NGHS11-2.5K60-115D-120 [NOVA]
TRUE ON-LINE UPS;型号: | NGHS11-2.5K60-115D-120 |
厂家: | Nova Electric |
描述: | TRUE ON-LINE UPS |
文件: | 总2页 (文件大小:1451K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
RUGGED
RUGGED
ADVANCED FEATUURES
TM
TM
NAVY GALAXY SERIES
Automatic DC offset
Totally Modular Design
Two Stage Battery Charger
Input Inrush Current Control
TRUE ON-LINE UPS
POWER FACTOR CORRECTED
D
&
GALVANICALLY ISOLATED
VA
1.5KVA & 2.5K
BULKHEAD MOUNT
OPTIONAL FEATURES SHOWN
APPL
This rugged UPS is specifically designed
for submarine and shipboard applications
in compliance to MIL-STD-1399, MIL-STD-461,
MIL-S-901, MIL-STD-167, MIL-STD-810,
and MIL-STD-740. It provides very high quality
pure sinewave output (2% THD) and is capable
of driving non-linear loads such as non-PFC
Switching Power Supplies.
NOVAA EELLEECCTTRRIICC
www.novaelectric.com
novasales@theallpower.com
A Leader in UPS Technology since 1966 - 500VA to 500+KVA
ADVANCED TRUE ONLINE RUGGED SINEWAVE UPS
BULKHEAD MOUNT
Designed to comply with MIL-STD-1399, MIL-STD-461, MIL-STD-167, MIL-STD-810, MIL-S-901 and MIL-STD-740.
SPECIFICATIONS
APPLICATIONS
ENVIRONMENTAL
ELECTRICAL
Optional Input Voltages available (select):
115, 120, 208, 220, 230, 240 VAC. 1Ø
115/200, 120/208, 220/380 3Ø
Optional Input Frequencies available (specify):
50, 60 or 400 Hz
Optional Output Voltages Available (specify):
115, 120, 208, 220, 230, 240 VAC 1Ø
Output Frequency (specify): 50, 60 or 400Hz
Voltage Regulation: ± 2% NL to FL
Frequency Regulation: 0.1%
Operating Temp: -20° to +50°C per MIL-
STD-810
This Power Factor Corrected Shipboard /
Submarine Grade UPS is specifically
designed and tested for Naval
Applications where MIL-STD-1399
power requirements apply. This unit
contains many advanced features,
yielding superior performance and
reliability.
Storage Temp Range: -40° to +60°C
Humidity: to 95% non-condensing
Elevation: 15,000 Ft. (4,572m) operating
40,000Ft(12,192m) non-operating
Audible Noise: Less than 55 dbA at 5 ft.
Cooling: Forced air
EMI: per MIL-STD-461
Vibration: per MIL-STD-167
Shock: 20g for 20mS half sinewave per
MIL-S-901D Grade A
Structureborne noise: MIL-STD-740B Grade A
MTBF: 100,000+ hours per field data
MTTR: 30 minutes
Harmonic Distortion: 2% THD Typical
5% Max
Input Power Factor: 0.99
Efficiency at full load: 82% typical
Overload: 125% for 5 minutes
OPTIONS
Single Phase Input
RS 232 or SNMP Interface
MS Connector Mates
High Speed Mechanical Transfer Switch
Wide temperature range
Shock mounts
INTERNAL BATTERIES
Premium wide temp batteries which
are sealed, maintenance- free, and
user replaceable. Extended runtime
available
ALARMS & DIAGNOSTICS
System Status (Green/Red)
Manual bypass switch
Utility Off (Red)
UPS Off (Red)
UPS Overload (Red)
Over Temp. (Red)
External bypass switch
Custom Paint & Markings
PROTECTIVE FEATURES
Low Battery (Red)
Logic Fault (Red)
Load On Utility (Red)
(with XFR SW Option)
AC & DC Input Circuit Breakers, Low
Battery Shut Off, Overload & Thermal
Protection, Audible Alarm with
DIMENSIONS
Alarm Contacts: Standard
RS 232 or SNMP: Optional
30” H x 24” W x 12” D
including internal batteries
Silence Switch, and optional EPO.
MODEL SELECTION
INPUT
PARTIAL MODEL SELECTION
NGHS11-1.5K60-115-120
KVA
1.5
1.5
2.5
2.5
OUTPUT
UPS LBS
145
RUN TIME
10 min
115 VAC
120 VAC
120 VAC
120 VAC
120 VAC
NGHS11-1.5K60-115(D)-120
NGHRS11-2.5K60-115-120
NGHS11-2.5K60-115(D)-120
115 VAC L-L
115 VAC
145
155
155
10 min
10 min
10 min
115 VAC L-L
TYPICAL OUTLINE DRAWING
NOVA ELECTRIC
WEB : www.novaelectric.com
A Division of
ISO 9001
TECHNOLOGY DYNAMICS, INC.
100 School St., Bergenfield NJ 07621
E-Mail : novasales@theallpower.com
PHONE : (201) 385-0500 FAX : (201) 385-0702
相关型号: