NIPCI-6528 [NI]

24 or 48 channel-to-channel optically isolated inputs and solid-state relay outputs; 24或48通道至通道光隔离输入和固态继电器输出
NIPCI-6528
型号: NIPCI-6528
厂家: National Instruments    National Instruments
描述:

24 or 48 channel-to-channel optically isolated inputs and solid-state relay outputs
24或48通道至通道光隔离输入和固态继电器输出

继电器 固态继电器
文件: 总5页 (文件大小:663K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Industrial Digital Input/Output –  
60 V, Channel-to-Channel Isolated  
NI 6528, NI PXI-6529 NEW!  
• 24 or 48 channel-to-channel optically  
isolated inputs and solid-state relay outputs  
• High-reliability industrial feature set –  
isolation, programmable power-up states,  
digital I/O watchdogs, change detection,  
and programmable input filters  
Operating Systems  
• Windows Vista/XP/2000  
• LabVIEW Real-Time  
Recommended Software  
• LabVIEW  
• LabWindows/CVI  
• High-voltage input to PXI trigger bus  
or RTSI bus  
• Measurement Studio  
• Superior features for automotive,  
aerospace, industrial monitoring, and  
control applications  
• NI-DAQmx driver software for highest  
productivity and performance  
Other Compatible Software  
• LabVIEW SignalExpress  
• Visual Studio .NET  
• C/C++/C#  
Measurement Services  
Software (included)  
• NI-DAQmx driver software  
• Measurement & Automation  
Explorer configuration utility  
• LabVIEW SignalExpress LE  
data-logging software  
Family  
NI 6528  
NI 6529  
Bus  
PCI, PXI  
PXI  
Input Lines  
Output Lines  
Isolation  
Channel-to-channel  
Channel-to-channel  
Max Range  
60 VDC  
60 VDC  
Low Threshold High Threshold Output Current  
Industrial Feature Set  
24  
48  
24  
1 VDC  
1 VDC  
3.2 VDC  
3.2 VDC  
150 mA  
Table 1. NI 6528 and PXI-6529 Specifications Overview  
Overview and Applications  
Hardware  
National Instruments 6528 and PXI-6529 devices are industrial  
channel-to-channel isolated digital I/O interfaces for PCI and  
PXI. You can use the optically isolated inputs of NI 6528 and  
PXI-6529 devices to read the status of sensors, actuators, and logic  
devices. NI 6528 devices have 24 solid-state relay outputs to switch  
external devices with input currents up to 150 mA. With high current  
drive and isolation, NI 6528 and PXI-6529 devices are ideal for a variety  
of applications from automotive design, industrial factory automation,  
and machine control to aerospace, laboratory research, and biomedical  
applications. Industrial digital I/O devices are designed to incorporate  
the latest hardware technologies for applications requiring ease of use,  
high reliability, and performance. NI 6528 and PXI-6529 devices are  
jumper-free and take advantage of NI-DAQmx measurement services  
software to speed up application development with features such as  
DAQ Assistant, automatic code generation, and high-performance  
multithreaded streaming technology.  
Industrial Feature Set  
NI industrial digital I/O devices provide a set of high-reliability features  
designed to automate even the most demanding applications.  
• Isolation offers an extended voltage range for direct connection  
to industrial sensors and actuators  
• Programmable power-up states provide safe operation  
when connected to pumps/valves/motors/relays  
• Digital I/O watchdog timers detect computer or application crashes  
and ensure safe recovery  
• Change detection triggers your application and performs a read  
operation after a digital event with minimal processor usage  
• Programmable input filters eliminate glitches/spikes and remove noise  
• Industrial certifications from CE, FCC, C-Tick, UL, and VDE ensure EMI  
compliance in most regions of the world and certify that the system  
is safe to operate  
Industrial Digital Input/Output – 60 V, Channel-to-Channel Isolated  
digital lines. Using change detection, you can monitor for digital  
Connect Sensors Directly with Isolation  
events with minimal processor usage. No polling is necessary because  
the digital I/O module generates an interrupt to automatically wake  
up your application.  
Isolation is a form of built-in signal conditioning that provides an  
extended voltage range for direct connection to industrial sensors and  
actuators. NI 6528 and PXI-6529 devices provide channel-to-channel  
isolation where every channel is physically and electrically separated  
from the others and earth ground. Optical isolators separate the high-  
