D1U86P-D-1600-12-HB3DC [MURATA]
86mm 1U Front End DC-DC Power Supply Converter;型号: | D1U86P-D-1600-12-HB3DC |
厂家: | muRata |
描述: | 86mm 1U Front End DC-DC Power Supply Converter |
文件: | 总5页 (文件大小:229K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
D1U86-D-1600-12-HxxDC Series
86mm 1U Front End DC-DC Power Supply Converter
PRODUCT OVERVIEW
The D1U86P-D-1600-12-HxxDC series are highly efficient 1600 watt, DC input front end supplies with a
12V main output and a 12V (30W) standby. They have current sharing and up to 8 supplies may be oper-
ated in parallel. The supplies may be hot plugged, they recover from overtemperature faults, and have
logic and PMBus monitoring and control. Their low profile 1U package and >38.6W/cubic inch power
density make them ideal for delivering reliable, efficient power to servers, workstations, storage systems
and other 12V distributed power systems.
ORDERING GUIDE
Part Number
Power Output
1600W
Main Output
12Vdc
Standby Output1
12Vdc
Airflow
FEATURES
1600W output power
D1U86P-D-1600-12-HB4DC
D1U86P-D-1600-12-HB3DC
Back to front
Front to back
93% efficiency at half load
12V main output
INPUT CHARACTERISTICS
Parameter
12V standby output of 30W
Conditions
Min.
-40
-43
Nom.
-48
-43.5
-39
Max.
Units
Vdc
1U height: 3.4" x 7.75" x 1.59"
Input Voltage Operating Range
Turn-on Voltage
Turn-off Voltage
-72
-44
-39.5
47
50
100
Ramp up
Ramp down
Maximum Current at Vin = -40Vdc 1600W
38.6 Watts per cubic inch density
Vdc
Adc
Apk
-38.5
N+1 redundancy, including hot plugging (up to
8 in parallel)
40
72
DC Line Inrush Peak Current
Efficiency (48V)
Cold start between 0 to 200msec
Current sharing on 12V main output, ORing FET
20% load
50% load
100% load
92
93
89
Overvoltage, overcurrent,
overtemperature protection
%
Internal cooling fan (variable speed)
OUTPUT VOLTAGE CHARACTERISTICS
PMBus™ / I²C interface monitoring and control
Output
Parameter
Voltage
Conditions
50% load
Min.
Typ.
Max.
Units
RoHS compliant
Voltage Set Point
12.17
11.4
12.20
3.10
12.23
12.6
Vdc
Line and Load Regulation
Droop
Ripple Voltage & Noise1
mV/A
mV p-p
A
12V
20MHz Bandwidth
50% load
120
133.3
10000
12.03
12.6
Output Current
Load Capacitance
Voltage Set Point
0
0
μF
11.97
11.4
12.0
120
Vdc
Line and Load Regulation
Droop
Ripple Voltage & Noise1
mV/A
mV p-p
A
12VSB
20MHz Bandwidth
120
2.5
350
Output Current
0
0
Load Capacitance
μF
1
Ripple and noise are measured with 0.1 μF of ceramic capacitance and 10 μF of tantalum capacitance on each of the power supply
outputs. A short coaxial cable with 50Ω scope termination is used.
Available now at
www.murata-ps.com/en/3d/acdc.html
CB
Test Certificate
and Test Report
For full details go to
www.murata-ps.com/rohs
www.murata-ps.com/support
D1U86-D-1600-12-HxxDC.A01 Page 1 of 5
D1U86-D-1600-12-HxxDC Series
86mm 1U Front End DC-DC Power Supply Converter
OUTPUT CHARACTERISTICS
Parameter
Output Rise Monotonicity
Startup Time
Conditions
No voltage excursion
DC ramp up
12V, 50% load step, 1.0A/ꢀs di/dt
12VSB, 50% load step, 1.0A/ꢀs di/dt
At 100% load
All outputs remain in regulation
At full load (48V input)
Min.
Typ.
Max.
3
Units
1.5
600
600
s
Transient Response
mV
Current sharing accuracy (up to 8 in parallel)2
Hot Swap Transients
Holdup Time
5
5
%
%
ms
1
ENVIRONMENTAL CHARACTERISTICS
Parameter
Storage Temperature Range
Operating Temperature Range
Operating Humidity
Storage Humidity
Altitude (without derating at 45°C)
Shock
Conditions
Min.
-40
0
5
5
Typ.
Max.
85
55
90
95
Units
°C
Noncondensing
%
m
3000
30G non operating
Operational Vibration
MTBF
1G, 10-500Hz, 1.6G (non-operational)
Per Telcordia SR-322 M1C1@ 40°C
500K
hrs
CSA/UL 60950-1-07-2nd Ed.
Safety Approvals
IEC 60950-1:2005 (2nd Edition) w Am. 1:2009
CE Marking per LVD DIRECTIVE 2006/95/EC
Input Fuse
Weight
Power Supply has internal 60A/170VDC fast blow fuse on the DC line input
1.108kg (2.44lbs)
2
The load current of 100% refers to each power module max load connected in an N+1 configuration; therefore the total load will be “N” x 100% load of each module. The share accuracy of 5% is a fixed
percentage irrespective of the total loading and number of units connected in parallel.
PROTECTION CHARACTERISTICS
Output
Voltage
Parameter
Conditions
Min.
Typ.
70
Max.
Units
An OTP warning will be issued via the PMBus interface when the air inlet exceeds 70°C;
however the power module shall not shut down until critical internal hotspot tempera-
tures are exceeded.
Overtemperature (intake)
°C
V
The unit will shut down when internal hot spot exceed the derating guide lines and auto-
Overtemperature (hotspots) matically recovers when the unit is cooled down. The unit will shut down due to hot spot
at ambient temperature between 55°C-60°C with main 12V at full load.
Overvoltage
55-60
Latching
13.2
137
14.4
154
For overloads (slow) over current events a 147A nominal constant current will be sus-
tained until the output voltage drops below 3VDC. At this point the unit shall shut down
after a 1sec period and remain in that condition for 10secs. The cycle will then repeat.
For severe (short circuit) over current events the unit shall shut down within 1ms and
remain in this condition for 200ms before attempting a re-start. the unit shall attempt
10 shutdown/re-start cycles before permanently latching off. It will then be necessary to
either recycle the DC input or toggle the PSON# input.
12V
Overcurrent
Overvoltage
Overcurrent
Latching
Autorecovery
13.2
2.75
14.4
3.0
V
A
12VSB
TBD
ISOLATION CHARACTERISTICS
Parameter
Conditions
Min.
1500
1500
500
Typ.
Max.
Units
Input to Output - Basic
Input to Chassis - Basic
Output to Chassis
Vdc
Vdc
Vdc
Insulation Safety Rating / Test Voltage
Isolation
www.murata-ps.com/support
D1U86-D-1600-12-HxxDC.A01 Page 2 of 5
D1U86-D-1600-12-HxxDC Series
86mm 1U Front End DC-DC Power Supply Converter
EMISSIONS AND IMMUNITY
Characteristic
Standard
Compliance
Conducted Emissions
ESD Immunity
FCC 47 CFR Part 15/CISPR 22/EN55022
IEC/EN 61000-4-2
IEC/EN 61000-4-3
IEC/EN 61000-4-4
IEC/EN 61000-4-5
IEC/EN 61000-4-6
IEC/EN 61000-4-8
Class A, 6dB margin
Level 3 criteria A
Level 3 criteria B
Level 3 criteria A
Level 2 criteria B
Level 3 criteria A
3 A/m criteria B
Radiated Field Immunity
Electrical Fast Transient Immunity
Surge Immunity
Radiated Field Conducted Immunity
Magnetic Field Immunity
STATUS INDICATORS AND CONTROL SIGNALS
Signal
Description
PSON#
Low = main output on; PSON# can be permanently tied to GND within the host system.
Short pin pulled down on p/s; pulled up to either 3.3V or 12V (max) in the host system. For 3.3V use a 5.11Kꢁ resistor; for 12V
use a 21Kꢁ resistor.
PRESENT#
PS INTERRUPT
ADDR
Open drain PMBus signal; can be left open if not used.
PMBus Address; ADDR can be grounded or left open if not used. If grounded, the address will be 000, if it is open, the default
address will be 111.
ISHARE
PSOK3
Analog representation of main output current; can be left open if not used.
Three level signal based on DC input and DC output status; can be left open if not used.
I2C CLOCK
I2C DATA
I2C clock
I2C data
LED State
Mode
Operating Condition
1. Off
Input Turn-off
Standby
Power-good
Warning
Fault
DC Input is below minimum power-supply turn-on specification
Power supply standby output is operating within normal parameters and main output is disabled
Power supply standby & main outputs are operating within normal parameters and delivering power
Warning condition in power supply has been detected
2. Green – blinking 1Hz
3. Green – solid
4. Yellow – blinking 1Hz
5. Yellow – solid
Fault condition in power supply has been detected.
OUTPUT CONNECTOR AND SIGNAL SPECIFICATION
Pin#
Function
Pin Type
Description
14-26, 39-51 RTN
Power Ground Power and Standby Return
1-13, 52-64
37
12V
12VSB
Power
Power
12V Output
12V Standby Output
Power Supply Output Card Edge
Active low; interrupt line for power supply
fault & warning detection as per PMBus spec
Power Supply Present Signal (shortest pin)
Combination of there power supply output
indicator signals:
64
1
38
36
PSINTERRUPT Output
PRESENT#
Input
35
PSOK3
Analog output 1. DC input OK
2. Power Good
3. Power Supply Fault
Analog representation of main output current.
Typical analog voltage shall be 60.15mV/Amp
of main output current.
34
ISHARE
Analog I/O
33
32
31
30
29
28
27
PSON#
SCL
SDA
GND
N/A
N/A
Input
Input
I/O
Analog I/O
N/A
Power Supply on/off control signal
SMBus/PMBus Clock
SMBus/PMBus Data
Power Supply Signal Ground
Reserved; no User connection
Reserved; no User connection
PMBus Address
33
32
PCB Top Side
PCB Bottom Side
N/A
Analog input
ADDR
CONNECTOR AND SIGNAL SPECIFICATION3 PSOK TRUTH TABLE VS. ANALOG OUTPUT
DC_OK_H
PWR_GOOD_H
PS_FAULT_L
PSOK
OPERATION MODE
No DC Input
Invalid
0
0
1
1
X
0
1
0
1
X
1
1
1
1
0
< 0.1Vdc
(1/3) VDD
(2/3) VDD
VDD
VDD = 3.3Vdc Standby
Power Good
0.2-0.4Vdc
PS Fault
www.murata-ps.com/support
D1U86-D-1600-12-HxxDC.A01 Page 3 of 5
D1U86-D-1600-12-HxxDC Series
86mm 1U Front End DC-DC Power Supply Converter
WIRING DIAGRAM FOR OUTPUT
1-13, 52-64
1-13, 52-64
Main output
load
RTN
RTN 14-26, 39-51
14-26, 39-51
D1U86
D1U86
12VSB
12VSB
37
37
PSON#
RTN
PSON#
33
33
VSB load
FET,BJT,wire
FET,BJT,wire
or switch (debounced)
to turn on 12V main
output
or switch (debounced)
to turn on 12V main
output
RTN
CURRENT SHARING NOTES
Main Output: Current share is achieved using the droop method. Nominal output voltage (12.20V) is achieved at 50% load and output voltage changes at a rate of
3.10mv per amp. Startup of parallel power supplies is not internally synchronized. If more than 1600W combined power is needed, start-up synchronization must
be provided by using a common PS_ON signal. To account for 5% full load current sharing accuracy and the reduction in full load output voltage due to droop,
available output power must be derated by 10% when units are operated in parallel. Internal ORing FETs are provided.
Standby output can be tied together for redundancy but total combined output power must not exceed 30W; Internal MOSFET ORing devices are used.
www.murata-ps.com/support
D1U86-D-1600-12-HxxDC.A01 Page 4 of 5
D1U86-D-1600-12-HxxDC Series
86mm 1U Front End DC-DC Power Supply Converter
MECHANICAL DIMENSIONS
197.70 ±0.65
9.00 ±0.30
230.41 REF
198.05 0.65
AIRFLOW FRONT TO BACK
AIRFLOW BACK TO FRONT
41.90
86.40 ±0.60
10.25 0.40
DC input connector: Terminal Block, Dinkle Enterprise: Part No. DT-7C-B14W-02
Dimensions: 3.4" x 7.75" x 1.59" [86mm x 196.85mm x 39.9mm]
MATING CONNECTOR
Part Number
Description
FCI 10053363-200LF
FCI 10046971-008LF
Right Angle
Vertical
OPTIONAL ACCESSORIES
Description
Part Number
12V D1U86P Output Connector Card
D1U86P-12-CONC
APPLICATION NOTES
Document Number
ACAN-50
Description
D1U86P Output Connector Card
D1U86P Communication Protocol
ACAN-54
This product is subject to the following operating requirements
and the Life and Safety Critical Application Sales Policy:
Refer to: http://www.murata-ps.com/requirements/
Murata Power Solutions, Inc.
11 Cabot Boulevard, Mansfield, MA 02048-1151 U.S.A.
ISO 9001 and 14001 REGISTERED
Murata Power Solutions, Inc. makes no representation that the use of its products in the circuits described herein, or the use of other
technical information contained herein, will not infringe upon existing or future patent rights. The descriptions contained herein do not imply
the granting of licenses to make, use, or sell equipment constructed in accordance therewith. Specifications are subject to change without
notice.
© 2015 Murata Power Solutions, Inc.
www.murata-ps.com/support
D1U86-D-1600-12-HxxDC.A01 Page 5 of 5
相关型号: