxiliary power to FE1)  
EXTERNAL VIEW  
FRONT VIEW  
3
2
1
9
8ch 8 8ch 7 7ch 6 7ch 5 6ch 4 6ch 3 5ch 2 5ch 1  
CC-Link Terminals  
Terminal Block, Current Input 2  
DB DG DA  
5
T2 3L 1L 3L 1L 3L 1L 3L 1L  
18 8ch 17 8ch 16 7ch 15 7ch 14 6ch 13 6ch 12 5ch 11 5ch 10  
7
6
4
NC NC SLD FE  
T1 3K 1K 3K 1K 3K 1K 3K 1K  
Terminating Resistor SW  
Term on  
SD Card Slot  
STATION  
Station Address Setting Rotary SW  
Baud Rate Setting Rotary SW  
Operating Mode Setting DIP SW (SW1)  
PC Configurator Connection Jack  
Status Indicator / CC-Link LED  
Terminal Block,  
Voltage Input / Auxiliary Power Supply  
10 1ch 11 1ch 12 2ch 13 2ch 14 3ch 15 3ch 16 4ch 17 4ch 18  
NC 1K 3K 1K 3K 1K 3K 1K 3K  
4
5
6
7
P1 P2 P3  
1
N
3
Terminal Block, Current Input 1  
2
1
1ch  
2 1ch 3 2ch 4 2ch 5 3ch 6 3ch 7 4ch 8 4ch 9  
(
U +  
)
(-)  
V
FE1  
NC 1L 3L 1L 3L 1L 3L 1L 3L  
R9CWTU SPECIFICATIONS  
ES-6222 Rev.8 Page 3/7  
http://www.m-system.co.jp/  
MODEL: R9CWTU  
TERMINAL CONNECTIONS  
Use the model CLSE clamp sensor for current inputs.  
The figure below shows only one circuit.  
A maximum of eight (8) current sensor inputs can be connected (Ch. 1 through Ch. 8).  
Grounding is not required for low voltage circuits.  
System /  
Application  
System /  
Application  
Terminal  
Terminal  
P1 P2 P3 1K 1L  
P1  
N
1K 1L  
k
l
source  
L1  
load  
k
l
source  
L1  
load  
K
L
K
L
L2  
L3  
Three-phase  
/ 3-wire  
N
Single-phase  
/ 2-wire  
balanced  
load  
P1 P2 P3  
1K 1L  
P1  
N
1K 1L  
u
v
v
u
u
v
k
l
source  
L1  
load  
k
l
U
V
V
U
source  
L1  
U
V
load  
K
L
K
L
L2  
L3  
N
P1  
N P3 1K 1L 3K 3L  
P1 P2 P3 1K 1L 3K 3L  
k
l
source  
L1  
N
load  
k
l
source  
L1  
load  
K
L
k
l
K
L
k
l
L2  
L3  
Three-phase  
/ 3-wire  
L2  
K
L
K
L
Single-phase  
/ 3-wire  
unbalanced  
load  
P1  
N
P3  
1K 1L 3K 3L  
P1 P2 P3  
1K 1L 3K 3L  
u
v
v
u
u
v
v
u
k
l
source  
L1  
load  
U
V
V
U
k
l
source  
L1  
load  
U
V
V
U
K
L
k
l
K
L
k
l
N
L2  
L3  
L2  
K
L
K
L
COMMUNICATION CABLE CONNECTIONS  
MASTER CONNECTION  
Master Unit  
Remote Unit  
Remote Unit  
TERMINATOR  
TERMINATOR  
blue  
DA  
DB  
DA  
DB  
DA  
DB  
white  
yellow  
DG  
SLD  
FG  
DG  
SLD  
FE  
DG  
SLD  
FE  
Be sure to connect the terminating resistor across DA and DB at both ends of communication line.  
When this unit is located at an end, turn the terminating resistor SW ON.  
The Master Unit can be located at not only both ends but also any node of the of communication line.  
R9CWTU SPECIFICATIONS  
ES-6222 Rev.8 Page 4/7  
http://www.m-system.co.jp/  
MODEL: R9CWTU  
TERMINAL ASSIGNMENTS  
• CC-Link  
• Current Input 2  
3
DB DG DA  
2
1
9
8ch  
3L  
8
8ch  
1L  
7
7ch  
3L  
6
7ch  
1L  
5
6ch  
3L  
4
6ch  
1L  
3
5ch  
3L  
2
5ch  
1L  
1
T2  
7
6
5
NC NC SLD FE  
4
18 8ch 17 8ch 16 7ch 15 7ch 14 6ch 13 6ch 12 5ch 11 5ch 10  
T1  
3K  
1K  
3K  
1K  
3K  
1K  
3K  
1K  
No.  
ID  
FUNCTION  
No.  
ID  
FUNCTION  
No.  
ID  
FUNCTION  
1
2
3
4
5
6
7
DA  
DG  
DB  
FE  
DA  
1
2
3
4
5
6
7
8
9
5ch 1L Ch.5, Current input 1L  
5ch 3L Ch.5, Current input 3L  
6ch 1L Ch.6, Current input 1L  
6ch 3L Ch.6, Current input 3L  
7ch 1L Ch.7, Current input 1L  