voltage front end from the low-voltage back end, breaking ground  
loops, improving common-mode voltage rejection, and protecting  
computer circuitry from hazardous voltages. Industrial environments  
containing machinery and inductive loads require isolation to protect  
the electronics from transient voltage spikes and provide greater  
common-mode noise rejection.  
Using NI-DAQmx software technology, NI 6528 and PXI-6529 devices  
notify the software application when an event is detected, causing the  
application to automatically perform a read operation. To minimize  
the effects of noisy input lines, use programmable input filters in  
combination with change detection to eliminate spurious change-  
detection events caused by noise or glitches.  
Eliminate Noise with Programmable  
Input Filters  
Programmable input filters remove noise, glitches, and spikes on  
inputs as well as provide debouncing for digital switches and relays.  
These features are important for applications in industrial environments  
to prevent false readings caused by noise. You can configure the  
programmable input filter for each digital line by setting the filter time.  
NI 6528 and PXI-6529 devices block any digital noise, glitch, or spike  
that is shorter than half of the specified filter time, preventing invalid  
readings and false triggers for change-detection events.  
Achieve Glitch-Free Startup with  
Programmable Power-Up States  
Using programmable power-up states, you can configure the initial  
NI 6528 output states in software to ensure glitch-free operation  
when connected to industrial actuators such as pumps, valves, motors,  
and relays. An NI 6528 holds these output states after receiving power,  
so your computer can boot and your software application can begin  
running. Programmable power-up states are glitch-free, meaning the  
outputs never go through an incorrect state during power up.  
You can configure each individual digital line as high-output or  
low-output. An NI 6528 stores the settings in onboard nonvolatile  
memory and implements the power-up states instantaneously after  
power is applied to the device.  
Use High-Voltage Triggering  
With NI 6528 and PXI-6529 devices, you can route isolated high-voltage  
( 60 VDC) signals to the PXI trigger bus or RTSI (Real-Time System  
Integration) bus, so you can synchronize between multiple high-voltage  
devices without additional circuitry. This feature benefits automotive,  
aerospace, and industrial monitoring and control applications needing  
high-voltage triggers.  
Detect Faults and Recover with Digital  
I/O Watchdogs  
Digital I/O watchdog timers are an innovative technology that can  
detect a variety of fault conditions, such as an application crash, and  
automatically respond by setting the outputs to a user-configured safe  
state. Watchdogs are important whenever the module is connected to  
actuators such as pumps, valves, motors, and relays. An NI 6528  
monitors the software application; if the application fails to respond  
within a preset time limit, an NI 6528 automatically sets the output  
lines to a user-defined safe state. An NI 6528 remains in the watchdog  
state until the watchdog timer is disarmed, an NI 6528 is reset, or the  
computer is restarted.  
Recommended Software  
National Instruments measurement services software, built around  
NI-DAQmx driver software, includes intuitive application programming  
interfaces, configuration tools, I/O assistants, and other tools designed  
to reduce system setup, configuration, and development time. National  
Instruments recommends using the latest version of NI-DAQmx driver  
software for application development in National Instruments LabVIEW,  
LabWindows/CVI, and Measurement Studio. To obtain the latest version  
of NI-DAQmx, visit ni.com/support/daq/versions. NI measurement  
services software speeds up your development with features including:  
• A guide to create fast and accurate measurements with no  
programming using the DAQ Assistant  
Trigger Your Application with  
Change Detection  
• Free LabVIEW SignalExpress LE data-logging software  
With change detection, you can automatically trigger your software  
application to perform a digital read operation upon a digital change  
of state. A digital change of state is defined as the rising edge  
