R9CWTU-2001-AD4 [MSYSTEM]
Remote I/O R9 Series MULTI POWER MONITORING UNIT;型号: | R9CWTU-2001-AD4 |
厂家: | M-SYSTEM |
描述: | Remote I/O R9 Series MULTI POWER MONITORING UNIT 监视器 |
文件: | 总7页 (文件大小:279K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R9CWTU
Remote I/O R9 Series
EXTENSION UNIT
1: With connection
MULTI POWER MONITORING UNIT
(Clamp-on current sensor CLSE, CC-Link)
Functions & Features
AUXILIARY POWER SUPPLY
AD4: universal
• Multi Power Monitoring Unit for CC-Link.
• By using clamp-on current sensors, there is no need of
current transformers.
100 – 240 V AC (Operational range 85 – 264 V, 50 / 60 Hz) /
110 – 240 V DC (Operational range 99 – 264 V,
ripple 10 %p-p max)
• Up to 8 circuits can be measured. (Common voltage
measurement)
[1] OPTIONS (multiple selections)
CC-Link Version
• Current sensors are easy to install in existing systems.
Wide input range of 5 to 600 A is availabe.
• All measured values, counter values, display mode,
setting data are stored in the non-volatile memory when
power is off.
blank: Ver.1.10
/2: Ver.2.0
Other Options
blank: none
• By using SD card, data logging of current and power etc.
with calendar is available.
/Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
125 (4.92)
/C02: Polyurethane coating
/C03: Rubber coating
140 (5.51)
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
(No. ESU-6222)
80 (3.15)
mm (inch)
RELATED PRODUCTS
• Discrete I/O extension unit (model: R9WTU-ED)
• Multi power monitoring extension unit (model: R9WTU-EP)
• PC configurator software (model: PMCFG)
Downloadable at M-System’s web site.
MODEL: R9CWTU–2001–AD4[1]
ORDERING INFORMATION
• Code number: R9CWTU-2001-AD4[1]
Specify a code from below for [1].
(e.g. R9CWTU-2001-AD4/2/Q)
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
• Specify the specification for option code /Q
(e.g. /C01/SET)
• Clamp-on current sensor (model: CLSE)
The clamp-on current sensors, not included in this product
package, must be ordered separately. Required number
depends upon the system configuration.
• SD card
CONFIGURATION
2: Single-phase/2-wire, 3-phase/3-wire, single-phase/3-wire; 8 circuits
A SD card is required to store data in the unit.
Use the specified model number of memory card.
Available for purchase from M-System. Consult M-System.
- Hagiwara Solutions NSD6-004GH(B21SEI
(NSD6-004GH(A00SDI, NSDA-004GT,
CONNECTION
0: Terminal block
NSDA-004GL ... discontinued)
I/O
- Apacer Technology AP-ISD04GIS4B-3T
(AP-ISD04GIS4B-T ... discontinued)
0: Without
R9CWTU SPECIFICATIONS
ES-6222 Rev.8 Page 1/7
http://www.m-system.co.jp/
MODEL: R9CWTU
GENERAL SPECIFICATIONS
Construction: Stand-alone
CC-Link COMMUNICATION
CC-Link: Ver.1.10/Ver.2.0
Degree of protection: IP20
Station Type: Remote device
Connection
Connector: M3 screw terminal
Auxiliary power or voltage input: M3.5 screw terminals
(torque 0.8 N·m)
Network cable: CC-Link cable designated by Mitsubishi
Electric
Current input: M3 screw terminals (torque 0.5 N·m)
CC-Link: M3 screw terminals (torque 0.5 N·m)
Solderless terminal: Refer to the drawing at the end of the
section.
Station number: 1 - 64 (set by rotary switch)
Baud rate setting: 156 kbps (default), 625 kbps, 2.5 Mbps,
5 Mbps, 10 Mbps (selected by rotary switch)
CC-Link LED: Run, RD, SD, ERR
Ver.1.10
Recommended manufacturer: Japan Solderless Terminal
MFG.Co.Ltd, Nichifu Co.,ltd
No.of occupied stations: 1
Applicable wire size
Configuration: Via PC configurator software or CC-Link
Data acquisition: Data is read by command-driven
program
M3 screw terminal: 0.25 to 1.65 mm
2
(AWG 22 to 16)
(AWG 16 to 14)
M3.5 screw terminal: 1.04 to 2.63 mm
2
Configuration: Single-phase/2-wire, single-phase/3-wire, 3-
phase/3-wire
Ver.2.0
No.of occupied stations: 4 (Extended cyclic: 8)
Configuration: Via PC configurator software
Data acquisition: Max. 62 points of data can be
designated and read
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (black)
Isolation: Sensor core to sensor output or current input or
voltage input to CC-Link to auxiliary power to FE1
■ Measured variables
Terminating resistor: Built-in (Set by DIP SW; disabled at
default)
Voltage: R – N, S – N, T – N, R – S, S – T, T – R
Current: R, S, T, N
INPUT SPECIFICATIONS
Frequency: 50 / 60 Hz (45 – 65 Hz)
• Voltage Input
Active / reactive / apparent power: R, S, T, Σ
Power factor: R, S, T, Σ
Frequency
Rated voltage
Active energy: Incoming
•Between lines: 400 V AC
Reactive energy: Incoming lag
•Line-neutral (phase voltage): 230 V (single-phase / 2-wire
and 3-wire)
Active / reactive / apparent power intervals (demand)
Average (demand) current: R, S, T, N
Harmonic contents: Σ
Input burden: ≤ ULN2 / 300 kΩ / phase
Overload capacity: 200 % of rating for 10 sec., 120 %
continuous
Voltage: R - N, S - N, T - N, R - S, S - T, T - R
Current: R, S, T, N
Selectable primary voltage range: 50 – 400 000 V
• Current Input
Max. and min. values
Calendar log (inserting SD card): Voltage, Current, power,
electric energy, power factor
CLSE-R5: 0 – 5 A AC
CLSE-05: 0 – 50 A AC
Operating mode setting: Connection, clamp-on sensor
selection
CLSE-10: 0 – 100 A AC
CLSE-20: 0 – 200 A AC
Status indicators: Power, SD Card
■Recommended solderless terminal size - M3
CLSE-40: 0 – 400 A AC
CLSE-60: 0 – 600 A AC
3.3 (.13) max
Overload capacity: 120 % continous, 500 % for 10 sec.
Note: Use for the circuit not exceed 480 V
Selectable primary current range: 1 – 20 000 A (Using CLSE-
R5 the unit is configurable only with configurator software.)
Operational range
mm (inch)
■Recommended solderless terminal size - M3.5
Current: 0 – 120 % of the rating
Voltage: 10 – 120 % of the rating
Apparent power: ≤ 120 % of the rating
Active/reactive power: ±120 % of the rating
Frequency: 45 – 65 Hz
3. (.1 ) max
mm (inch)
Power factor: ±1
R9CWTU SPECIFICATIONS
ES-6222 Rev.8 Page 2/7
http://www.m-system.co.jp/
MODEL: R9CWTU
INSTALLATION
Auxiliary power supply
•AC: < 9 VA
•DC: < 3 W
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail
Weight: 500 g (1.1 lb)
PERFORMANCE
Accuracy (at 10 - 35°C or 50 - 95°F, 45 – 65 Hz)*1
Add the accuracy of the current sensor for overall values.
Voltage: ±0.5 % of the rating*2
Current: ±0.5 % of the rating*2
Power: ±0.5 % of the rating*2
Power factor: ±1.5 %
Frequency: ±0.1 % of the rating*2
Energy: ±1 %
Harmonic contents: ±2 % of the rating*2
*1. Sensor error margin not included
*2. The described accuracy levels are ensured at the input
1% or more for neutral current in a 1-phase/3-wire circuit
and phase-S current in an unbalanced 3-phase/3-wire
circuit.
Data update period:
Harmonic contents and frequency: ≤ 1 sec.
Other: ≤ 500 msec.
Calendar clock: (with battery backup)
Accuracy: Monthly deviation 3 minutes at 25°C
Back up period: Approx. 2 years at 25°C without power
With the power on, no battery drain
Battery: Primary lithium battery (non-removable)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute (current input or
voltage input to CC-Link to auxiliary power to FE1)
EXTERNAL VIEW
FRONT VIEW
3
2
1
9
8ch 8 8ch 7 7ch 6 7ch 5 6ch 4 6ch 3 5ch 2 5ch 1
CC-Link Terminals
Terminal Block, Current Input 2
DB DG DA
5
T2 3L 1L 3L 1L 3L 1L 3L 1L
18 8ch 17 8ch 16 7ch 15 7ch 14 6ch 13 6ch 12 5ch 11 5ch 10
7
6
4
NC NC SLD FE
T1 3K 1K 3K 1K 3K 1K 3K 1K
Terminating Resistor SW
Term on
SD Card Slot
STATION
Station Address Setting Rotary SW
Baud Rate Setting Rotary SW
Operating Mode Setting DIP SW (SW1)
PC Configurator Connection Jack
Status Indicator / CC-Link LED
Terminal Block,
Voltage Input / Auxiliary Power Supply
10 1ch 11 1ch 12 2ch 13 2ch 14 3ch 15 3ch 16 4ch 17 4ch 18
NC 1K 3K 1K 3K 1K 3K 1K 3K
4
5
6
7
P1 P2 P3
1
N
3
Terminal Block, Current Input 1
2
1
1ch
2 1ch 3 2ch 4 2ch 5 3ch 6 3ch 7 4ch 8 4ch 9
(
U +
)
(-)
V
FE1
NC 1L 3L 1L 3L 1L 3L 1L 3L
R9CWTU SPECIFICATIONS
ES-6222 Rev.8 Page 3/7
http://www.m-system.co.jp/
MODEL: R9CWTU
TERMINAL CONNECTIONS
Use the model CLSE clamp sensor for current inputs.
The figure below shows only one circuit.
A maximum of eight (8) current sensor inputs can be connected (Ch. 1 through Ch. 8).
Grounding is not required for low voltage circuits.
System /
Application
System /
Application
Terminal
Terminal
P1 P2 P3 1K 1L
P1
N
1K 1L
k
l
source
L1
load
k
l
source
L1
load
K
L
K
L
L2
L3
Three-phase
/ 3-wire
N
Single-phase
/ 2-wire
balanced
load
P1 P2 P3
1K 1L
P1
N
1K 1L
u
v
v
u
u
v
k
l
source
L1
load
k
l
U
V
V
U
source
L1
U
V
load
K
L
K
L
L2
L3
N
P1
N P3 1K 1L 3K 3L
P1 P2 P3 1K 1L 3K 3L
k
l
source
L1
N
load
k
l
source
L1
load
K
L
k
l
K
L
k
l
L2
L3
Three-phase
/ 3-wire
L2
K
L
K
L
Single-phase
/ 3-wire
unbalanced
load
P1
N
P3
1K 1L 3K 3L
P1 P2 P3
1K 1L 3K 3L
u
v
v
u
u
v
v
u
k
l
source
L1
load
U
V
V
U
k
l
source
L1
load
U
V
V
U
K
L
k
l
K
L
k
l
N
L2
L3
L2
K
L
K
L
COMMUNICATION CABLE CONNECTIONS
MASTER CONNECTION
Master Unit
Remote Unit
Remote Unit
TERMINATOR
TERMINATOR
blue
DA
DB
DA
DB
DA
DB
white
yellow
DG
SLD
FG
DG
SLD
FE
DG
SLD
FE
Be sure to connect the terminating resistor across DA and DB at both ends of communication line.
When this unit is located at an end, turn the terminating resistor SW ON.
The Master Unit can be located at not only both ends but also any node of the of communication line.
R9CWTU SPECIFICATIONS
ES-6222 Rev.8 Page 4/7
http://www.m-system.co.jp/
MODEL: R9CWTU
TERMINAL ASSIGNMENTS
• CC-Link
• Current Input 2
3
DB DG DA
2
1
9
8ch
3L
8
8ch
1L
7
7ch
3L
6
7ch
1L
5
6ch
3L
4
6ch
1L
3
5ch
3L
2
5ch
1L
1
T2
7
6
5
NC NC SLD FE
4
18 8ch 17 8ch 16 7ch 15 7ch 14 6ch 13 6ch 12 5ch 11 5ch 10
T1
3K
1K
3K
1K
3K
1K
3K
1K
No.
ID
FUNCTION
No.
ID
FUNCTION
No.
