OKL-T/6-W5 Series  
s
Programmable Output 6-Amp iLGA SMT PoLs  
PRODUCT OVERVIEW  
The OKL-T/6-W5 series are non-isolated  
efficient Point of Load (PoL) module features  
Point-of-Load (PoL) DC/DC power converters for  
programmable output voltage and On/Off control.  
embedded applications. Featuring inspectable Land These converters also include under voltage lock  
Grid Array (LGA) format, the OKL-T/6-W5 measures out (UVLO), output short circuit protection, over-  
only 0.48 x 0.48 x 0.283 inches max. (12.2 x 12.2  
x 7.2 mm max.).  
The wide input range is 2.4 to 5.5 Volts DC.  
The maximum output current is 6 Amps. Based  
on fixed-frequency synchronous buck converter  
switching topology, the high power conversion  
current and over temperature protections.  
An optional sequence/tracking feature allows  
power sequencing of PoL’s. These units meet all  
standard UL/EN/IEC 60950-1 safety certifications  
(2nd Edition) and RoHS-6 hazardous substance  
compliance.  
Typical unit  
FEATURES  
2.4-5.5Vdc input voltage range  
Programmable output voltage from 0.6-3.3Vdc  
High power conversion efficiency at 93.5%  
Inspectable Land Grid Array  
Contents  
Page  
Description, Connection Diagram, Photograph  
Ordering Guide, Model Numbering, Product Label  
1
2
Drives up to 300 μF ceramic capacitive loads  
On/Off control  
Mechanical Specifications, Input/Output Pinout  
Output Voltage Adustment, Application Notes  
Soldering Guidelines  
Performance Data and Oscillograms  
Tape & Reel Information  
3
5
7
8
Optional Sequence/Tracking operation  
Outstanding thermal derating performance  
Over temperature and over current protection  
Meets UL/EN/IEC 60950-1 safety, 2nd Edition  
RoHS-6 hazardous substance compliance  
15  
Connection Diagram  
+Vin  
+Vout  
Sense  
tꢀ4XJUDIJOH  
tꢀ'JMUFST  
F1  
On/Off  
Control  
Controller  
tꢀ$VSSFOUꢀ4FOTF  
External  
DC  
Trim  
Power  
Source  
Reference and  
Error Amplifier  
Open = On  
Closed = Off  
(Positive  
On/Off)  
Common  
Common  
Sequence/Tracking  
(OKL2 Models)  
Figure 1. OKL-T/6-W5  
Note: Murata Power Solutions strongly recommends an external input fuse, F1. See specifications.  
For full details go to  
www.murata-ps.com/rohs  
www.murata-ps.com  
email: sales@murata-ps.com  
13 May 2010 MDC_OKL-T/6-W5 Series.A02 Page 1 of 15  
OKL-T/6-W5 Series  
Programmable Output 6-Amp iLGA SMT PoLs  
Performance Specifications and Ordering Guide  
ORDERING GUIDE  
Output  
Input  
Package–Pinout P83  
Efficiency  
On/Off Seq/  
Polarity Track  
Model Number  
Regulation (max.)  
Vin nom. Range Iin, no load Iin, full load  
Vout Iout (Amps, Power R/N (mV p-p)  
Case C83  
inches (mm)  
(Volts) ➀  
max.)  
(Watts)  
Max. ➃  
(Volts) (Volts) (mA) (Amps) ➁  
Line  
Load  
Min. Typ.  
0.48x0.48x0.283 max  
(12.2x12.2x7.2) max  
OKL-T/6-W5P-C  
OKL-T/6-W5N-C  
0.6-3.3  
6
19.8  
25  
0.35% 0.35%  
0.35% 0.35%  
0.35% 0.35%  
5
5
5
5
2.4-5.5  
2.4-5.5  
2.4-5.5  
2.4-5.5  
25  
25  
25  
25  
4.24  
4.24  
4.24  
4.24  
91.5% 93.5% Pos.  
91.5% 93.5% Neg.  
no  
no  
0.48x0.48x0.283 max  
(12.2x12.2x7.2) max  
0.6-3.3  
6
6
6
19.8  
19.8  
19.8  
25  
25  
25  
0.48x0.48x0.283 max  
(12.2x12.2x7.2) max  
OKL2-T/6-W5P-C 0.6-3.3  
OKL2-T/6-W5N-C 0.6-3.3  
91.5% 93.5% Pos. yes  
91.5% 93.5% Neg. yes  
0.48x0.48x0.283 max  
(12.2x12.2x7.2) max  
0.35% 0.35%  
The output range (50% load) is limited by Vin. See detailed specs for full conditions.  
Use adequate ground plane and copper thickness adjacent to the converter.  
ꢀꢁRipple and Noise (R/N) are shown at Vout=1V. See specs for details.  
No load input current is shown at Vout = 3.3V.  
All specifications are at nominal line voltage, Vout=nominal (3.3V for W5 models) and full load,  
+25 deg.C. unless otherwise noted.  
Output capacitors are 10 μF ceramic. Input cap is 22 μF. See detailed specifications.  
I/O caps are necessary for our test equipment and may not be needed for your application.  
PART NUMBER STRUCTURE  
OK L 2 - T / 6 - W5 N - C  
Okami Non-isolated PoL  
LGA Surface Mount  
RoHS Hazardous  
Substance Compliance  
C = RoHS-6 (does not claim EU RoHS exemption  
7b–lead in solder)  
Sequence/tracking  
Blank = Not installed  
2 = Installed  
On/Off Polarity  
P = Positive Polarity  
N = Negative Polarity  
Trimmable Output  
Voltage Range  
0.6-3.3Vdc  
Input Voltage Range  
2.4-5.5Vdc  
Maximum Rated Output  
Current in Amps  
Product Label  
Because of the small size of these products, the product label contains a  
character-reduced code to indicate the model number and manufacturing date  
code. Not all items on the label are always used. Please note that the label  
differs from the product photograph. Here is the layout of the label:  
Model Number  
Product Code  
L01006  
OKL-T/6-W5P-C  
OKL-T/6-W5N-C  
OKL2-T/6-W5P-C  
OKL2-T/6-W5N-C  
L00006  
L21006  
L20006  
XXXXXX  
Product code  
Revision level  
Mfg.  
date  
code  
YMDX Rev.  
The manufacturing date code is four characters:  
Figure 2. Label Artwork Layout  
First character – Last digit of manufacturing year, example 2009  
Second character – Month code (1 through 9 and O through D)  
Third character – Day code (1 through 9 = 1 to 9, 10=O and  
11 through 31 = A through Z)  
The label contains three rows of information:  
First row – Murata Power Solutions logo  
Second row – Model number product code (see table)  
Third row – Manufacturing date code and revision level  
Fourth character – Manufacturing information  
www.murata-ps.com  
email: sales@murata-ps.com  
13 May 2010 MDC_OKL-T/6-W5 Series.A02 Page 2 of 15  
OKL-T/6-W5 Series  
Programmable Output 6-Amp iLGA SMT PoLs  
MECHANICAL SPECIFICATIONS  
Top View  
INPUT/OUTPUT CONNECTIONS  
0.043 (1.09)  
NOM. PCB  
THK  
0.48  
(12.19)  
Pin  
1
Function  
On/Off Control*  
VIN  
Bottom View  
2
3
Ground  
4
VOUT  
5
Sense  
6
7
8
9
10  
11  
12  
Trim  
Ground  
0.48  
(12.19)  
No Connection  
Sequence/Tracking  
No Connection  
No Connection  
No Connection  
Side View  
*The Remote On/Off can be provided with  
either positive (P suffix) or negative (N  
suffix) polarity  
0.283  
(7.2)  
max.  
End View  
Recommended Footprint  
-through the Board-  
Bottom View  
0.480 (12.19)  
0.135  
(3.43)  
0.180  
(4.57)  
0.045  
(1.14)  
0.070 x 0.160 x3  
(1.77 x 4.07)  
4
3
2
2
3
4
Vin  
Gnd  
0.420 (10.67)  
0.375 (9.53)  
Gnd  
Vin  
0.180 (4.57)  
0.180 (4.57)  
C
L
0.135 (3.43)  
5
On/Off  
Sense  
NC  
5
11  
6
1
Sense  
On/Off  
C
0.240 (6.10)  
0.150 (3.81)  
1
L
0.090  
(2.29)  
10  
NC  
NC  
11  
6
10  
9
Seq  
Trim  
Gnd  
NC  
0.060 (1.52)  
0
9
Seq NC Gnd NC  
Trim  
8
7
12  
12  
7
8
Dimensions are in inches (mm shown for ref. only).  
0.090  
(2.29)  
Third Angle Projection  
0.180 0.090  
(4.57) (2.29)  
0.040 x 0.040 (9 places)  
(1.01 x 1.01)  
Tolerances (unless otherwise specified):  
.XX 0.02 (0.5)  
.XXX 0.010 (0.25)  
Angles 1ꢀ  
Components are shown for reference only.  
Figure 3. OKL-T/6-W5 Mechanical Outline  
www.murata-ps.com  
email: sales@murata-ps.com  
13 May 2010 MDC_OKL-T/6-W5 Series.A02 Page 3 of 15  
OKL-T/6-W5 Series  
Programmable Output 6-Amp iLGA SMT PoLs  
Dynamic Characteristics  
Performance and Functional Specifications  
See Note 1  
Dynamic Load Response  
50ꢁSec max. to within 2% of final value  
Input  
(50-100% load step, di/dt=1A/μSec)  
Peak Deviation  
(Note 1)  
350 mV  
Input Voltage Range  
Isolation  
See Ordering Guide and Note 7.  
Start-Up Time  
(Vin on or On/Off to Vout regulated)  
6 mSec for Vout=nominal (Vin On)  
6 mSec for Vout=nominal (Remote On/Off)  
Not isolated  
2.05 V  
Start-Up Voltage  
100 kHz  
Switching Frequency  
600 KHz  
Undervoltage Shutdown (see Note 15)  
Overvoltage Shutdown  
1.92 V  
None  
Environmental  
OKL Models  
Reflected (Back) Ripple Current (Note 2) TBD mA pk-pk  
Calculated MTBF (hours)  
Telecordia method (4a)  
OKL2 Models  
5,341  
Internal Input Filter Type  
Capacitive  
5,573,000  
,000  
(hours)  
Calculated MTBF  
Recommended External Fuse  
Reverse Polarity Protection  
TBD  
MIL-HDBK-217N2 method (4b)  
5,999,000  
5,176,000  
None, Install external fuse  
Operating Temperature Range (Ambient, all output ranges)  
Input Current:  
Full Load Conditions  
Inrush Transient  
Shutdown Mode (Off, UV, OT)  
Output in Short Circuit  
Low Line (Vin=Vmin)  
See derating curves  
-40 to +85 °C. with derating (Note 9)  
See Ordering Guide  
TBD  
1 mA  
10 mA  
A2Sec.  
Storage Temperature Range  
Thermal Protection/Shutdown  
-55 to +125 °C.  
Included in PWM  
Relative Humidity  
To 85%/+85 C., non-condensing  
°
4.68 A (Vout = 3.3V)  
Remote On/Off Control (Note 5)  
Negative Logic  
Physical  
ON = Open pin or -0.2V to Vin -1.6V max.  
OFF = Vin -0.8V min. to +Vin max.  
ON = Open pin (internally pulled up) or  
+1.2V to +Vin max.  
OFF = -0.3V to +0.3V max. or ground  
TBD  
Outline Dimensions  
Weight  
See Mechanical Specifications  
0.06 ounces (1.6 grams)  
Positive Logic  
Safety  
Meets UL/cUL 60950-1, CSA-  
C22.2 No. 60950-1, IEC/EN 60950-1,  
2nd Edition  
Current  
RoHS-6 (does not claim EU RoHS exemption  
7b–lead in solder)  
Tracking/Sequencing (optional)  
Slew Rate  
Tracking accuracy, rising input  
Tracking accuracy, falling input  
Restriction of Hazardous Substances  
2 Volts per millisecond, max.  
Vout = 100 mV of Sequence In  
Vout = 100 mV of Sequence In  
Absolute Maximum Ratings  
Input Voltage (Continuous or transient)  
On/Off Control  
0 V. to +6 Volts max.  
0 V. min. to +Vin max.  
Output  
Output Power  
19.8W max.  
Input Reverse Polarity Protection  
Output Current (Note 7)  
None, Install external fuse  
Output Voltage Range  
See Ordering Guide  
No minimum load  
2 % of Vnominal  
See Ordering Guide  
None  
Current-limited. Devices can withstand a  
sustained short circuit without damage.  
The outputs are not intended to accept  
appreciable reverse current.  
Minimum Loading  
Accuracy (50% load, untrimmed)  
Voltage Output Range (Note 13)  
Overvoltage Protection (Note 16)  
Temperature Coefficient  
Ripple/Noise (20 MHz bandwidth)  
Line/Load Regulation  
Storage Temperature  
Lead Temperature  
-55 to +125 °C.  
See soldering specifications  
TBD  
Absolute maximums are stress ratings. Exposure of devices to greater than any of  
any of these conditions may adversely affect long-term reliability. Proper operation  
under conditions other than those listed in the Performance/Functional Specifications  
Table is not implied nor recommended.  
See Ordering Guide and note 8  
See Ordering Guide and note 10  
See Ordering Guide  
Efficiency  
Maximum Capacitive Loading (Note 14)  
Cap-ESR=0.001 to 0.01 Ohms  
Cap-ESR >0.01 Ohms  
Specification Notes:  
300 ꢁF  
TBD  
(1) Specifications are typical at +25 °C, Vin=nominal (+5V), Vout=nominal (+3.3V), full load, external caps and  
natural convection unless otherwise indicated. Extended tests at full power must supply substantial forced airflow.  
Current Limit Inception (Note 6)  
(98% of Vout setting, after warm up) 12 Amps  
All models are tested and specified with external 10ꢁF ceramic output capacitors and a 22 ꢁF external  
input capacitor. All capacitors are low ESR types. These capacitors are necessary to accommodate our test  
equipment and may not be required to achieve specified performance in your applications. However, Murata  
Power Solutions recommends installation of these capacitors. All models are stable and regulate within  
spec under no-load conditions.  
Short Circuit Mode  
Short Circuit Current Output  
Protection Method  
10 mA  
Hiccup autorecovery upon overload  
removal. (Note 17)  
Continuous, no damage  
(output shorted to ground)  
Converter will start up if the external  
output voltage is less than Vnominal.  
(2) Input Back Ripple Current is tested and specified over a 5 Hz to 20 MHz bandwidth. Input filtering is Cin=2 x  
100 ꢁF ceramic, Cbus=1000 ꢁF electrolytic, Lbus=1 ꢁH.  
Short Circuit Duration  
Prebias Startup  
(3) Note that Maximum Power Derating curves indicate an average current at nominal input voltage. At higher  
temperatures and/or lower airflow, the DC/DC converter will tolerate brief full current outputs if the total  
RMS current over time does not exceed the Derating curve.  
(4a) Mean Time Before Failure is calculated using the Telcordia (Belcore) SR-332 Method 1, Case 3, ground fixed  
conditions, Tpcboard=+25 ꢀC, full output load, natural air convection.  
(4b) Mean Time Before Failure is calculated using the MIL-HDBK-217N2 method, ground benign, +25ºC., full  
output load, natural convection.  
(5) The On/Off Control Input should use either a switch or an open collector/open drain transistor referenced  
to -Input Common. A logic gate may also be used by applying appropriate external voltages which do not  
exceed +Vin.  
(6) Short circuit shutdown begins when the output voltage degrades approximately 2% from the selected  
setting.  
www.murata-ps.com  
email: sales@murata-ps.com  
13 May 2010 MDC_OKL-T/6-W5 Series.A02 Page 4 of 15  
OKL-T/6-W5 Series  
Programmable Output 6-Amp iLGA SMT PoLs  
APPLICATION NOTES  
Specification Notes, Cont.:  
(7) Please observe the voltage input and output specifications in the Voltage Range Graph on page 7.  
Input Fusing  
(8) Output noise may be further reduced by adding an external filter. At zero output current, the output may  
contain low frequency components which exceed the ripple specification. The output may be operated  
indefinitely with no load.  
Certain applications and/or safety agencies may require fuses at the inputs  
of power conversion components. Fuses should also be used when there  
is the possibility of sustained input voltage reversal which is not current-  
limited. For greatest safety, we recommend a fast blow fuse installed in the  
ungrounded input supply line.  
(9) All models are fully operational and meet published specifications, including “cold start” at –40ꢀ C.  
(10) Regulation specifications describe the deviation as the line input voltage or output load current is varied  
from a nominal midpoint value to either extreme.  
(11) Other input or output voltage ranges will be reviewed under scheduled quantity special order.  
(12) Maximum PC board temperature is measured with the sensor in the center of the converter.  
(13) Do not exceed maximum power specifications when adjusting the output trim.  
The installer must observe all relevant safety standards and regulations.  
For safety agency approvals, install the converter in compliance with the  
end-user safety standard.  
(14) The maximum output capacitive loads depend on the the Equivalent Series Resistance (ESR) of the external  
output capacitor and, to a lesser extent, the distance and series impedance to the load. Larger caps will  
reduce output noise but may change the transient response. Newer ceramic caps with very low ESR may  
require lower capacitor values to avoid instability. Thoroughly test your capacitors in the application. Please  
refer to the Output Capacitive Load Application Note.  
Input Under-Voltage Shutdown and Start-Up Threshold  
(15) Do not allow the input voltage to degrade lower than the input undervoltage shutdown voltage at all times.  
Otherwise, you risk having the converter turn off. The undervoltage shutdown is not latching and will  
attempt to recover when the input is brought back into normal operating range.  
Under normal start-up conditions, converters will not begin to regulate  
properly until the rising input voltage exceeds and remains at the Start-Up  
Threshold Voltage (see Specifications). Once operating, converters will not  
turn off until the input voltage drops below the Under-Voltage Shutdown  
Limit. Subsequent restart will not occur until the input voltage rises again  
above the Start-Up Threshold. This built-in hysteresis prevents any unstable  
on/off operation at a single input voltage.  
(16) The outputs are not intended to sink appreciable reverse current.  
(17) “Hiccup” overcurrent operation repeatedly attempts to restart the converter with a brief, full-current output.  
If the overcurrent condition still exists, the restart current will be removed and then tried again. This short  
current pulse prevents overheating and damaging the converter. Once the fault is removed, the converter  
immediately recovers normal operation.  
Output Voltage Adustment  
The output voltage may be adjusted over a limited range by connecting an  
external trim resistor (Rtrim) between the Trim pin and Ground. The Rtrim  
resistor must be a 1/10 Watt precision metal film type, 0.5% accuracy or  
better with low temperature coefficient, 100 ppm/ C. or better. Mount the  
°
resistor close to the converter with very short leads or use a surface mount  
trim resistor.  
Users should be aware however of input sources near the Under-Voltage  
Shutdown whose voltage decays as input current is consumed (such as  
capacitor inputs), the converter shuts off and then restarts as the external  
capacitor recharges. Such situations could oscillate. To prevent this, make  
sure the operating input voltage is well above the UV Shutdown voltage AT  
ALL TIMES.  
In the table below, the calculated resistance is given. Do not exceed the  
specified limits of the output voltage or the converter’s maximum power  
rating when applying these resistors. Also, avoid high noise at the Trim  
input. However, to prevent instability, you should never connect any capaci-  
tors to Trim.  
Start-Up Delay  
Assuming that the output current is set at the rated maximum, the Vin to  
Vout Start-Up Delay (see Specifications) is the time interval between the  
point when the rising input voltage crosses the Start-Up Threshold and the  
fully loaded regulated output voltage enters and remains within its specified  
regulation band. Actual measured times will vary with input source imped-  
ance, external input capacitance, input voltage slew rate and final value of  
the input voltage as it appears at the converter.  
Resistor Trim Equation, OKL-T/6-W5 models:  
1.2  
VOUT – 0.6  
___________  
RTRIM (K) =  
These converters include a soft start circuit to moderate the duty cycle of  
the PWM controller at power up, thereby limiting the input inrush current.  
The On/Off Remote Control interval from inception to Vout regulated  
assumes that the converter already has its input voltage stabilized above  
the Start-Up Threshold before the On command. The interval is measured  
from the On command until the output enters and remains within its  
specified accuracy band. The specification assumes that the output is fully  
loaded at maximum rated current.  
Output Voltage  
3.3 V.  
Calculated Rtrim (KΩ)  
0.444  
0.632  
1.0  
2.5 V.  
1.8 V.  
1.5 V.  
1.333  
2.0  
1.2 V.  
Recommended Input Filtering  
1.0 V.  
3.0  
The user must assure that the input source has low AC impedance to  
provide dynamic stability and that the input supply has little or no inductive  
content, including long distributed wiring to a remote power supply. The  
converter will operate with no additional external capacitance if these  
conditions are met.  
0.6 V.  
∞ (open)  
www.murata-ps.com  
email: sales@murata-ps.com  
13 May 2010 MDC_OKL-T/6-W5 Series.A02 Page 5 of 15  
OKL-T/6-W5 Series  
Programmable Output 6-Amp iLGA SMT PoLs  
For best performance, we recommend installing a low-ESR capacitor  
immediately adjacent to the converter’s input terminals. The capacitor  
should be a ceramic type such as the Murata GRM32 series or a polymer  
type. Initial suggested capacitor values are 10 to 22 μF, rated at twice the  
expected maximum input voltage. Make sure that the input terminals do  
not go below the undervoltage shutdown voltage at all times. More input  
bulk capacitance may be added in parallel (either electrolytic or tantalum)  
if needed.  
COPPER STRIP  
+OUTPUT  
RLOAD  
SCOPE  
C1  
C2  
Recommended Output Filtering  
-OUTPUT  
The converter will achieve its rated output ripple and noise with no  
additional external capacitor. However, the user may install more exter-  
nal output capacitance to reduce the ripple even further or for improved  
dynamic response. Again, use low-ESR ceramic (Murata GRM32 series)  
or polymer capacitors. Initial values of 10 to 47 μF may be tried, either  
single or multiple capacitors in parallel. Mount these close to the converter.  
Measure the output ripple under your load conditions.  
COPPER STRIP  
C1 = 1μF CERAMIC  
C2 = 10μF CERAMIC  
LOAD 2-3 INCHES (51-76mm) FROM MODULE  
Figure 5: Measuring Output Ripple and Noise (PARD)  
Use only as much capacitance as required to achieve your ripple and  
noise objectives. Excessive capacitance can make step load recovery  
sluggish or possibly introduce instability. Do not exceed the maximum rated  
output capacitance listed in the specifications.  
Minimum Output Loading Requirements  
All models regulate within specification and are stable under no load to full  
load conditions. Operation under no load might however slightly increase  
output ripple and noise.  
Input Ripple Current and Output Noise  
All models in this converter series are tested and specified for input  
reflected ripple current and output noise using designated external input/  
output components, circuits and layout as shown in the figures below. The  
Cbus and Lbus components simulate a typical DC voltage bus. Please note  
that the values of Cin, Lbus and Cbus will vary according to the specific  
converter model.  
Temperature Derating Curves  
The graphs in the next section illustrate typical operation under a variety of  
conditions. The Derating curves show the maximum continuous ambient air  
temperature and decreasing maximum output current which is accept-  
able under increasing forced airflow measured in Linear Feet per Minute  
(“LFM”). Note that these are AVERAGE measurements. The converter will  
accept brief increases in current or reduced airflow as long as the average  
is not exceeded.  
TO  
CURRENT  
PROBE  
OSCILLOSCOPE  
Note that the temperatures are of the ambient airflow, not the converter  
itself which is obviously running at higher temperature than the outside  
air. Also note that very low flow rates (below about 25 LFM) are similar to  
“natural convection”, that is, not using fan-forced airflow.  
+INPUT  
-INPUT  
LBUS  
+
+
VIN  
CBUS  
CIN  
Murata Power Solutions makes Characterization measurements in a  
closed cycle wind tunnel with calibrated airflow. We use both thermo-  
couples and an infrared camera system to observe thermal performance.  
C
IN = 2 x 100μF, ESR < 700mΩ @ 100kHz  
BUS = 1000μF, ESR < 100mΩ @ 100kHz  
C
LBUS = 1μH  
Figure 4: Measuring Input Ripple Current  
In figure 5, the two copper strips simulate real-world printed circuit  
impedances between the power supply and its load. In order to minimize  
circuit errors and standardize tests between units, scope measurements  
should be made using BNC connectors or the probe ground should not  
exceed one half inch and soldered directly to the test circuit.  
www.murata-ps.com  
email: sales@murata-ps.com  
13 May 2010 MDC_OKL-T/6-W5 Series.A02 Page 6 of 15  
OKL-T/6-W5 Series  
Programmable Output 6-Amp iLGA SMT PoLs  
Output Current Limiting  
Voltage Range Graph  
Current limiting inception is defined as the point at which full power falls  
below the rated tolerance. See the Performance/Functional Specifica-  
tions. Note particularly that the output current may briefly rise above its  
rated value in normal operation as long as the average output power is  
not exceeded. This enhances reliability and continued operation of your  
application. If the output current is too high, the converter will enter the  
short circuit condition.  
Please observe the limits below for voltage input and output ranges. These  
limits apply at all output currents.  
6
5
4
Vin=2.4V / Vout=1.8V  
3
Output Short Circuit Condition  
When a converter is in current-limit mode, the output voltage will drop as  
the output current demand increases. If the output voltage drops too low  
(approximately 98% of nominal output voltage for most models), the mag-  
netically coupled voltage used to develop PWM bias voltage will also drop,  
thereby shutting down the PWM controller. Following a time-out period, the  
PWM will restart, causing the output voltage to begin rising to its appropri-  
ate value. If the short-circuit condition persists, another shutdown cycle  
will initiate. This rapid on/off cycling is called “hiccup mode”. The hiccup  
cycling reduces the average output current, thereby preventing excessive  
internal temperatures and/or component damage.  
2
1
0
Upper Limit  
Lower Limit  
0.5  
1
1.5  
2
2.5  
3
3.5  
Output Voltage (V)  
Soldering Guidelines  
Murata Power Solutions recommends the specifications below when installing these  
converters. These specifications vary depending on the solder type. Exceeding these  
specifications may cause damage to the product. Your production environment may differ  
The “hiccup” system differs from older latching short circuit systems  
because you do not have to power down the converter to make it restart.  
The system will automatically restore operation as soon as the short circuit  
condition is removed.  
therefore please thoroughly review these guidelines with your process engineers.  
Reflow Solder Operations for surface-mount products (SMT)  
For Sn/Ag/Cu based solders:  
Remote On/Off Control  
The remote On/Off Control can be specified with either positive or negative  
logic polarity. Please refer to the Connection Diagram on page 1 for On/Off  
connections.  
Preheat Temperature  
Time over Liquidus  
Less than 1 ºC. per second  
45 to 75 seconds  
Maximum Peak Temperature  
Cooling Rate  
260 ºC.  
Positive polarity models are enabled when the On/Off pin is left open or  
is pulled high to +Vin with respect to –Vin. An internal bias current causes  
the open pin to rise to +Vin. Positive-polarity devices are disabled when the  
On/Off is grounded or brought to within a low voltage (see Specifications)  
with respect to –Vin.  
Less than 3 ºC. per second  
For Sn/Pb based solders:  
Preheat Temperature  
Time over Liquidus  
Less than 1 ºC. per second  
60 to 75 seconds  
Negative polarity devices are on (enabled) when the On/Off is open or  
brought to within a low voltage (see Specifications) with respect to –Vin.  
The device is off (disabled) when the On/Off is pulled high with respect to  
–Vin (see specifications).  
Maximum Peak Temperature  
Cooling Rate  
235 ºC.  
Less than 3 ºC. per second  
Recommended Lead-free Solder Reflow Profile  
Dynamic control of the On/Off function should be able to sink the speci-  
fied signal current when brought low and withstand appropriate voltage  
when brought high. Be aware too that there is a finite time in milliseconds  
(see Specifications) between the time of On/Off Control activation and  
stable, regulated output. This time will vary slightly with output load type  
and current and input conditions.  
Peak Temp.  
235-260° C  
250  
200  
Reflow Zone  
150  
100  
50  
Soaking Zone  
120 sec max  
time above 217° C  
45-75 sec  
Output Capacitive Load  
These converters do not require external capacitance added to achieve  
rated specifications. Users should only consider adding capacitance to  
reduce switching noise and/or to handle spike current load steps. Install  
only enough capacitance to achieve noise objectives. Excess external  
capacitance may cause regulation problems, degraded transient response  
and possible oscillation or instability.  
<1.5° C/sec  
Preheating Zone  
240 sec max  
0
0
30  
60  
90  
120  
150  
Time (sec)  
180  
210  
240  
270  
300  
High trace = normal upper limit  
Low trace - normal lower limit  
www.murata-ps.com  
email: sales@murata-ps.com  
13 May 2010 MDC_OKL-T/6-W5 Series.A02 Page 7 of 15  
OKL-T/6-W5 Series  
Programmable Output 6-Amp iLGA SMT PoLs  
PERFORMANCE DATA, OKL-T/6-W5  
Efficiency vs. Line Voltage and Load Current @ +25°C (VOUT = 3.3V)  
Maximum Current Temperature Derating at Sea Level  
(VIN= 5V, VOUT = 3.3V).  
100  
99  
7
6
5
4
3
2
1
0
Natural convection  
98  
97  
VIN = 4V  
96  
VIN = 5V  
VIN = 5.5V  
95  
94  
93  
0
2
4
6
Load Current (Amps)  
20  
25  
30  
35  
40  
45  
50  
55  
60  
65  
70  
75  
80  
85  
90  
Ambient Temperature (ºC)  
Output Ripple and Noise (Vin=5V, Vout=3.3V, Iout=6A, ScopeBW=100MHz)  
On/Off Enable Startup (Vin=5V, Vout=3.3V, Iout=6A, Cload=0)  
Trace 4=Enable, Trace2=Vout  
Step Load Transient Response (Vin=5V, Vout=3.3V, Iout=6A to 3A)  
Trace 2=Vout, 200 mV/div. Trace 4=Iout, 5A/div.  
Step Load Transient Response (Vin=5V, Vout=3.3V, Iout=3A to 6A)  
Trace 2=Vout, 200 mV/div. Trace 4=Iout, 5A/div.  
www.murata-ps.com  
email: sales@murata-ps.com  
13 May 2010 MDC_OKL-T/6-W5 Series.A02 Page 8 of 15  
OKL-T/6-W5 Series  
Programmable Output 6-Amp iLGA SMT PoLs  
PERFORMANCE DATA, OKL-T/6-W5  
Efficiency vs. Line Voltage and Load Current @ +25°C (VOUT = 2.5V)  
Maximum Current Temperature Derating at Sea Level  
(VIN= 5V, VOUT = 2.5V).  
100  
98  
7
6
5
4
3
2
1
0
Natural convection  
96  
VIN = 3V  
VIN = 5V  
94  
92  
90  
VIN = 5.5V  
0
2
4
6
Load Current (Amps)  
20  
25  
30  
35  
40  
45  
50  
55  
60  
65  
70  
75  
80  
85  
90  
Ambient Temperature (ºC)  
Output Ripple and Noise (Vin=5V, Vout=2.5V, Iout=6A, ScopeBW=100MHz)  
On/Off Enable Startup (Vin=5V, Vout=2.5V, Iout=6A, Cload=0)  
Trace 4=Enable, Trace2=Vout  
Step Load Transient Response (Vin=5V, Vout=2.5V, Iout=6A to 3A)  
Trace 2=Vout, 200 mV/div. Trace 4=Iout, 5A/div.  
Step Load Transient Response (Vin=5V, Vout=2.5V, Iout=3A to 6A)  
Trace 2=Vout, 200 mV/div. Trace 4=Iout, 5A/div.  
www.murata-ps.com  
email: sales@murata-ps.com  
13 May 2010 MDC_OKL-T/6-W5 Series.A02 Page 9 of 15  
OKL-T/6-W5 Series  
Programmable Output 6-Amp iLGA SMT PoLs  
PERFORMANCE DATA, OKL-T/6-W5  
Efficiency vs. Line Voltage and Load Current @ +25°C (VOUT = 1.8V)  
Maximum Current Temperature Derating at Sea Level  
(VIN= 5V, VOUT = 1.8V).  
98  
96  
94  
7
6
5
4
3
2
1
0
Natural convection  
92  
90  
88  
86  
VIN = 2.4V  
VIN = 5V  
VIN = 5.5V  
0
2
4
6
Load Current (Amps)  
20  
25  
30  
35  
40  
45  
50  
55  
60  
65  
70  
75  
80  
85  
90  
Ambient Temperature (ºC)  
Output Ripple and Noise (Vin=5V, Vout=1.8V, Iout=6A, ScopeBW=100MHz)  
On/Off Enable Startup (Vin=5V, Vout=1.8V, Iout=6A, Cload=0)  
Trace 4=Enable, Trace2=Vout  
Step Load Transient Response (Vin=5V, Vout=1.8V, Iout=6A to 3A)  
Trace 2=Vout, 200 mV/div. Trace 4=Iout, 5A/div.  
Step Load Transient Response (Vin=5V, Vout=1.8V, Iout=3A to 6A)  
Trace 2=Vout, 200 mV/div. Trace 4=Iout, 5A/div.  
www.murata-ps.com  
email: sales@murata-ps.com  
13 May 2010 MDC_OKL-T/6-W5 Series.A02 Page 10 of 15  
OKL-T/6-W5 Series  
Programmable Output 6-Amp iLGA SMT PoLs  
PERFORMANCE DATA, OKL-T/6-W5  
Efficiency vs. Line Voltage and Load Current @ +25°C (VOUT = 1.5V)  
Maximum Current Temperature Derating at Sea Level  
(VIN= 5V, VOUT = 1.5V).  
98  
96  
94  
7
6
5
4
3
2
1
0
Natural convection  
92  
VIN = 2.4V  
90  
VIN = 5V  
VIN = 5.5V  
88  
86  
84  
0
2
4
6
Load Current (Amps)  
20  
25  
30  
35  
40  
45  
50  
55  
60  
65  
70  
75  
80  
85  
90  
Ambient Temperature (ºC)  
Output Ripple and Noise (Vin=5V, Vout=1.5V, Iout=6A, ScopeBW=100MHz)  
On/Off Enable Startup (Vin=5V, Vout=1.5V, Iout=6A, Cload=0)  
Trace 4=Enable, Trace2=Vout  
Step Load Transient Response (Vin=5V, Vout=1.5V, Iout=6A to 3A)  
Trace 2=Vout, 200 mV/div. Trace 4=Iout, 5A/div.  
Step Load Transient Response (Vin=5V, Vout=1.5V, Iout=3A to 6A)  
Trace 2=Vout, 200 mV/div. Trace 4=Iout, 5A/div.  
www.murata-ps.com  
email: sales@murata-ps.com  
13 May 2010 MDC_OKL-T/6-W5 Series.A02 Page 11 of 15  
OKL-T/6-W5 Series  
Programmable Output 6-Amp iLGA SMT PoLs  
PERFORMANCE DATA, OKL-T/6-W5  
Efficiency vs. Line Voltage and Load Current @ +25°C (VOUT = 1.2V)  
Maximum Current Temperature Derating at Sea Level  
(VIN= 5V, VOUT = 1.2V).  
96  
94  
92  
7
6
5
4
3
2
1
0
Natural convection  
90  
VIN = 2.4V  
88  
VIN = 5V  
VIN = 5.5V  
86  
84  
82  
0
2
4
6
Load Current (Amps)  
20  
25  
30  
35  
40  
45  
50  
55  
60  
65  
70  
75  
80  
85  
90  
Ambient Temperature (ºC)  
Output Ripple and Noise (Vin=5V, Vout=1.2V, Iout=6A, ScopeBW=100MHz)  
On/Off Enable Startup (Vin=5V, Vout=1.2V, Iout=6A, Cload=0)  
Trace 4=Enable, Trace2=Vout  
Step Load Transient Response (Vin=5V, Vout=1.2V, Iout=6A to 3A)  
Trace 2=Vout, 200 mV/div. Trace 4=Iout, 5A/div.  
Step Load Transient Response (Vin=5V, Vout=1.2V, Iout=3A to 6A)  
Trace 2=Vout, 200 mV/div. Trace 4=Iout, 5A/div.  
www.murata-ps.com  
email: sales@murata-ps.com  
13 May 2010 MDC_OKL-T/6-W5 Series.A02 Page 12 of 15  
OKL-T/6-W5 Series  
Programmable Output 6-Amp iLGA SMT PoLs  
PERFORMANCE DATA, OKL-T/6-W5  
Efficiency vs. Line Voltage and Load Current @ +25°C (VOUT = 1.0V)  
Maximum Current Temperature Derating at Sea Level  
(VIN= 5V, VOUT = 1.0V).  
7
6
5
4
3
2
1
0
93  
88  
Natural convection  
VIN = 2.4V  
VIN = 5V  
VIN = 5.5V  
83  
78  
0
2
4
6
Load Current (Amps)  
20  
25  
30  
35  
40  
45  
50  
55  
60  
65  
70  
75  
80  
85  
90  
Ambient Temperature (ºC)  
Output Ripple and Noise (Vin=5V, Vout=1.0V, Iout=6A, ScopeBW=100MHz)  
On/Off Enable Startup (Vin=5V, Vout=1.0V, Iout=6A, Cload=0)  
Trace 4=Enable, Trace2=Vout  
Step Load Transient Response (Vin=5V, Vout=1.0V, Iout=6A to 3A)  
Trace 2=Vout, 200 mV/div. Trace 4=Iout, 5A/div.  
Step Load Transient Response (Vin=5V, Vout=1.0V, Iout=3A to 6A)  
Trace 2=Vout, 200 mV/div. Trace 4=Iout, 5A/div.  
www.murata-ps.com  
email: sales@murata-ps.com  
13 May 2010 MDC_OKL-T/6-W5 Series.A02 Page 13 of 15  
OKL-T/6-W5 Series  
Programmable Output 6-Amp iLGA SMT PoLs  
PERFORMANCE DATA, OKL-T/6-W5  
Efficiency vs. Line Voltage and Load Current @ +25°C (VOUT = 0.6V)  
Maximum Current Temperature Derating at Sea Level  
(VIN= 5V, VOUT = 0.6V).  
90  
85  
7
6
5
4
3
2
1
0
Natural convection  
80  
75  
70  
VIN = 2.4V  
VIN = 5V  
VIN = 5.5V  
0
2
4
6
Load Current (Amps)  
20  
25  
30  
35  
40  
45  
50  
55  
60  
65  
70  
75  
80  
85  
90  
Ambient Temperature (ºC)  
Output Ripple and Noise (Vin=5V, Vout=0.6V, Iout=6A, ScopeBW=100MHz)  
On/Off Enable Startup (Vin=5V, Vout=0.6V, Iout=6A, Cload=0)  
Trace 4=Enable, Trace2=Vout  
Step Load Transient Response (Vin=5V, Vout=0.6V, Iout=6A to 3A)  
Trace 2=Vout, 200 mV/div. Trace 4=Iout, 5A/div.  
Step Load Transient Response (Vin=5V, Vout=0.6V, Iout=3A to 6A)  
Trace 2=Vout, 200 mV/div. Trace 4=Iout, 5A/div.  
www.murata-ps.com  
email: sales@murata-ps.com  
13 May 2010 MDC_OKL-T/6-W5 Series.A02 Page 14 of 15  
OKL-T/6-W5 Series  
Programmable Output 6-Amp iLGA SMT PoLs  
TAPE AND REEL INFORMATION  
Tape Detail  
7.40 0.1  
Round  
Sprocket  
Holes  
2.00 0.1  
4.00 0.1  
0.40 0.05  
+0.1  
ø1.50  
-0  
16.00 0.1  
B’  
B
A
Vacuum Pickup  
Point in Center  
A’  
Pulling direction  
12.60 0.1  
(7.0º)  
Notes  
1) The radius (R) is 0.3mm max.  
2) Cumulative tolerance of 10 pitches of the sprocket hole is 0.2mm.  
A-A’ SECTION  
Reel Detail  
Reel diameter 330.2  
Start of  
pocket tape  
A
End of modules  
C
B
Start of  
Start of  
modules  
cover tape  
in pockets  
Reel Information (400 units per reel)  
Hub diameter 13.00  
Inner diameter 101.6  
Key  
A
Description  
Length (mm)  
800 40  
All dimensions are in millimeters.  
Tape trailer (no modules)  
B
Pocket tape length before modules  
Cover tape length before pocket tape  
200 min.  
C
240 40  
www.murata-ps.com  
email: sales@murata-ps.com  
13 May 2010 MDC_OKL-T/6-W5 Series.A02 Page 15 of 15  

相关型号:

OKL-T/6-W5P-C/S

DC-DC Regulated Power Supply Module
MURATA

OKL-T1-W12

Programmable Output 1-Amp iLGA SMT PoLs
MURATA

OKL2-T/12-W12N2-C

DC-DC Regulated Power Supply Module
MURATA

OKL2-T/12-W12P2-C

DC-DC Regulated Power Supply Module
MURATA

OKL2-T/20-W12N2-C

DC-DC Regulated Power Supply Module
MURATA

OKL2-T/20-W12N2-C/S

DC-DC Regulated Power Supply Module, 1 Output, 110W, Hybrid, LGA-10
MURATA

OKL2-T/20-W12P2-C

DC-DC Regulated Power Supply Module
MURATA

OKL2-T/20-W12P2-C/S

DC-DC Regulated Power Supply Module, 1 Output, 110W, Hybrid, LGA-10
MURATA

OKL2-T/20-W5N-C

民用设备,工业设备
MURATA

OKL2-T/20-W5P-C

DC-DC Regulated Power Supply Module
MURATA

OKL2-T/3-W5N-C

Programmable Output 3-Amp iLGA SMT PoLs
MURATA

OKL2-T/3-W5P-C

Programmable Output 3-Amp iLGA SMT PoLs
MURATA