(0 to 1 transition) or falling edge (1 to 0 transition) on one or more  
• Automatic code generation to create your application in NI LabVIEW,  
LabWindows/CVI, and LabVIEW SignalExpress as well as Microsoft Visual  
Studio .NET, C/C++/C#, or Visual Basic using NI Measurement Studio  
BUY ONLINE at ni.com or CALL 800 813 3693 (U.S.)  
2
Industrial Digital Input/Output – 60 V, Channel-to-Channel Isolated  
• Multithreaded technology for 1,000 times performance improvements  
• Automatic timing, triggering, and synchronization routing to make  
advanced applications easy  
R1005050 – Unshielded ribbon cable that terminates with two  
50-pin IDC connectors.  
0.5 m cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .182762-0R5  
1 m cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .182762-01  
2 m cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .182762-02  
• More than 3,000 free software downloads to jump-start your project  
available at ni.com/zone  
• Software configuration of all digital I/O features without hardware  
switches/jumpers  
SCB-100 – Shielded I/O connector block with screw terminals and  
a general breadboard area for 100-pin digital I/O devices.  
NI 6528 and PXI-6529 devices are compatible with the following  
versions (or later) of NI application software: LabVIEW, LabWindows/CVI,  
or Measurement Studio versions 7.x; LabVIEW SignalExpress 1.x; or  
LabVIEW with the LabVIEW Real-Time Module 7.1. NI 6528 and PXI-6529  
devices are not compatible with the Traditional NI-DAQ (Legacy) driver.  
SCB-100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .776990-01  
CB-50 – Unshielded I/O connector block with DIN-rail mounting and screw  
terminals. Includes 50-pin header for direct connection to 50-pin cables.  
CB-50 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .776164-90  
Digital I/O Cables and Accessories  
The 100-pin high-density SCSI connector on NI 6528 and PXI-6529  
devices interfaces to 100-pin ribbon cables or shielded cables. For  
low-cost unshielded connectivity, use the R1005050 ribbon cable with  
two CB-50LP or CB-50 connector blocks (a CB-100 kit). For shielded  
connectivity, use the SH100-100-F shielded digital I/O cable with the  
SCB-100 connector block.  
CB-50LP – Unshielded termination board with 50 screw terminals.  
Includes a 50-pin header for direct connection to 50-pin cables.  
CB-50LP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .777101-01  
CB-100 Connector Kit – Includes two CB-50 I/O connector blocks and  
a 1 m R1005050 ribbon cable.  
CB-100 with 1 m R1005050 cable . . . . . . . . . . . . . . . . . . . .777812-01  
SH100-100-F – Shielded 100-conductor cable that terminates with a  
100-pin 0.050 series D-type connector that attaches to 100-pin accessories. PCB Mounting Connectors – PCB connectors for use in building custom  
1 m cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .185095-01  
2 m cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .185095-02  
accessories that connect to 100-conductor shielded and ribbon cables.  
100-pin, female, right-angle mounting . . . . . . . . . . . . . . . .777778-01  
100-pin, female, vertical mounting . . . . . . . . . . . . . . . . . . .777779-01  
SH100-100-F  
CB-50LP  
CB-50  
R1005050  
SCB-100  
Ordering Information  
NI PCI-6528 .......................................................................... 778833-01  
NI PXI-6528 .......................................................................... 778543-01  
NI PXI-6529 .......................................................................... 779949-01  
BUY NOW!  
For complete product specifications, pricing, and accessory  
information, call 800 813 3693 (U.S.) or go to ni.com/dataacquisition.  
CB-100  
PCB Mounting Connectors  
BUY ONLINE at ni.com or CALL 800 813 3693 (U.S.)  
3
Industrial Digital Input/Output – 60 V, Channel-to-Channel Isolated  
Operating Environment  
Specifications  
Ambient temperature ......................... 0 to 55 °C  
Relative humidity ................................ 10 to 90ꢀ, noncondensing  
Altitude .............................................. 2,000 m at 25 °C ambient  
temperature  
These specifications are typical at 25 °C, unless otherwise noted.  
Digital Inputs  
NI 6528................................................ 24, ch-ch isolated  
NI PXI-6529 ......................................... 48, ch-ch isolated  
I/O connector ...................................... 100-pin keyed female  
SCSI connector  
Input voltage range............................. -60 to 60 VDC  
Digital logic levels  
(tested in accordance with IEC-60068-2-1, IEC-60068-2-2, and IEC-60068-2-56)  
Storage Environment  
Ambient temperature ......................... -20 to 70 °C  
Relative humidity ............................... 5ꢀ to 95ꢀ, noncondensing  
(tested in accordance with IEC-60068-2-1, IEC-60068-2-2, and IEC-60068-2-56)  
Level  
Input low voltage  
Input high voltage  
Min  
-60 VDC  
3.2 VDC  
Max  
1 VDC  
60 VDC  
Shock and Vibration (PXI-6528 and PXI-6529 only)  
Operational shock .............................. 30 g peak, half-sine,  
11 ms pulse  
Input current  
(tested in accordance with IEC-60068-2-27; test profile developed in accordance with  
MIL-PRF-28800F)  
5 V inputs........................................ 1.5 mA/channel max  
60 V inputs...................................... 3 mA/channel max  
Isolation............................................... 60 VDC channel-to-channel and  
channel-to-earth  
Random vibration  
Operating ....................................... 5 to 500 Hz, 0.3 grms  
Nonoperating ................................. 5 to 500 Hz, 2.4 grms  
(tested in accordance with IEC-60068-2-64; nonoperating test profile developed in accordance  
with MIL-PRF-28800F, Class 3)  
Digital Output (NI 6528 Only)  
Number of channels............................ 24, ch-ch isolated  
Relay type ........................................... Normally open form A  
solid-state relays  
Safety  
NI 6528 and PXI-6529 devices are designed to meet the requirements  
of the following standards of safety for electrical equipment for  
measurement, control, and laboratory use:  
• IEC 61010-1, EN 61010-1  
Max Switching Voltage  
AC ................................................... 30 Vrms (42 V peak)  
DC ................................................... 60 VDC  
Max switching capacity...................... 150 mA  
Common-mode isolation..................... 60 VDC  
30 Vrms (42 V peak)  
• UL 61010-1, CSA 61010-1  
For UL and other safety certifications, refer to the product label, or visit  
ni.com/certification, search by model number or product line, and click  
the appropriate link in the Certification column.  
(ch-ch and ch-earth)  
On-resistance...................................... 18 , max  
Output capacitance............................. 50 pF at 50 V  
Off-leakage current (max)................... 1 µA  
Relay set time (max) ........................... 5.0 ms  
Relay reset time (max)........................ 5.0 ms  
Default power-on state....................... Relays open  
Electromagnetic Compatibility  
• EN 55011 Emissions; Group 1, Class A  
• EN 61326 EMC requirements; Minimum Immunity  
• CE, C-Tick, ICES, and FCC Part 15 Emissions; Class A Compliant  
For EMC compliance, operate this device according to product documentation.  
Power Requirements  
+5 VDC ( 5ꢀ)...................................... 300 mA, typical (excluding the  
CE Compliance  
This product meets the essential requirements of applicable  
European Directives, as amended for CE marking, as follows:  
• 73/23/EEC; Low-Voltage Directive (safety)  
power consumed through the  
I/O connector)  
+3.3 VDC ( 5ꢀ)................................... 600 mA, typical  
Power available at I/O connector....... +4.5 to +5.25 VDC, fused at 1 A  
• 89/336/EEC; Electromagnetic Compatibility Directive (EMC)  
Refer to the Declaration of Conformity (DoC) for this product for any  
additional regulatory compliance information. To obtain the DoC for this  
product, visit ni.com/certification, search by model number or product  
line, and click the appropriate link in the Certification column.  
Physical  
Dimensions  
PCI-6528 (w/o connectors) ............. 17.5 by 10.7 cm (6.9 by 4.2 in.)  
PXI-6528 (w/o connectors) ............. 16 by 10 cm (6.3 by 3.9 in.)  
PXI-6529 (w/o connectors) ............. 16 by 10 cm (6.3 by 3.9 in.)  
Environment  
NI 6528 and PXI-6529 devices are intended for indoor use only.  
BUY ONLINE at ni.com or CALL 800 813 3693 (U.S.)  
4
NI Services and Support  
NI has the services and support to meet  
Local Sales and Technical Support  
your needs around the globe and through  
the application life cycle – from planning  
and development through deployment  
and ongoing maintenance. We offer  
services and service levels to meet  
customer requirements in research,  
design, validation, and manufacturing.  
Visit ni.com/services.  
In offices worldwide, our staff is local to the country, giving you access  
to engineers who speak your language. NI delivers industry-leading  
technical support through online knowledge bases, our applications  
engineers, and access to 14,000 measurement and automation  
professionals within NI Developer Exchange forums. Find immediate  
answers to your questions at ni.com/support.  
We also offer service programs that provide automatic upgrades to  
your application development environment and higher levels of technical  
support. Visit ni.com/ssp.  
Training and Certification  
NI training is the fastest, most certain route to productivity with our  
products. NI training can shorten your learning curve, save development  
time, and reduce maintenance costs over the application life cycle. We  
schedule instructor-led courses in cities worldwide, or we can hold a  
course at your facility. We also offer a professional certification program  
that identifies individuals who have high levels of skill and knowledge on  
using NI products. Visit ni.com/training.  
Hardware Services  
NI Factory Installation Services  
NI Factory Installation Services (FIS) is the fastest and easiest way to  
use your PXI or PXI/SCXI combination systems right out of the box.  
Trained NI technicians install the software and hardware and configure  
the system to your specifications. NI extends the standard warranty by  
one year on hardware components (controllers, chassis, modules)  
purchased with FIS. To use FIS, simply configure your system online  
with ni.com/pxiadvisor.  
Professional Services  
Our NI Professional Services team is composed of NI applications  
and systems engineers and a worldwide National Instruments Alliance  
Partner program of more than 600 independent consultants and  
integrators. Services range  
Calibration Services  
NI recognizes the need to maintain properly calibrated devices for  
high-accuracy measurements. We provide manual calibration  
procedures, services to recalibrate your products, and automated  
calibration software specifically designed for use by metrology  
laboratories. Visit ni.com/calibration.  
from start-up assistance to  
turnkey system integration.  
Visit ni.com/alliance.  
OEM Support  
Repair and Extended Warranty  
We offer design-in consulting and product integration assistance if you  
want to use our products for OEM applications. For information about  
special pricing and services for OEM customers, visit ni.com/oem.  
NI provides complete repair services for our products. Express repair  
and advance replacement services are also available. We offer  
extended warranties to help you meet project life-cycle requirements.  
Visit ni.com/services.  
ni.com • 800 813 3693  
*351500A-01*  
351500A-01  
2007-8837-301-101-D  
National Instruments • info@ni.com  
© 2007 National Instruments Corporation. All rights reserved. CVI, LabVIEW, Measurement Studio, National Instruments, National Instruments Alliance Partner, NI, ni.com, RTSI, SCXI,  
and SignalExpress are trademarks of National Instruments. The mark LabWindows is used under a license from Microsoft Corporation. Other product and company names listed are  
trademarks or trade names of their respective companies. A National Instruments Alliance Partner is a business entity independent from NI and has no agency, partnership, or joint-ven-  
ture relationship with NI.  

相关型号:

NIPCI-6534

High-Speed 32-bit Digital Pattern I/O and Handshaking
NI

NIPCI-6541

100 and 50 MHz Digital Waveform Generator/Analyzers
NI

NIPCI-6542

100 MHz Logic Analyzer/Digital Pattern Generators
NI

NIPCI-6551

100 and 50 MHz, Programmable-Voltage Digital Waveform Generator/Analyzers
NI

NIPCI-6552

100 MHz Logic Analyzer/Digital Pattern Generators
NI

NIPCI-6561

400 and 200 Mb/s LVDS Digital Waveform Generator/Analyzers
NI

NIPCI-6562

400 and 200 Mb/s LVDS Digital Waveform Generator/Analyzers
NI

NIPCI-6601

32-Bit Counter/Timers
NI

NIPCI-6602

32-Bit Counter/Timers
NI

NIPCI-6624

Industrial, Channel-Channel Isolated,32-Bit Counter/Timers
NI

NIPCI-6703

Software-Timed Analog Output-16-Bit, 16 or 32 Channels
NI

NIPCI-6704

Software-Timed Analog Output-16-Bit, 16 or 32 Channels
NI