ID
FUNCTION
1
2
3
4
5
6
7
DA
DG
DB
FE
DA
1
2
3
4
5
6
7
8
9
5ch 1L Ch.5, Current input 1L
5ch 3L Ch.5, Current input 3L
6ch 1L Ch.6, Current input 1L
6ch 3L Ch.6, Current input 3L
7ch 1L Ch.7, Current input 1L
7ch 3L Ch.7, Current input 3L
8ch 1L Ch.8, Current input 1L
8ch 3L Ch.8, Current input 3L
10
11
12
13
14
15
16
17
18
5ch 1K Ch.5, Current input 1K
5ch 3K Ch.5, Current input 3K
6ch 1K Ch.6, Current input 1K
6ch 3K Ch.6, Current input 3K
7ch 1K Ch.7, Current input 1K
7ch 3K Ch.7, Current input 3K
8ch 1K Ch.8, Current input 1K
8ch 3K Ch.8, Current input 3K
DG
DB
CC-Link ground
SLD Shield
NC
NC
Unused
Unused
T2
Unused
T1
Unused
• Auxiliary Power Supply, Voltage Input
4
5
P2
6
P3
7
• Current Input 1
P1
N
1
2
3
10 1ch 11 1ch 12 2ch 13 2ch 14 3ch 15 3ch 16 4ch 17 4ch 18
U(+) V(−) FE1
NC
1K
3K
1K
3K
1K
3K
1K
3K
1
1ch
2
1ch
3
2ch
4
2ch
5
3ch
6
3ch
7
4ch
8
4ch
9
NC
1L
3L
1L
3L
1L
3L
1L
3L
No.
ID
FUNCTION
1
2
3
4
5
6
7
U(+) Auxiliary power (+)
V(−) Auxiliary power (−)
FE1 Power ground
No.
ID
FUNCTION
Unused
No.
ID
FUNCTION
Unused
1
2
3
4
5
6
7
8
9
NC
10
11
12
13
14
15
16
17
18
NC
P1
P2
P3
N
Voltage input P1
Voltage input P2
Voltage input P3
Voltage input N
1ch 1L Ch.1, Current input 1L
1ch 3L Ch.1, Current input 3L
2ch 1L Ch.2, Current input 1L
2ch 3L Ch.2, Current input 3L
3ch 1L Ch.3, Current input 1L
3ch 3L Ch.3, Current input 3L
4ch 1L Ch.4, Current input 1L
4ch 3L Ch.4, Current input 3L
1ch 1K Ch.1, Current input 1K
1ch 3K Ch.1, Current input 3K
2ch 1K Ch.2, Current input 1K
2ch 3K Ch.2, Current input 3K
3ch 1K Ch.3, Current input 1K
3ch 3K Ch.3, Current input 3K
4ch 1K Ch.4, Current input 1K
4ch 3K Ch.4, Current input 3K
R9CWTU SPECIFICATIONS
ES-6222 Rev.8 Page 5/7
http://www.m-system.co.jp/
MODEL: R9CWTU
EXTERNAL DIMENSIONS unit: mm (inch)
43−M3 SCREW TERMINAL
6 (.24)
4 − 4.5 (.18) dia. MTG HOLE
DIN RAIL
35 mm wide
75 (2.95)
6.5 (.25)
[4 (.16)]
125 (4.92)
80 (3.15)
7−M3.5 SCREW TERMINALS
7.3 (.29)
MOUNTING REQUIREMENTS unit: mm (inch)
■ SINGLE MOUNTING
75 (2.95)
4–M4
Pitch 130 (5.12) min.
■ BASIC + EXTENSION UNIT
75 (2.95)
70.5 (2.78)
6–M4
Pitch 223 (8.78) min.
R9CWTU SPECIFICATIONS
ES-6222 Rev.8 Page 6/7
http://www.m-system.co.jp/
MODEL: R9CWTU
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
1
3
2
5
4
6
7
DA
U(+)
V(-)
FE1
P1
1
2
3
4
5
6
7
AUXILIARY
POWER SUPPLY
DB
Isolation
To other
Comm.
Circuit
DG
SLD
FE
COMMUNICATION
CC-Link devices
AUX. POWER SUPPLY
VOLTAGE INPUT
P2
VOLTAGE
NC
NC
P3
N
1K 11
1L
3K 12
3L
1K 13
1L
3K 14
3L
1K 15
1L
3K 16
3L
1K 17
1L
3K 18
10
1
1K
1L
3K
3L
2
Ch. 1
Ch. 5
CURRENT
CURRENT
11
2
3
12
3
1K
1L
3K
3L
Control
Circuit
4
Ch. 2
Ch. 6
CURRENT INPUT 1
CURRENT
CURRENT
13
4
5
CURRENT INPUT 2
14
5
1K
1L
3K
3L
6
Ch. 3
Ch. 7
CURRENT
CURRENT
15
6
7
16
7
1K
1L
3K
3L
T1
T2
8
Ch. 4
Ch. 8
CURRENT
CURRENT
17
8
3L
NC
NC
9
1
9
10
18
Specifications are subject to change without notice.
R9CWTU SPECIFICATIONS
ES-6222 Rev.8 Page 7/7
http://www.m-system.co.jp/
相关型号: