D4NL-1GFA-B4 [OMRON]

Best-selling Guard Lock Safety-door Switch Available in Several Compact, Multi-contact Models; 最畅销的防护锁安全门开关有多种结构紧凑,多接触模型
D4NL-1GFA-B4
型号: D4NL-1GFA-B4
厂家: OMRON ELECTRONICS LLC    OMRON ELECTRONICS LLC
描述:

Best-selling Guard Lock Safety-door Switch Available in Several Compact, Multi-contact Models
最畅销的防护锁安全门开关有多种结构紧凑,多接触模型

开关
文件: 总19页 (文件大小:3612K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
DGua4rd NLocLk Safety-door Switch  
CSM_D4NL_DS_E_3_2  
Best-selling Guard Lock Safety-door  
Switch Available in Several  
Compact, Multi-contact Models  
• Selectable Operation Key insertion direction and  
adjustable mounting ensure installation flexibility.  
• Built-in switches with multiple-contact construction are  
available.  
• Key holding force of 1,300 N minimum.  
• Can be used for either standard loads or microloads.  
• Lineup includes models with a conduit size of M20.  
• IP67 degree of protection.  
• Variety of Metallic Heads Available.  
Be sure to read the “Safety Precautions” on page 16 and the  
“Precautions for All Safety Door Switches”.  
Model Number Structure  
Model Number Legend  
Switch (Standard type)  
Switch (Metallic release key type)  
D4NL-@@@@-@@@-SJ  
D4NL-@@@@-@@@  
1 2 3 4 5 6  
7
1 2 3 4 5 6  
7
1. Conduit Size  
1. Conduit Size  
1: Pg13.5  
2: G1/2  
4: M20  
2: G1/2 (1-conduit)  
4: M20 (1-conduit)  
2. Built-in Switch  
E: 2NC/1NO  
F: 2NC/1NO  
+
+
1NC/1NO  
2NC  
2. Built-in Switch (with Door Open/Closed Detection Switch and  
Lock Monitor Switch Contacts)  
A: 1NC/1NO (slow-action contacts) + 1NC/1NO (slow-action contacts)  
B: 1NC/1NO (slow-action contacts) + 2NC (slow-action contacts)  
C: 2NC (slow-action contacts) + 1NC/1NO (slow-action contacts)  
D: 2NC (slow-action contacts) + 2NC (slow-action contacts)  
E: 2NC/1NO (slow-action contacts) + 1NC/1NO (slow-action contacts)  
F: 2NC/1NO (slow-action contacts) + 2NC (slow-action contacts)  
G: 3NC (slow-action contacts) + 1NC/1NO (slow-action contacts)  
H: 3NC (slow-action contacts) + 2NC (slow-action contacts)  
3. Head Mounting Direction and Material  
F: Four mounting directions possible (Front-side mounting at  
shipping)/plastic  
G: 3NC  
H: 3NC  
+
+
1NC/1NO  
2NC  
3. Head Material  
F: resin  
4. Door Lock and Release  
A: Mechanical lock/ 24 VDC solenoid release  
G: 24 VDC solenoid lock/ mechanical release  
5. Indicator  
B: 10 to 115 VAC/VDC (orange LED indicator)  
6. Release Key Type  
Blank: Standard (metal)  
7. Release Key Position  
Blank: Bottom  
D: Four mounting directions possible (Front-side mounting at  
shipping)/metal  
4. Door Lock and Release  
Operation Key  
A: Mechanical lock/24 VDC solenoid release  
B: Mechanical lock/110 VAC solenoid release  
G: 24 VDC solenoid lock/mechanical release  
H: 110 VAC solenoid lock/mechanical release  
5. Indicator  
\
D4DS-K@  
1
1. Operation Key Type  
1: Horizontal mounting  
2: Vertical mounting  
3: Adjustable mounting (horizontal)  
5: Adjustable mounting (horizontal/vertical)  
B: 10 to 115 VAC/VDC (orange LED indicator)  
6. Release Key Type  
Blank: Standard (resin)  
4:  
Special release key (resin)  
(Note: Release keys are provided.)  
7. Release Key Position  
Blank: Bottom  
S:  
Front  
1
D4NL  
Ordering Information  
List of Models  
Switches (Operation Keys are sold separately.)  
: Models with certified direct opening contacts.  
Consult with your OMRON representative when ordering any models that are not listed in this table.  
Contact configuration  
(door open/closed  
detection switch and lock  
monitor switch contacts)  
(slow-action)  
Release  
key  
position  
Head  
material  
Release  
key type  
Solenoid voltage/  
indicator  
Lock and release  
types  
Conduit opening  
Model  
Certified direct opening  
NC contact  
Pg13.5  
G1/2  
D4NL-1AFA-B  
D4NL-2AFA-B  
D4NL-4AFA-B  
D4NL-1BFA-B  
D4NL-2BFA-B  
D4NL-4BFA-B  
D4NL-1CFA-B  
D4NL-2CFA-B  
D4NL-4CFA-B  
D4NL-1DFA-B  
D4NL-2DFA-B  
D4NL-4DFA-B  
D4NL-1EFA-B  
D4NL-2EFA-B  
D4NL-4EFA-B  
D4NL-1FFA-B  
D4NL-2FFA-B  
D4NL-4FFA-B  
D4NL-1GFA-B  
D4NL-2GFA-B  
D4NL-4GFA-B  
D4NL-1HFA-B  
D4NL-2HFA-B  
D4NL-4HFA-B  
D4NL-1AFG-B  
D4NL-2AFG-B  
D4NL-4AFG-B  
D4NL-1BFG-B  
D4NL-2BFG-B  
D4NL-4BFG-B  
D4NL-1CFG-B  
D4NL-2CFG-B  
D4NL-4CFG-B  
D4NL-1DFG-B  
D4NL-2DFG-B  
D4NL-4DFG-B  
D4NL-1EFG-B  
D4NL-2EFG-B  
D4NL-4EFG-B  
D4NL-1FFG-B  
D4NL-2FFG-B  
D4NL-4FFG-B  
D4NL-1GFG-B  
D4NL-2GFG-B  
D4NL-4GFG-B  
D4NL-1HFG-B  
D4NL-2HFG-B  
D4NL-4HFG-B  
1NC/1NO+1NC/1NO  
1NC/1NO+2NC  
2NC+1NC/1NO  
2NC+2NC  
M20  
Pg13.5  
G1/2  
M20  
Pg13.5  
G1/2  
M20  
Pg13.5  
G1/2  
M20  
Mechanical lock  
Solenoid release  
Pg13.5  
G1/2  
2NC/1NO+1NC/1NO  
2NC/1NO+2NC  
3NC+1NC/1NO  
3NC+2NC  
M20  
Pg13.5  
G1/2  
M20  
Pg13.5  
G1/2  
M20  
Pg13.5  
G1/2  
Solenoid: 24 VDC  
Orange LED: 10 to 115  
VAC/VDC  
M20  
Standard  
(resin)  
Plastic * Bottom  
Pg13.5  
G1/2  
1NC/1NO+1NC/1NO  
1NC/1NO+2NC  
2NC+1NC/1NO  
2NC+2NC  
M20  
Pg13.5  
G1/2  
M20  
Pg13.5  
G1/2  
M20  
Pg13.5  
G1/2  
M20  
Solenoid lock  
Mechanical release  
Pg13.5  
G1/2  
2NC/1NO+1NC/1NO  
2NC/1NO+2NC  
3NC+1NC/1NO  
3NC+2NC  
M20  
Pg13.5  
G1/2  
M20  
Pg13.5  
G1/2  
M20  
Pg13.5  
G1/2  
M20  
* Switches with metal heads can also be manufactured upon request. Ask your OMRON representative for details.  
2
D4NL  
Contact configuration  
(door open/closed  
detection switch and lock  
monitor switch contacts)  
(slow-action)  
Release  
key  
position  
Head  
material  
Release  
key type  
Solenoid voltage/  
indicator  
Lock and release  
types  
Conduit opening  
Model  
Certified direct opening  
NC contact  
Pg13.5  
G1/2  
D4NL-1AFA-B4  
D4NL-2AFA-B4  
D4NL-4AFA-B4  
D4NL-1BFA-B4  
D4NL-2BFA-B4  
D4NL-4BFA-B4  
D4NL-1CFA-B4  
D4NL-2CFA-B4  
D4NL-4CFA-B4  
D4NL-1DFA-B4  
D4NL-2DFA-B4  
D4NL-4DFA-B4  
D4NL-1EFA-B4  
D4NL-2EFA-B4 *2  
D4NL-4EFA-B4  
D4NL-1FFA-B4  
D4NL-2FFA-B4 *2  
D4NL-4FFA-B4  
D4NL-1GFA-B4  
D4NL-2GFA-B4 *2  
D4NL-4GFA-B4  
D4NL-1HFA-B4  
D4NL-2HFA-B4 *2  
D4NL-4HFA-B4  
D4NL-1AFG-B4  
D4NL-2AFG-B4  
D4NL-4AFG-B4  
D4NL-1BFG-B4  
D4NL-2BFG-B4  
D4NL-4BFG-B4  
D4NL-1CFG-B4  
D4NL-2CFG-B4  
D4NL-4CFG-B4  
D4NL-1DFG-B4  
D4NL-2DFG-B4  
D4NL-4DFG-B4  
D4NL-1EFG-B4  
D4NL-2EFG-B4  
D4NL-4EFG-B4  
D4NL-1FFG-B4  
D4NL-2FFG-B4  
D4NL-4FFG-B4  
D4NL-1GFG-B4  
D4NL-2GFG-B4  
D4NL-4GFG-B4  
D4NL-1HFG-B4  
D4NL-2HFG-B4  
D4NL-4HFG-B4  
1NC/1NO+1NC/1NO  
1NC/1NO+2NC  
2NC+1NC/1NO  
2NC+2NC  
M20  
Pg13.5  
G1/2  
M20  
Pg13.5  
G1/2  
M20  
Pg13.5  
G1/2  
M20  
Mechanical lock  
Solenoid release  
Pg13.5  
G1/2  
2NC/1NO+1NC/1NO  
2NC/1NO+2NC  
3NC+1NC/1NO  
3NC+2NC  
M20  
Pg13.5  
G1/2  
M20  
Pg13.5  
G1/2  
M20  
Pg13.5  
G1/2  
Special  
release  
key  
Solenoid: 24 VDC  
Orange LED: 10 to 115  
VAC/VDC  
M20  
Plastic *1 Bottom  
Pg13.5  
G1/2  
(resin)  
1NC/1NO+1NC/1NO  
1NC/1NO+2NC  
2NC+1NC/1NO  
2NC+2NC  
M20  
Pg13.5  
G1/2  
M20  
Pg13.5  
G1/2  
M20  
Pg13.5  
G1/2  
M20  
Solenoid lock  
Mechanical release  
Pg13.5  
G1/2  
2NC/1NO+1NC/1NO  
2NC/1NO+2NC  
3NC+1NC/1NO  
3NC+2NC  
M20  
Pg13.5  
G1/2  
M20  
Pg13.5  
G1/2  
M20  
Pg13.5  
G1/2  
M20  
*1. Switches with metal heads can also be manufactured upon request. Ask your OMRON representative for details.  
*2. Models with Korean S-mark certification.  
3
D4NL  
Contact configuration  
(door open/closed  
detection switch and lock  
monitor switch contacts)  
(slow-action)  
Release  
key  
position  
Head  
material  
Release  
key type  
Solenoid voltage/  
indicator  
Lock and release  
types  
Conduit opening  
Model  
Certified direct opening  
NC contact  
G1/2  
M20  
G1/2  
M20  
G1/2  
M20  
G1/2  
M20  
G1/2  
M20  
G1/2  
M20  
G1/2  
M20  
G1/2  
M20  
D4NL-2EFA-B-SJ *  
D4NL-4EFA-B-SJ *  
D4NL-2FFA-B-SJ *  
D4NL-4FFA-B-SJ *  
D4NL-2GFA-B-SJ *  
D4NL-4GFA-B-SJ *  
D4NL-2HFA-B-SJ *  
D4NL-4HFA-B-SJ *  
D4NL-2EFG-B-SJ *  
D4NL-4EFG-B-SJ *  
D4NL-2FFG-B-SJ *  
D4NL-4FFG-B-SJ *  
D4NL-2GFG-B-SJ *  
D4NL-4GFG-B-SJ *  
D4NL-2HFG-B-SJ *  
D4NL-4HFG-B-SJ *  
2NC/1NO+1NC/1NO  
2NC/1NO+2NC  
3NC+1NC/1NO  
3NC+2NC  
Mechanical lock  
Solenoid release  
Solenoid: 24 VDC  
Orange LED: 10 to 115  
VAC/VDC  
Standard  
(metal)  
Plastic  
Bottom  
2NC/1NO+1NC/1NO  
2NC/1NO+2NC  
3NC+1NC/1NO  
3NC+2NC  
Solenoid lock  
Mechanical release  
* These models will receive Korean S-mark certification.  
4
D4NL  
Operation Keys  
Type  
Model  
Horizontal mounting  
D4DS-K1  
Vertical mounting  
D4DS-K2  
D4DS-K3  
Adjustable mounting  
(Horizontal)  
Adjustable mounting  
(Horizontal/Vertical)  
D4DS-K5  
Specifications  
Standards and EC Directives  
Conforms to the following EC Directives:  
Certified Standard Ratings  
TÜV (EN60947-5-1), CCC (GB14048.5)  
Machinery Directive  
Low Voltage Directive  
EN 1088  
EN 60204-1  
GS-ET-19  
Utilization  
AC-15  
DC-13  
0.27 A  
250 V  
Item  
category  
Rated operating current (Ie) 3 A  
Rated operating voltage (Ue) 240 V  
Note: Use a 10 A fuse type gI or gG that conforms to IEC60269 as a  
short-circuit protection device. This fuse is not built into the  
Switch.  
Certified Standards  
Certification body  
Standard  
File No.  
Consult your  
OMRON  
(certified direct opening) representative for  
details.  
UL/CSA (UL508, CSA C22.2 No. 14)  
A300  
EN60947-5-1  
TÜV SÜD  
Current (A)  
Make Break  
60  
30  
Volt-amperes (VA)  
Rated  
Carry current  
UL *1  
CQC (CCC)  
KOSHA *2  
UL508, CSA C22.2 No.14  
GB14048.5  
E76675  
2003010305064267  
2005-196  
voltage  
Make  
Break  
120 VAC  
240 VAC  
6
10 A  
7,200  
720  
EN60947-5-1  
3
*1. Certification for CSA C22.2 No. 14 is authorized by the UL mark.  
*2. Only certain models have been certified.  
Q300  
Current (A)  
Volt-amperes (VA)  
Rated  
voltage  
Carry current  
Make  
Break  
0.55  
Make  
Break  
125 VDC  
250 VDC  
0.55  
0.27  
2.5 A  
69  
69  
0.27  
Solenoid Coil Characteristics  
Item  
Type  
24 VDC  
110 VAC  
Rated operating voltage  
(100% ED)  
24 VDC +1150ꢀ  
110 VAC 10ꢀ  
Approx. 50 mA  
Current  
consumption  
Approx. 200 mA  
Insulation  
Class B (130°C max.)  
Indicator Characteristics  
Item  
Type  
LED  
10 to 115 VAC/VDC  
Rated voltage  
Current leakage  
Color (LED)  
Approx. 1 mA  
Orange  
5
D4NL  
Characteristics  
Degree of protection *1  
IP67 (EN60947-5-1)  
Mechanical  
Electrical  
1,000,000 operations min.  
500,000 operations min. (3 A resistive load at 250 VAC) *3  
0.05 to 0.5 m/s  
Durability *2  
Operating speed  
Operating frequency  
30 operations/minute max.  
60 N min. (EN60947-5-1)  
10 mm min. (EN60947-5-1)  
1,300 N min.  
Direct opening force *4  
Direct opening travel *4  
Holding force *5  
Contact resistance  
25 mΩ max. (per contact)  
1 mA resistive load at 5 VDC (N-level reference value)  
300 V (EN60947-5-1)  
Minimum applicable load *6  
Rated insulation voltage (Ui)  
Rated frequency  
50/60 Hz  
Protection against electric shock  
Pollution degree (operating environment)  
Class II (double insulation)  
3 (EN60947-5-1)  
Between terminals of  
same polarity  
2.5 kV  
4 kV  
Between terminals of  
different polarity  
Impulse withstand  
voltage  
(EN60947-5-1)  
Between each  
terminal and  
6 kV  
non-current carrying  
metallic parts  
Insulation resistance  
Contact gap  
100 MΩ min. (at 500 VDC)  
2 × 2 mm min.  
Vibration  
resistance  
Malfunction  
10 to 55 Hz, 0.75 mm single amplitude  
Destruction  
Malfunction  
1,000 m/s2 min.  
100 m/s2 min.  
Shock resistance  
Conditional short-circuit current  
Conventional free air thermal current (Ith)  
Ambient operating temperature  
Ambient operating humidity  
Weight  
100 A (EN60947-5-1)  
10 A (EN60947-5-1)  
10 to 55°C (with no icing)  
95ꢀ max.  
Approx. 370 g (D4NL-1AFA-B)  
Note: 1. The above values are initial values.  
2. The Switch contacts can be used with either standard loads or microloads. Once the contacts have been used to switch a load, however,  
they cannot be used to switch smaller loads. The contact surfaces will become rough once they have been used and contact reliability  
for smaller loads may be reduced.  
*1. The degree of protection is tested using the method specified by the standard (EN60947-5-1). Confirm that sealing properties are sufficient for  
the operating conditions and environment beforehand. Although the switch box is protected from dust or water penetration, do not use the  
D4NL in places where foreign material may enter through the key hole on the head, otherwise Switch damage or malfunctioning may occur.  
*2. The durability is for an ambient temperature of 5 to 35°C and an ambient humidity of 40ꢀ to 70ꢀ. For more details, consult your OMRON  
representative.  
*3. Do not pass the 3 A, 250 VAC load through more than 2 circuits.  
*4. These figures are minimum requirements for safe operation.  
*5. This figure is based on the GS-ET-19 evaluation method.  
*6. This value will vary with the switching frequency, environment, and reliability level. Confirm that correct operation is possible with the actual  
load beforehand.  
6
D4NL  
Connections  
Internal Circuit Diagram  
Indicator  
Circuit Connection Example  
Connection Example for D4NL-@F@@-B  
Terminals 12 and 41 are connected internally. When connecting  
inputs to safety circuits, use terminals 11 and 42. (GS-ET-19).  
Connect terminals 21 and 22 and terminals 51 and 52 in series  
when using as safety-circuit inputs (redundancy circuit for  
terminals 11 and 12 and terminals 41 and 42 below). Connect the  
terminals individually when using as auxiliary-circuit inputs (e.g.,  
terminals 21 and 22 for safety-door open/closed monitoring and  
terminals 51 and 52 for monitoring the lock status).  
10 to 115 VAC/VDC  
R
ZD  
LED  
R
Constant-current diode  
In the following connection example, terminals 21 and 22 and  
terminals 51 and 52 are used as auxiliary-circuit inputs.  
Solenoid  
Direct opening contacts used as safety-circuit inputs are indicated  
24 VDC  
110 VAC/230 VAC  
with the  
mark. Terminals 11 and 42, and terminals 21 and 22  
E1 (+)  
E1 (+)  
have direct opening contacts.  
Connect the indicators in parallel to the auxiliary circuits or  
terminals E1 and E2 (D4NL-@@@A-B, -@@@G-B, -@@@B-B, and  
-@@@H-B only).  
E2 ()  
E2 ()  
Connecting to contacts with direct opening mechanisms may result  
in short-circuit current flowing if the indicator is destroyed, possibly  
resulting in incorrect equipment operation.  
Do not switch circuits for two or more standard loads at the same  
time. Doing so may adversely affect insulation performance.  
DC solenoids have polarity. Confirm terminal polarity before wiring.  
51  
12  
41  
42  
Safety  
11  
21  
circuit  
52  
Auxiliary  
circuit  
22  
Auxiliary  
circuit  
34  
Auxiliary  
circuit  
33  
E2 ()  
E1 (+)  
Indicator  
(Orange)  
O1  
O2  
7
D4NL  
Operation Method  
Operation Principles  
Solenoid  
Operation Key  
ON  
OFF  
OFF  
Mechanical  
lock  
models  
When the Operation Key is inserted, it is The solenoid is released only when the  
Spring  
Lock plate  
locked by the lock spring. The door will  
stay locked even if there is a power  
interruption.  
lock is turned ON.  
