PQU650-28 [MURATA]
AC-DC Regulated Power Supply Module,;型号: | PQU650-28 |
厂家: | muRata |
描述: | AC-DC Regulated Power Supply Module, |
文件: | 总10页 (文件大小:702K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
PQU650 Series
650W 4" x 6" AC-DC “U” Channel Power Supply Converter
DESCRIPTION
The PQU650 Series products are rated at 650W employing a “U” channel construction to operate
with natural convection or forced airflow. The PQU650 series is a 6”x 4” format capable of
providing a continuous 650W1 output, with a constant current overload characteristic, and 800W
“power boost” at output start4 to deliver transient loads.
The compact form factor offers an impressive 450W of natural convection cooled power at +50°C.
Provision of an adjustable Main output, plus Auxiliary/Standby and fan outputs, will enable this
technically superior solution to be deployed across multiple market sectors, complemented by
safety certification applicable to medical/Audio/Video/Communication and ITE standards.
ORDERING GUIDE (MODEL NUMBER)
Main output (V1)
Aux Output (V2)
Current Adc
Fan Output V36
Current Adc
Current Adc
Model (Order) Number
Voltage
Vdc
@ 50°C
650W1
54.2
27.1
23.2
13.6
12.1
27.1
23.2
Vdc
Vdc
@50°C
@50°C
PQU650-122
PQU650-24
PQU650-28
12
24
28
48
54
24
28
48
54
PQU650-483
PQU650-542,3
PQU650-24P2
PQU650-28P2
PQU650-48P2,3
PQU650-54P2,3
PQU-COVER2.5
5
0.5
12
0.6
13.6
12.1
Optional cover kit; End User assembly required.
1 Forced convection airflow required.
2 Consult Murata sales channel for availability.
3 PoE Isolation Compliant.
4 Any condition resulting in the Main V1 output restarting; i.e. recycling of PS_ON or recovery from
OCP/OTP protection.
5 Derating for convection cooling required.
6 Only available for forced air cooled deployments (not available for convection cooled deployments).
FEATURES2
INPUT CHARACTERISTICS
Parameter
Input Voltage AC Operating Range
Input Frequency
Turn-on input voltage
Turn-off input voltage
Conditions
Single Phase
Min
90
47
75
65
Nom
100/240 264
Max
Units
Vac
Hz
Vac
Vac
Compact high density design and thermal performance
operation to:
50/60
30
63
90
80
• 450W convection at +50°C; no derating with input
line voltage
• 650W with forced airflow at +50°C; no derating
with input line voltage
Input rising
Input falling
Vin = 90VAC; Full Load1
(650W FL)
Maximum input current
9.0
Arms
• 800W “power boost” (at output start-up)
Voltage (+15%)3 adjustment of Main V1 Output
+5VAux/Standby and 12V Fan outputs
4" x 6" industry standard footprint; “U” channel form
factor with industry “standard” mounting footprints.
Inrush Current
Power Factor
Hold-up Time
230Vac,Cold start, 25°C
At 230VAC, full load
90Vac; 650W
20% Full Load
50% Full Load
Apk
W/VA
msec
0.95
10
92
95
94
Efficiency @ 230VAC
%
W
•
•
•
40mm maximum overall “U” Channel height
42.7mm max overall height with cover
100% Full Load
(PS_ON = OFF; Aux (V2) = 0A
No Load Input Power Consumption
<0.5
1 Input current will increase to ≈10Arms under 800W peak power
Choice of screwed or pluggable connector variants2
High efficiency of 95% typical at 50% load
Very low no load standby power consumption
True zero load operation of the Main (V1) output; no
minimum load requirements
Remote sense, main output (option)
Universal AC input; active PFC; EN61000-3-2 Class A
MTBF 797Khrs; Telcordia SR332 Issue 3; M1 Case 3;
+40ºC)
MAIN OUTPUT CHARACTERISTICS (ALL MODELS)
Parameter
Conditions
Min
0
Nom
Max
5
Units
%
A
Line, Load Regulation
Minimum Load Capability
Output Ripple
Main (V1) Output1
Stable Operation
Zero to Full Load2
1%
mVPP
1 Zero load output voltage may exceed the regulation window however will not cause OVP to engage or PWOK to change to low state.