7ch 3L Ch.7, Current input 3L  
8ch 1L Ch.8, Current input 1L  
8ch 3L Ch.8, Current input 3L  
10  
11  
12  
13  
14  
15  
16  
17  
18  
5ch 1K Ch.5, Current input 1K  
5ch 3K Ch.5, Current input 3K  
6ch 1K Ch.6, Current input 1K  
6ch 3K Ch.6, Current input 3K  
7ch 1K Ch.7, Current input 1K  
7ch 3K Ch.7, Current input 3K  
8ch 1K Ch.8, Current input 1K  
8ch 3K Ch.8, Current input 3K  
DG  
DB  
CC-Link ground  
SLD Shield  
NC  
NC  
Unused  
Unused  
T2  
Unused  
T1  
Unused  
• Auxiliary Power Supply, Voltage Input  
4
5
P2  
6
P3  
7
• Current Input 1  
P1  
N
1
2
3
10 1ch 11 1ch 12 2ch 13 2ch 14 3ch 15 3ch 16 4ch 17 4ch 18  
U(+) V(−) FE1  
NC  
1K  
3K  
1K  
3K  
1K  
3K  
1K  
3K  
1
1ch  
2
1ch  
3
2ch  
4
2ch  
5
3ch  
6
3ch  
7
4ch  
8
4ch  
9
NC  
1L  
3L  
1L  
3L  
1L  
3L  
1L  
3L  
No.  
ID  
FUNCTION  
1
2
3
4
5
6
7
U(+) Auxiliary power (+)  
V(−) Auxiliary power (−)  
FE1 Power ground  
No.  
ID  
FUNCTION  
Unused  
No.  
ID  
FUNCTION  
Unused  
1
2
3
4
5
6
7
8
9
NC  
10  
11  
12  
13  
14  
15  
16  
17  
18  
NC  
P1  
P2  
P3  
N
Voltage input P1  
Voltage input P2  
Voltage input P3  
Voltage input N  
1ch 1L Ch.1, Current input 1L  
1ch 3L Ch.1, Current input 3L  
2ch 1L Ch.2, Current input 1L  
2ch 3L Ch.2, Current input 3L  
3ch 1L Ch.3, Current input 1L  
3ch 3L Ch.3, Current input 3L  
4ch 1L Ch.4, Current input 1L  
4ch 3L Ch.4, Current input 3L  
1ch 1K Ch.1, Current input 1K  
1ch 3K Ch.1, Current input 3K  
2ch 1K Ch.2, Current input 1K  
2ch 3K Ch.2, Current input 3K  
3ch 1K Ch.3, Current input 1K  
3ch 3K Ch.3, Current input 3K  
4ch 1K Ch.4, Current input 1K  
4ch 3K Ch.4, Current input 3K  
R9CWTU SPECIFICATIONS  
ES-6222 Rev.8 Page 5/7  
http://www.m-system.co.jp/  
MODEL: R9CWTU  
EXTERNAL DIMENSIONS unit: mm (inch)  
43−M3 SCREW TERMINAL  
6 (.24)  
4 − 4.5 (.18) dia. MTG HOLE  
DIN RAIL  
35 mm wide  
75 (2.95)  
6.5 (.25)  
[4 (.16)]  
125 (4.92)  
80 (3.15)  
7−M3.5 SCREW TERMINALS  
7.3 (.29)  
MOUNTING REQUIREMENTS unit: mm (inch)  
SINGLE MOUNTING  
75 (2.95)  
4M4  
Pitch 130 (5.12) min.  
BASIC + EXTENSION UNIT  
75 (2.95)  
70.5 (2.78)  
6M4  
Pitch 223 (8.78) min.  
R9CWTU SPECIFICATIONS  
ES-6222 Rev.8 Page 6/7  
http://www.m-system.co.jp/  
MODEL: R9CWTU  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
1
3
2
5
4
6
7
DA  
U(+)  
V(-)  
FE1  
P1  
1
2
3
4
5
6
7
AUXILIARY  
POWER SUPPLY  
DB  
Isolation  
To other  
Comm.  
Circuit  
DG  
SLD  
FE  
COMMUNICATION  
CC-Link devices  
AUX. POWER SUPPLY  
VOLTAGE INPUT  
P2  
VOLTAGE  
NC  
NC  
P3  
N
1K 11  
1L  
3K 12  
3L  
1K 13  
1L  
3K 14  
3L  
1K 15  
1L  
3K 16  
3L  
1K 17  
1L  
3K 18  
10  
1
1K  
1L  
3K  
3L  
2
Ch. 1  
Ch. 5  
CURRENT  
CURRENT  
11  
2
3
12  
3
1K  
1L  
3K  
3L  
Control  
Circuit  
4
Ch. 2  
Ch. 6  
CURRENT INPUT 1  
CURRENT  
CURRENT  
13  
4
5
CURRENT INPUT 2  
14  
5
1K  
1L  
3K  
3L  
6
Ch. 3  
Ch. 7  
CURRENT  
CURRENT  
15  
6
7
16  
7
1K  
1L  
3K  
3L  
T1  
T2  
8
Ch. 4  
Ch. 8  
CURRENT  
CURRENT  
17  
8
3L  
NC  
NC  
9
1
9
10  
18  
Specifications are subject to change without notice.  
R9CWTU SPECIFICATIONS  
ES-6222 Rev.8 Page 7/7  
http://www.m-system.co.jp/  

相关型号:

R9CWTU-2001-AD4/2

Remote I/O R9 Series MULTI POWER MONITORING UNIT
MSYSTEM

R9CWTU-2001-AD4/Q

Remote I/O R9 Series MULTI POWER MONITORING UNIT
MSYSTEM

R9EWTU

Remote I/O R9 Series MULTI POWER MONITORING UNIT
MSYSTEM

R9EWTU-2001-AD4

Remote I/O R9 Series MULTI POWER MONITORING UNIT
MSYSTEM

R9EWTU-2001-AD4/Q

Remote I/O R9 Series MULTI POWER MONITORING UNIT
MSYSTEM

R9F64110

Thermal Magnetic Circuit Breaker,
SCHNEIDER

R9G00.512XXWA

Rectifier Diode, 1 Phase, 1 Element, 1200A, 50V V(RRM), Silicon, R9G, 2 PIN
POWEREX

R9G00.518XXWA

Rectifier Diode, 1 Phase, 1 Element, 1800A, 50V V(RRM), Silicon, R9G, 2 PIN
POWEREX

R9G00.522XXWA

Rectifier Diode, 1 Phase, 1 Element, 2200A, 50V V(RRM), Silicon, R9G, 2 PIN
POWEREX

R9G00112XXWA

Rectifier Diode, 1 Phase, 1 Element, 1200A, 100V V(RRM), Silicon, R9G, 2 PIN
POWEREX

R9G00118

Diode,
POWEREX

R9G00118XXWA

Rectifier Diode, 1 Phase, 1 Element, 1800A, 100V V(RRM), Silicon, R9G, 2 PIN
POWEREX