2 Ripple and noise are measured with 0.1uF ceramic capacitor and 10uF tantalum capacitor. A short coaxial cable with 50 ohm termination is used.
Min 120uF cap required at the output to keep ripple within 1% for 54V output.
Min 10% load current required, to maintain ripple within 1% for 12V output model. 1A min.
RoHS2 compliant
Active inrush protection
Droop Current Share
IEC60601 Ed.3 medical (2 x MOPP Pri-Sec);
1 x MOPP Pri-Chassis Ground)
AUXILIARY OUTPUT CHARACTERISTICS
Aux Output
Voltage
Line, Load, Cross
Regulation
Ripple Voltage &
Auxiliary
Output
Load Current
Load Capacitance
0 to 220µF
Noise
Aux (V2)
5V
0 to 0.5A
4.75t o 5.25Vdc
100mVPP
IEC62368-1; (migration planned for all PQU650 Series
members)
FAN OUTPUT CHARACTERISTICS (ALL MODELS)
Designed to comply with IEC60601-2 4th Edition EMC
Standard Requirements1
Aux Output
Auxiliary
Line, Load, Cross
Regulation
Ripple Voltage &
Noise
Load Current
0 to 0.6A
Load Capacitance
0 to 220µF
1 When deployed in End User Systems
Voltage
12V
Output1
2 Consult Murata sales channel for availability.
3 54V output adjustment range is +5% max to maintain max voltage to <60V.
Aux (V3)
10.8 to 13.2Vdc
120mVPP
1 Not recommended for “general use” due to its semi regulated characteristic. The output is for use with a fan intended to cool the PQU650; therefore if the
PQU650 is convection cooled only then this output should not be used. A 1.5A non replaceable fuse is provided in this output for overload protection.
2 Only available for forced air cooled deployments (not available for convection cooled deployments)
Report & Certificate
https://www.murata-ps.com/support
PQU650.A02 Page 1 of 10
PQU650 Series
650W 4" x 6" AC-DC “U” Channel Power Supply Converter
MAIN OUTPUT CHARACTERISTICS (ALL MODELS EXCEPT UNLESS NOTED)
Parameter
Conditions
Typ.
Max.
5
500
3
Units
%
µsec
sec
Transient Response1
Settling Time to 1% of Nominal
Turn On Delay
50% load step, 1A/µsec slew rate and min 10% load
After application of input power
Output Voltage Rise
200
msec
Compensates for up to 120mV of total lead drop (output and return connections) with
remote sense connected. Protected against short circuit and reverse connection.
Remote Sense2
1
%
1 Min. 1 second time between consecutive transients; requires 10% minimum load.
2 Remote sense fs not offered as a standard feature due to droop current share characteristic offered on the standard models; consult the sales channel for availability of remote sense option.
ENVIRONMENTAL CHARACTERISTICS
Parameter
Conditions
Min.
-40
-30
10
Typ.
Max.
85
70
95
50002
Units
Storage Temperature Range
°C
Operating Temperature Range4 See power derating curves
Operating Humidity
Operating Altitude
Non-condensing
%
m
-200
Telcordia SR-332 Issue 3; M1C3 @ 25°C
Telcordia SR-332 Issue 3; M1C3 @ 40°C
30G, non-operating
Sine Sweep; 5-150Hz, 2G
Random Vibration, 5-500Hz, 1.11G
1810K
797K
MTBF
Hours
Shock
Complies
Complies
Operational Vibration
IEC 60601-1 (ed.3.1)
Safety – Medical Standards
CAN/CSA-C22.2 No. 60601-1:2008/A1:2014
2 x MOPP (Primary-Secondary) ANSI/AAMI ES 60601-1:2005/A1:2012
EN 60601-1:2006/A1:2013
IEC 60950-1:2005, IEC 60950-1:2005/AMD1:2009, IEC 60950-1:2005/AMD2:2013
CAN/CSA-C22.2 No. 60950-1-07, Amendment 1:2011, Amendment 2:2014 (MOD)
ANSI/UL 60950-1-2014
Safety – ITE,
Audio/Video/Communications & EN 60950-1:2006/A2:2013
Consumer Standards
CCC: GB17625.1-2012; GB4943.1-2011; GB/T9254-2008 (Class A)
CE Marking per LVD
IEC 62368-11
Fuses
Dual Fuses; Line and Neutral; 12.5A Fast Acting; 250V
4.0" x 6.0" x 1.69" (101.6mm x 152.4mm x 42.8mm) nominal
0.692/1.526
Outside Dimensions
Weight (typ.)
kg/lbs.
1 Planned submission end 2019; contact Murata for additional details.
2 Meets 5000 M max. altitude for Medical certification requirements.
3 When deployed in End User Systems
4 Starts at -30°C at 100Vac minimum input; however full specification guaranteed at -20°C; *contact Murata for lower operating temperature range.
PROTECTION CHARACTERISTICS
Parameter
Conditions
Min.
115
5.5
Typ.
Max.
140
Units
%
V1 (main output) latching
Over Voltage Protection
Over Current Protection
V1 (48V *54V models)
latching
V2 (aux output) latching
V3, (Fuse Protected)
60
Vdc
Adc
7.5
1.5A
The Constant Current characteristic as shown in the following curves. This feature will enable the PQU650 to successfully start in to application loads exhibiting large inrush current i.e. large
capacitive loads, incandescent lamps, motors & solenoids.
1. Curves generated for the PQU650 variants by subjecting output to an incremental (constant resistance load, equivalent to 1Adc increments (above full load).
2. The resultant curve shows the current limited to a constant “brick wall” shown by the blue portion of curve.
3. If the load current is further incremented the output will enter “hiccup” (recycling on/off; shown by the red dashed curve) commencing when the output voltage falls to ~75% of the nominal set point.
4. If the overload current is maintained above maximum load for an extended period the “hiccup” operation will continue indefinitely while the overload persists. In the event that the overload is maintained just
below that where “hiccup” operation is initiated then, dependent on the prevailing operating conditions, the power module may enter thermal protection.
5. Each time the output recovers from hiccup the output power will be capable of 800W peak to provide additional power to ensure that the transient load is delivered.
https://www.murata-ps.com/support
PQU650.A02 Page 2 of 10
PQU650 Series
650W 4" x 6" AC-DC “U” Channel Power Supply Converter
PROTECTION CHARACTERISTICS
Parameter
Conditions
V2, auto-recovery
V3; non-resettable fuse1
Min.
110
Typ.
Max.
150
1.5
Units
%
Adc
Over Current Protection
Over Voltage Protection2
Latching
110
140
%Vdc
Over Temperature Protection
Primary Heatsink Temperature
Secondary Temperature
Auto-recovery
130
130
°C
Remote Sense Short Circuit Protection
Remote Sense Reverse Connection Protection
Complies
Complies
--
--
1OCP of the 12V Fan (V3) output is provided by an SMD fuse (accessible from top) rated at 1.5A; therefore if ruptured the 12V Fan output will not be available and the fuse shall require to be replaced.
2Refers to percentage of nominal voltage
ISOLATION CHARACTERISTICS
Parameter
Conditions
Primary to Chassis
Primary to Secondary (2xMOPP)
Secondary to Chassis1
Output to Output
Min.
1500
4000
1500
Typ.
Max.
400
Units
Vac
Isolation
1
1500
Earth Leakage Current (under normal conditions)
264Vac, 60Hz, 25°C
µAac
1 Meets PoE isolation limits
CURRENT SHARING OPTION
Model Number
Description
Main output current share is achieved using the “droop” method. Nominal output voltage is achieved at 50% load; the output voltage increases/decreases (approximately
3% of nominal voltage) with decreasing/increasing (respectively) load current. This regulation window does not include the additional tolerance due to line, temperature,
long term stability etc.
Startup of parallel power supplies is not internally synchronized. No more than 800W combined power is allowed at start-up. To account for 10% full load current sharing
accuracy, and the reduction in full load output voltage due to droop, available output power must be derated by 15% when units are operated in parallel. Current sharing
can be achieved with or without remote sense connected to the common load.
All PQU650
Refer to
ACAN-107
for additional
details
External ORING protection is recommended (see Application notes, ACAN-105 for additional details); Aux (V2) outputs can be tied together for redundancy but total
combined output power must not exceed 2.5W; external ORing devices are recommended to preserve redundancy.
It is not recommended that the 12V Fan (V3) outputs are connected in parallel since these outputs are only semi regulated.
EMISSIONS AND IMMUNITY
Characteristic
Standard
Compliance
Input Current Harmonics
Voltage Fluctuation and Flicker
IEC/EN 61000-3-2
IEC/EN 61000-3-3
CISPR 32/EN 55032
FCC Part 15
CISPR 32/EN 55032
FCC 15.109 - 3 meter
IEC/EN 61000-4-2
IEC/EN 61000-4-3
IEC/EN 61000-4-4
Class A
Complies
Class B
Class B
Class B
Class B
Conducted Emissions
Radiated Emissions
ESD Immunity
Radiated Field Immunity
Electrical Fast Transient Immunity
Level 4, Criterion 2
Level 3, Criterion A
Level 4, Criterion A
Level 3, Criterion A (Com. Mode: 2kV 12 OHM, Diff.
Mode: 1kV, 2ohm)
Level 3, 10V/m, Criterion A
Level 3, Criterion A
Level 3, Criterion B
Surge Immunity
IEC/EN 61000-4-5
Radiated Field Conducted Immunity
Magnetic Field Immunity
Voltage dips, interruptions
IEC/EN 61000-4-6
IEC/EN 61000-4-8
IEC/EN 61000-4-11
EMI CONSIDERATIONS
For optimum EMI performance, the power supply should be mounted to a metal plate grounded to all 4 mounting holes of the power supply. To comply with safety standards, this
plate must be properly grounded to protective earth (see mechanical dimension notes). Pre-compliance testing has shown the stand-alone power supply to comply with EN55032
class B radiated emissions with a metal enclosure with grounded base plate. See PQU-COVER for details - testing was based on adding a toroid (4 turns of both main output wires
wound as common mode choke on FAIR-RITE#5961002701). Radiated emission results vary with system enclosure and cable routing paths.
A minimum 10% load current is required, on the main output.
STATUS AND CONTROL SIGNALS
Conditions
Parameter
Models
This pin can be left unterminated (or alternatively pulled high to +5V_AUX; Connector J3 Pin 1) to (enable) turn on the main output. The +5V_AUX
output is independent of the PS_ON signal, and comes up automatically when the input AC or input DC voltage is applied (within their respective
(Except as noted) specified operating ranges).
PS_ON
Connector
J3 Pin 4
All Models
If it is desired to turn off the Main Output (during normal operation) then this pin can be pulled “low” (sink current >2mA) to +5V_AUX_RTN.
PWOK
Connector
J3 Pin 2
The PWOK is a combined digital signal that signifies the status of the Main V1 output. It changes state due to loss of the incoming AC source and any
condition that causes the Main V1 DC output shutdown (UVP, OCP, OTP protection).
The output is via an open drain CMOS buffer that transitions high 15-25ms after the main output is within regulation; it transitions low at least 1msec
All Models
https://www.murata-ps.com/support
PQU650.A02 Page 3 of 10
PQU650 Series
650W 4" x 6" AC-DC “U” Channel Power Supply Converter
PART NUMBER STRUCTURE
PQU
650
XX
yyy
-
Options
P = Plugs/Receptacles for all input, output and signal
Main Output Voltage
(12, 24, 28, 48. 54)
PQU = Power, Quality, “U” Channel
Output Power (Watts)
Examples: PQU650-24 = Base 24V Model; no options
PQU650-24P = Plug/Receptacles for all input, output and signal connections
PERFORMANCE TYPICAL DATA EXAMPLES (BASED ON 24V VARIANT)
Efficiency 24V Model
Typical Ripple & Noise (24V Model)
Transient Performance, 24V Model Half to Full Load
Transient Performance, 24V Model Full to Half Load
NB: Waveforms as shown includethe effects of 3% droop regulation.
Inrush Current; 264Vac Input, Cold Start, 10.5Apk
Hold Up Time; 90Vac; 650W
https://www.murata-ps.com/support
PQU650.A02 Page 4 of 10
PQU650 Series
650W 4" x 6" AC-DC “U” Channel Power Supply Converter
EMI; Conducted CISPR 22; Peak vs. Average Limit; L1; 100Vac 24Vdc @ 25Adc
EMI; Conducted CISPR 22; Peak vs. Average Limit; L2/Neutral; 100Vac 24Vdc @ 25Adc
PERFORMANCE TYPICAL DATA EXAMPLES
EMI; Conducted CISPR 22; Peak vs. Average Limit; L1; 208Vac 24Vdc @ 25Adc
EMI; Conducted CISPR 22; Peak vs. Average Limit; L2/Neutral; 208Vac 24Vdc @ 25Adc
https://www.murata-ps.com/support
PQU650.A02 Page 5 of 10
PQU650 Series
650W 4" x 6" AC-DC “U” Channel Power Supply Converter
THERMAL CONSIDERATIONS
System thermal management is critical to the performance and reliability of the PQU650 series power supplies. Performance derating curves shall be provided which
can be used as a guideline for what can be achieved (at various operating conditions) in a system configuration with controlled airflow.
The product is designed to provide 450W using natural convection cooling when mounted with un-obstructed convection current airflow flow at up to +50°C local
ambient temperature. At elevated temperatures the power supply data is taken while it is surrounded by a large vented enclosure to minimize forced cross flows
inherent in the elevated temperature test.
The product is capable of operation when mounted in diverse orientations; operational/derating curves shall be provided to show the effect of such mounting. See
ACAN-xx for additonal details
Capacitor Case Temperature and Mounting Orientation:
The power supply can operate in any orientation; however, the power supply contains overtemperature protection that will shut off the output as the temperature of
critical componenets exceed their safe and reliable thermal limits. Additonally, life expectantcy of the power supply is inversely proportional to the case temperature of
electrolytic capacitors. The designer of the system in which this power supply is deployed should consider this relationship to ensure optium product life. The
following charts are initial life predications based on 80% of full load capability that illustrate this relationship.
The PQU650 Series will also benefit from the provision of forced convection cooling airflow (generated by an external host system fan). A dedicated 12V Fan (V3)
output is provided that can be used to power an external (system) fan. This shall enable operation to the full capability of 650W at +50°C local ambient (forced
convection cooling air) temperature .
Please refer to ACAN-106 for additonal details
NB: The above curves are based on generic predicted life ; shall be updated when comprehensive data is available.
THERMAL DERATNG
The PQU650 will reliably provide 450W output power with no derating for AC line at a local ambient temperature of +50°C.
It is also capable of providing 300W at operation up to +70°C.
The PQU650 will provide 650W of power with a minimum recommended airflow of 300LFM/1.5m/s (for the opening area of the “U” channel i.e. 4.0” x 1.55 or
101.6mm x 40mm this equates to circa 13CFM/ 6.14 litre/s).
https://www.murata-ps.com/support
PQU650.A02 Page 6 of 10
PQU650 Series
650W 4" x 6" AC-DC “U” Channel Power Supply Converter
WIRING DIAGRAM FOR OUTPUT CONNECTIONS
Note: For parallel (current share) operation it is required to connect the sharing power supplies in parallel (+DC out connected together and DC out Return connected together on sharing
power supplies. Since each output has an identical “droop” share characteristic then each output will intrinsically share the total load current. See ACAN-xx for more details.
It is recommended that for redundant (critical) applications that external isolation devices (diodes or MOSFETS) are employed.
https://www.murata-ps.com/support
PQU650.A02 Page 7 of 10
PQU650 Series
650W 4" x 6" AC-DC “U” Channel Power Supply Converter
MECHANICAL DIMENSIONS (Nominal)
PQU650-xx MODELS
Input Connector J1
Output Connector J701, J701A
Signal Connector; J3
PCB Connector: Molex 90130-1108 (C-Grid IIITM Series
Mating Half Housing: Molex 0901420008
Crimps Terminals/pins Molex 0901190109
Phoenix Contact Part# 1715734
IHI Connectors; B2A-PCB
Supported Cable Gauge: 26-12AWG; 0.14-2.5mm2
Cable stripped end or with suitable ferrule
Pin 1
Pin 2
Pin3
PE/GND
AC Neutral/L2
AC Line/L1
J701
+DC_OUT
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Pin 6
Pin 7
Pin 8
+5V_AUX
PWR_OK
+12V_FAN_RTN
PS_ON
+Remote Sense
-Remote Sense
+12V_FAN
J701A
+DC_OUT_RTN
+5V_AUX_RTN
https://www.murata-ps.com/support
PQU650.A02 Page 8 of 10
PQU650 Series
650W 4" x 6" AC-DC “U” Channel Power Supply Converter
MECHANICAL DIMENSIONS (Nominal)
PQU650-xxP MODELS
Input Connector J1
Output Connector; J701
Signal Connector; J3
PCB Connector: Molex 90130-1108 (C-Grid IIITM
Series
JST Connectors, B03P-VL (VL Series)
Mating Half: JST Housing VLP-03V
Crimps/Terminals:
JST Connectors; B06P-VL (VL Series)
Mating Half: JST Housing VLP-06V
Crimps/Terminals:
Mating Half Housing: Molex 0901420008
Crimps Terminals/pins Molex 0901190109
Pin 1 +5V_AUX
Pin 2 PWR_OK
Pin 3 +12V_FAN_RTN
Pin 4 PS_ON
Pin 5 +Remote Sense
Pin 6 -Remote Sense
Pin 7 +12V_FAN
SVF-61T-P2.0; 20-14AWG & SVT-81T-P2.0 12AWG
SVF-61T-P2.0; 20-14AWG & SVT-81T-P2.0 12AWG
Pin 1
Pin 2
Pin3
AC Line/L1
AC Neutral/L2
PE/GND
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Pin 6
+DC_OUT_RTN
+DC_OUT
Pin 8 +5V_AUX_RTN
SAFETY CONSIDERATIONS
1. This power supply is a component level power supply intended for use in Class I applications.
2. A protective bonding conductor from the end product protective earthing terminal must be tied to connector J1 (relevant pin dependent on
connector type).
3. The primary heatsink is considered a live primary circuit, and should not be touched. It is recommended that the primary heatsink be kept at
least 4mm from chassis/ground and 8mm from secondary (SELV) circuitry. In all cases, the applicable safety standards must be applied to
ensure proper creepage and clearance requirements are met.
4. This product is subject to the following operating requirements and the Life and Safety Critical Application Sales Policy: http://www.murata-
ps.com/requirements/
5. The power supply has been evaluated for 5000m altitude and tropical climatic conditions for China.
6. Double pole/neutral fusing is used; the product label is annotated accordingly.
7. If the product is used with the PQU650 cover assembly the relevant safety creepage and clearance requirements are preserved when the
PQU650 if so installed.
8. For all deployment installed chassis mounting screws, the End User should ensure that the screw does not protrude by more than two (2)
threads through the captive PEM mounted in the “U” channel.
https://www.murata-ps.com/support
PQU650.A02 Page 9 of 10
PQU650 Series
650W 4" x 6" AC-DC “U” Channel Power Supply Converter
INPUT/OUTPUT CONNECTOR AND SIGNAL SPECIFICATION AND MATING CONNECTORS – PQC650-xx series
Connector
PIN
Description
Technical Data
Manufacturer
1
2
3
Protective Earth (PE)/Ground
AC Neutral/ L2
AC Line/L1)
Input Connector J1
300V, 10A, 3 positions.
Flame Rated: UL94V-0; 5.08mm Pitch
Phoenix Contact Order# 1715734
J701
J701A
+DC_OUT
+DC_OUT_RTN
+5V_AUX
PWR_OK
+12V_FAN_RTN
PS_ON
+Remote Sense
-Remote Sense
+12V_FAN
Output Connectors; J70x
Output Connector J3
600V, 100A, @AWG Wire Lug
IHI Connectors; B2A-PCB
1
2
3
4
5
6
7
8
PCB Connector: Molex 90130-1108 (C-Grid IIITM Series
Mating Half Housing: Molex 0901420008
Crimps Terminals/pins Molex 0901190109
250V, 3A, 8 positions.
Flame RatedUL94V-0; 85°C (minimum)
+5V_AUX_RTN
INPUT/OUTPUT CONNECTOR AND SIGNAL SPECIFICATION AND MATING CONNECTORS – PQC650-xxP
Connector
PIN
1
2
Description
Technical Data
Manufacturer
AC Line/L1
AC Neutral/L2
JST Connectors, B03P-VL (VL Series)
Mating Half: JST Housing VLP-03V
Crimps/Terminals:
Input Connector J1
250V, 7.5A, 3 positions.
Flame Rated: UL94V-0; 5.08mm Pitch
Protective Earth (PE)/Ground
3
SVF-61T-P2.0; 20-14AWG & SVT-81T-P2.0 12AWG
1
2
3
4
5
6
1
2
3
4
5
6
7
8
+DC_OUT_RTN
+DC_OUT
JST Connectors; B06P-VL (VL Series)
Mating Half: JST Housing VLP-06V
Crimps/Terminals:
600V, 15A, Flame Rated at 94V-0;
90°C temperature rated
Output Connectors; J701
Output Connector J3
SVF-61T-P2.0; 20-14AWG & SVT-81T-P2.0 12AWG
+5V_AUX
PWR_OK
+12V_FAN_RTN
PS_ON
+Remote Sense
-Remote Sense
+12V_FAN
PCB Connector: Molex 90130-1108 (C-Grid IIITM Series
Mating Half Housing: Molex 0901420008
Crimps Terminals/pins Molex 0901190109
250V, 3A, 8 positions.
Flame RatedUL94V-0; 85°C (minimum)
+5V_AUX_RTN
APPLICATION NOTES
Document Number
ACAN-105
Description
Link to Document
PQU650 External ORING deployment notes
PQU650 Installation/Thermal deployment notes
PQU650 Current Sharing deployment notes
Cover Kit datasheet
http://power.murata.com/datasheet?/data/apnotes/acan-105.pdf
http://power.murata.com/datasheet?/data/apnotes/acan-106.pdf
http://power.murata.com/datasheet?/data/apnotes/acan-107.pdf
https://power.murata.com/data/acdcsupplies/pqu650-cover.pdf
ACAN-106
ACAN-107
PQU-COVER
This product is subject to the following operating requirements and the Life and Safety Critical
Application Sales Policy. Refer to: http://www.murata-ps.com/requirements/
Murata Power Solutions, Inc. (“Murata”) makes no representation that the use of its products in the circuits described herein, or the use of other technical information contained herein, will
not infringe upon existing or future patent rights. The descriptions contained herein do not imply the granting of licenses to make, use, or sell equipment constructed in accordance therewith.
Buyer represents and agrees that it has all the necessary expertise to create and implement safeguards that anticipate dangerous consequences of failures, monitor failures and their
consequences lessen the likelihood of failures that might cause harm, and take appropriate remedial actions. Buyer will fully indemnify Murata, its affiliated companies, and its
representatives against any damages arising out of the use of any Murata products in safety-critical applications. Specifications are subject to change without notice.
© 2019 Murata Power Solutions, Inc.
Murata Power Solutions, Inc.
129 Flanders Road
Westborough, MA 01581
ISO 9001 and 14001 REGISTERED
https://www.murata-ps.com/support
PQU650.A02 Page 10 of 10
相关型号:
SI9130DB
5- and 3.3-V Step-Down Synchronous ConvertersWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1-E3
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135_11
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9136_11
Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130CG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130LG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130_11
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137DB
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137LG
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9122E
500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification DriversWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
©2020 ICPDF网 联系我们和版权申明