Solenoid  
Operation Key  
ON  
OFF  
Plunger  
OFF  
Solenoid  
lock  
models  
If the solenoid is OFF, the door will not be The door is locked only when the solenoid  
locked when the Operation Key is is turned ON. This means that the door will  
inserted. This means that the door can be be unlocked if there is a power interruption  
opened and closed easily when replacing and so this model cannot be used in  
Spring  
Lock plate  
workpieces or parts.  
systems that would maintain a hazardous  
state (e.g., systems requiring toxic gases,  
high temperatures, or gears that would  
continue to turn due to inertia).  
Structure and Nomenclature  
Structure  
Operation key hole  
Solenoid  
Terminal 42  
Back-mounting is also possible.  
The head can be  
mounted in 4 directions.  
Terminal 41  
Terminal E1 (+)  
Shorting pin (12-41)  
Terminal E2 ()  
Terminal 01  
Terminal 12  
Terminal 11  
Indicator  
Two conduits  
(horizontal and vertical)  
Terminal 02  
Door open/closed  
detection switch  
Lock monitor switch  
Terminal 21  
Conduit opening  
Special release key  
Terminal 22  
Terminal 31/33  
Terminal 32/34  
(horizontal)  
Standard Release Key  
(Bottom View)  
Special Release Key  
(Bottom View)  
Terminal 52/54  
Release key  
Terminal 51/53  
Conduit opening  
(vertical)  
UNLOCK  
LOCK  
UNLOCK  
LOCK  
Note: Terminal numbers vary with the model.  
8
D4NL  
Contact Form  
Indicates conditions where the Key is inserted and the lock is applied. Terminals 12 and 41 are connected internally (as per GS-ET-19).  
Contact form  
Contact  
(door open/closed  
detection and lock  
monitor)  
Door open/  
Model  
Operating pattern  
Remarks  
Lock  
monitor  
closed  
detection  
Lock position  
Only NC contacts 11-12  
have a certified direct  
opening mechanism.  
Door open/  
Lock monitor  
11-42  
33-34  
53-54  
closed detection  
ON  
ON  
ON  
Zb  
Zb  
D4NL-@AF@-@  
1NC/1NO + 1NC/1NO  
1NC/1NO + 2NC  
2NC + 1NC/1NO  
11  
33  
12 41  
34 53  
42  
54  
The terminals 11-42,  
33-34, and 53-54 can be  
used as unlike poles.  
Stroke  
Extraction  
completion  
position  
Operation  
Key insertion  
completion position  
Lock position  
Only NC contacts 11-12  
have a certified direct  
opening mechanism.  
Door open/  
closed detection  
Lock monitor  
Zb  
11-42  
33-34  
51-52  
Zb  
D4NL-@BF@-@  
D4NL-@CF@-@  
11  
33  
12 41  
42  
The terminals 11-42,  
33-34, and 51-52 can be  
used as unlike poles.  
Stroke  
Operation  
Extraction  
completion  
position  
34 51  
52  
Key insertion  
completion position  
Lock position  
Only NC contacts 11-12  
and 31-32 have a  
certified direct opening  
mechanism.  
Door open/  
closed detection  
Lock monitor  
11-42  
31-32  
53-54  
Zb  
Zb  
11  
31  
12 41  
32 53  
42  
54  
Stroke  
The terminals 11-42,  
31-32, and 53-54 can be  
used as unlike poles.  
Operation  
Extraction  
completion  
position  
Key insertion  
completion position  
Only NC contacts 11-12  
and 31-32 have a  
certified direct opening  
mechanism.  
Lock position  
Door open/  
Lock monitor  
Zb  
11-42  
closed detection  
31-32  
51-52  
ON  
Zb  
D4NL-@DF@-@  
D4NL-@EF@-@  
2NC + 2NC  
11  
31  
12 41  
42  
The terminals 11-42,  
31-32, and 51-52 can be  
used as unlike poles.  
Stroke  
Operation  
Extraction  
completion  
position  
32 51  
52  
Key insertion  
completion position  
Lock position  
Only NC contacts 11-12  
and 21-22 have a  
certified direct opening  
mechanism.  
Door open/  
closed detection  
Lock monitor  
11-42  
21-22  
33-34  
53-54  
ON  
Zb  
Zb  
11  
12 41  
42  
54  
2NC/1NO + 1NC/1NO  
The terminals 11-42,  
21-22, 33-34, and 53-54  
can be used as unlike  
poles.  
21  
33  
22 53  
34  
Stroke  
Operation  
Extraction  
completion  
position  
Key insertion  
completion position  
Lock position  
Only NC contacts 11-12  
and 21-22 have a  
certified direct opening  
mechanism.  
Door open/  
Lock monitor  
Zb  
11-42  
closed detection  
21-22  
33-34  
51-52  
ON  
ON  
ON  
Zb  
11  
12 41  
42  
D4NL-@FF@-@  
D4NL-@GF@-@  
D4NL-@HF@-@  
2NC/1NO + 2NC  
3NC + 1NC/1NO  
3NC + 2NC  
The terminals 11-42,  
21-22, 33-34, and 51-52  
can be used as unlike  
poles.  
Stroke  
21  
33  
22 51  
34  
52  
Operation  
Extraction  
completion  
position  
Key insertion  
completion position  
Lock position  
Only NC contacts 11-12,  
21-22, and 31-32 have a  
certified direct opening  
mechanism.  
Door open/  
Lock monitor  
11-42  
closed detection  
21-22  
31-32  
53-54  
Zb  
Zb  
11  
12 41  
42  
54  
The terminals 11-42,  
21-22, 31-32, and 53-54  
can be used as unlike  
poles.  
Stroke  
21  
31  
22 53  
32  
Operation  
Extraction  
completion  
position  
Key insertion  
completion position  
Lock position  
Only NC contacts 11-12,  
21-22, and 31-32 have a  
certified direct opening  
mechanism.  
Door open/  
Lock monitor  
Zb  
11-42  
closed detection  
21-22  
31-32  
51-52  
Zb  
11  
12 41  
42  
The terminals 11-42,  
21-22, 31-32, and 51-52  
can be used as unlike  
poles.  
Stroke  
21  
31  
22 51  
32  
52  
Extraction  
completion  
position  
Operation  
Key insertion  
completion position  
9
D4NL  
Dimensions  
(Unit: mm)  
Dimensions and Operating Characteristics  
Switches  
D4NL-@@@@-B  
8
Operating  
characteristics  
Model  
15.5  
30.5  
D4NL-@@@@-B  
Key insertion force  
Key extraction force  
15 N max.  
30 N max.  
Pre-travel distance  
Red  
Four, head mounting screws  
Operation Key  
Three, 4.3-dia. holes  
Black  
Pre-travel distance  
9 mm max.  
15.3  
29  
Movement before being  
locked  
6.5  
10.0  
4.4  
3 mm min.  
4
Dummy cap  
Indicator  
0.2  
32  
28.5  
UNLOCK  
(13.3)  
(95)  
6.5  
0.5  
(32.3)  
55  
LOCK  
29  
0.2  
(55.8)  
Five, cover  
59  
(3)  
mounting screws  
4
6.5  
0.5  
(30.7)  
Cap screw  
35.5  
(57.9)  
79  
(15.3)  
0.2  
5
4.5  
29  
(88.5)  
Conduit cap  
Release key  
(10)  
UNLOCK  
LOCK  
Conduit opening  
D4NL-@@@@-B4  
8
Operating  
characteristics  
Model  
15.5  
30.5  
D4NL-@@@@-B4  
Key insertion force  
Key extraction force  
15 N max.  
30 N max.  
Pre-travel distance  
Red  
Four, head mounting screws  
Operation Key  
Black  
Pre-travel distance  
9 mm max.  
15.3  
29  
Three, 4.3-dia. holes  
Movement before being  
locked  
6.5  
10.0  
4.4  
3 mm min.  
4
Dummy cap  
Indicator  
0.2  
32  
28.5  
UNLOCK  
(13.3)  
(95)  
6.5  
0.5  
(32.3)  
55  
LOCK  
29  
0.2  
(55.8)  
59  
Five, cover  
mounting screws  
(3)  
4
6.5  
(15.3)  
0.5  
(30.7)  
Cap screw  
35.5  
(57.9)  
79  
0.2  
5
4.5  
29  
(88.5)  
Releasing tool  
(provided)  
Release key  
M8 hexagonal material  
or equivalent  
Conduit cap  
8
10.5  
(10)  
UNLOCK  
LOCK  
21  
Conduit opening  
Note: 1. Unless otherwise specified, a tolerance of ±0.4 mm applies to all dimensions.  
2. There are fluctuations in the contact ON/OFF timing for Switches with multiple poles (2NC, 2NC/1NO, or 3NC). Confirm performance  
before application.  
10  
D4NL  
D4NL-@@@@-BS  
8
Operating  
characteristics  
Model  
15.5  
30.5  
D4NL-@@@@-BS  
Key insertion force  
Key extraction force  
15 N max.  
30 N max.  
Pre-travel distance  
Four, head mounting screws  
Operation Key  
Red  
Black  
15.3  
Pre-travel distance  
9 mm max.  
29  
Three, 4.3-dia. holes  
6.5  
10.0  
4.4  
Movement before being  
locked  
3 mm min.  
4
Release key  
0.2  
32  
28.5  
Indicator  
UNLOCK  
(13.3)  
(95)  
6.5  
0.5  
(32.3)  
55  
LOCK  
29  
0.2  
(31.5)  
(55.8)  
59  
Five, cover  
mounting screws  
(3)  
4
6.5  
0.5  
(30.7)  
Cap screw  
35.5  
(57.9)  
79  
(15.3)  
0.2  
5
4.5  
29  
(88.5)  
Dummy cap  
Conduit cap  
UNLOCK  
LOCK  
Conduit opening  
D4NL-@@@@-B4S  
8
15.5  
30.5  
Operating  
characteristics  
Model  
Pre-travel distance  
D4NL-@@@@-B4S  
Four, head mounting screws  
Operation Key  
15.3  
29  
Key insertion force  
Key extraction force  
15 N max.  
30 N max.  
Three, 4.3-dia. holes  
6.5  
10.0  
4.4  
Red  
Black  
4
Pre-travel distance  
9 mm max.  
Release key  
Indicator  
Movement before being  
locked  
0.2  
32  
28.5  
3 mm min.  
UNLOCK  
(13.3)  
(95)  
6.5  
(32.3)  
55  
LOCK  
29  
0.2  
(31.5)  
(55.8)  
Five, cover  
mounting screws  
59  
0.5  
(3)  
4
6.5  
(15.3)  
0.5  
(30.7)  
Cap screw  
35.5  
(57.9)  
79  
0.2  
5
4.5  
29  
Releasing tool  
(provided)  
(88.5)  
Dummy  
cap  
M8 hexagonal material  
or equivalent  
Conduit cap  
8
10.5  
UNLOCK  
LOCK  
21  
Conduit opening  
Note: 1. Unless otherwise specified, a tolerance of ±0.4 mm applies to all dimensions.  
2. There are fluctuations in the contact ON/OFF timing for Switches with multiple poles (2NC, 2NC/1NO, or 3NC). Confirm performance  
before application.  
Operation Keys  
14 28  
Angle adjustment bolt  
9 dia.  
D4DS-K3  
D4DS-K1  
17.5 28  
13  
8 dia.  
4.5 dia.  
4
4.3  
7
7
13  
30 40 56  
30 15  
13  
20°  
Black  
Four, 2.15R  
2
2
6.3  
20.9  
4
15  
10.5  
28  
24.6  
Mounting Holes  
D4DS-K5  
D4DS-K2  
(Enlargement)  
22.5  
6
7
7
9
28  
17  
15  
4.5  
30  
13  
15  
15°  
43 41  
8
30 55  
13  
2
4.3  
41  
43  
Four, 2.15R  
18°  
Black  
6.5  
(7)  
8
1
Note: Unless otherwise specified, a tolerance of ±0.4 mm applies to all dimensions.  
11  
D4NL  
With Operation Key Inserted  
D4NL + D4DS-K1  
D4NL + D4DS-K1  
(with Front-inserted Operation Key)  
(with Top-inserted Operation Key)  
Vertical  
insertion radius:  
R 200  
Horizontal  
insertion radius:  
R 200  
Red  
Red  
Black  
Black  
44 min 46.5 max  
Center  
tolerance of  
(8)  
Key insertion position  
(30.5)  
key hole:  
1
Center  
tolerance of  
key hole:  
15  
49.5 min 52.0 max  
Key insertion position  
(36)  
1
Vertical  
insertion radius:  
R 200  
44 min 46.5 max  
Key insertion position  
(30.5)  
Horizontal  
insertion radius:  
R 200  
Center  
(28.5)  
tolerance of  
Center  
tolerance of  
key hole:  
key hole:  
1
15  
1
49.5 min 52.0 max  
Key insertion position  
(36)  
D4NL + D4DS-K2  
(with Front-inserted Operation Key)  
D4NL + D4DS-K2  
(with Top-inserted Operation Key)  
Vertical  
insertion radius:  
R 200  
Horizontal  
insertion radius:  
R 200  
Black  
Red  
Red  
Black  
40 min 42.5 max  
Key insertion position  
Center  
tolerance of  
(30.5)  
(8)  
(6)  
key hole:  
1
Center  
tolerance of  
key hole:  
15  
45.5 min 48.0 max  
Key insertion position  
(36)  
1
Vertical  
insertion radius:  
R 200  
40 min 42.5 max  
Key insertion position  
(30.5)  
(6)  
Horizontal  
insertion radius:  
R 200  
Center  
tolerance of  
(22.5)  
key hole:  
1
Center  
tolerance of  
15  
key hole:  
1
(28.5)  
45.5 min 48.0 max  
Key insertion position  
(36)  
12  
D4NL  
D4NL + D4DS-K3  
D4NL + D4DS-K3  
(with Front-inserted Operation Key)  
(with Top-inserted Operation Key)  
Vertical  
insertion radius:  
R 200  
45 min 47.5 max  
Key insertion position  
Red  
Horizontal  
insertion radius:  
R 50  
Black  
Red  
Black  
(30.5)  
Center  
tolerance of  
(8)  
key hole:  
1
Center  
tolerance of  
key hole:  
(40)  
50.5 min 53.0 max  
Key insertion position  
1
(36)  
Vertical  
insertion radius:  
R 200  
45 min 47.5 max  
Key insertion position  
(30.5)  
Center  
tolerance of  
key hole:  
Horizontal  
insertion radius:  
R 50  
40  
Center  
tolerance of  
1
(28.5)  
key hole:  
1
50.5 min 53.0 max  
Key insertion position  
(36)  
D4NL + D4DS-K5  
D4NL + D4DS-K5  
(with Front-inserted Operation Key)  
(with Top-inserted Operation Key)  
Horizontal  
insertion radius:  
R 50  
Center  
tolerance of  
key hole:  
51.9 min 54.4 max  
Key insertion position  
Red  
(8)  
Black  
Red  
Black  
1
(30.5)  
57.4 min 59.9 max  
Key insertion position  
(36)  
(41 or 43)  
55  
Center  
tolerance of  
key hole:  
1
20.9  
Horizontal  
insertion radius:  
R 50  
Vertical  
insertion radius:  
R 50  
Center  
tolerance of  
key hole:  
Horizontal  
insertion radius:  
R 50  
43 0.1  
1
51.9 min 54.4 max  
Key insertion position  
(30.5)  
57.4 min 59.9 max  
Key insertion position  
Center  
(36)  
tolerance of  
key hole:  
1
(28.5)  
13  
D4NL  
Application Examples  
G9SA-321-T@ (24 VAC/VDC) + D4NL-@A@A-@, -@A@B-@, -@A@C-@  
(Mechanical Lock Type) Circuit Diagram (Manual Reset)  
Lock release signal  
KM1  
KM2  
S2  
S4  
42  
54  
S1:  
Safety Limit Switch  
with direct opening mechanism  
(D4B-N, D4N, D4F)  
Guard Lock Safety-door Switch  
Reset switch  
Lock release switch  
41  
12  
53  
34  
33  
S2:  
S3:  
S4:  
11  
KM1 and KM2: Magnetic Contactor  
PLC  
PLC  
M:  
3-phase motor  
Guard  
S1  
Feedback loop  
KM1  
OPEN  
S3  
KM2  
Stop signal  
A1 A2 T11  
TH  
T12  
T31  
T32  
13 23 33 43 53 61  
1
3
4
K3  
K4  
a
K1  
K2  
K3  
1
2
3
4
SA  
a
K4  
5
OffDelay  
Timer  
Control  
Circuit  
2
5
JP  
K1  
K2  
K1  
6
b
K2  
b
6
PE T21  
T23 T22  
A
B
14 24 34 44 54 62  
KM1 KM2  
Guard opens  
Timing Chart  
Limit switch S1  
Operation  
instruction  
Guard Lock  
Safety-door  
Switch S2  
Motor controller  
Lock release  
signal  
KM1  
KM2  
S4  
Guard can be opened  
Stop signal  
Reset switch  
S3  
K1 and K2  
(NC)  
M
K1 and K2  
(NO)  
K3 and K4  
(NC)  
K3 and K4  
(NO)  
KM1 and KM2  
(NC)  
Note: The above example circuit is for Category 3.  
KM1 and KM2  
(NO)  
Operation  
instruction  
Motor rotation  
OFF-delay time  
14  
D4NL  
G9SA-301 (24 VAC/VDC) + D4NL-@A@G-@, -@A@H-@, -@A@J-@  
(Solenoid Lock Type) Circuit Diagram (Auto-reset)  
Lock signal  
S2  
54  
53  
42  
41  
S1:  
S2:  
Safety Limit Switch  
with direct opening mechanism  
(D4B-N, D4N, D4F)  
Guard Lock Safety-door Switch  
12  
11  
34  
33  
KM1 and KM2:Magnetic Contactor  
M: 3-phase motor  
PLC  
PLC  
S1  
12  
11  
Feedback loop  
OPEN  
KM1  
KM2  
Operation signal  
A1 A2 T11  
TH  
T12  
T31  
T32  
13 23 33 41  
3
4
1
K1  
K2  
a
K1  
K2  
1
2
3
4
5
6
SA  
Control  
Circuit  
a
2
5
JP  
K1  
b
b
K2  
6
PE T21  
T23 T22  
A
B
14 24 34 42  
KM1 KM2  
Operation  
instruction  
Motor controller  
KM1  
Guard opens  
Timing Chart  
Limit switch S1  
KM2  
Guard Lock  
Safety-door  
Switch S2  
Operation signal  
M
Lock signal  
K1 and K2  
(NC)  
Note: 1. This example circuit is for Category 4.  
K1 and K2  
(NO)  
2. The lock can be released at any time. Therefore, do  
not use a model with a solenoid lock in applications  
where the operator may be exposed to danger when  
the guard opens. Use a model with a mechanical lock.  
KM1 and KM2  
(NC)  
KM1 and KM2  
(NO)  
15  
D4NL  
Safety Precautions  
Refer to the “Precautions for All Switches” and “Precautions for All Safety Door Switches”.  
Installation  
DANGER  
Make sure the Switch is mounted securely to prevent it from falling  
off. Otherwise injury may result.  
Do not use the Switch as a stopper.  
Be sure to install a stopper as shown in the following illustration to  
ensure that the base of the Operation Key does not strike the  
Head, and adjust the stopper to be within the setting zone (0.5 to 3  
mm) of the base of the Operation Key.  
Injury may occasionally occur. Always check to make  
sure that the safety functions operate correctly before  
using the machine. The safety functions may not operate  
correctly because of wiring mistakes, setting mistakes,  
or Switch malfunction, causing some machines to  
continue operating in situations where they should be  
stopped.  
Do not subject the Switch to a shock that exceeds the Switch's  
Injury may occasionally occur. If the machine is used  
with the release key in the UNLOCK position, the  
electromagnetic lock may not operate, causing some  
machines to continue operating in situations where they  
should be stopped. Be sure to put the release key in the  
LOCK position before using the machine. Also, check  
the condition of the lock and safety circuits.  
shock resistance of 1,000 m/s2.  
Operation Key  
Stopper  
Set zone  
(0.5 to 3 mm)  
Injury may occasionally occur. Always ensure that the  
release key is set to "UNLOCK" or that the Operation  
Key is inserted before changing the direction of the head.  
Not doing so may damage the Switch, causing some  
machines to continue operating in situations where they  
should be stopped. Refer to “Release Key” on page 16.  
UNLOCK  
LOCK  
Precautions for Correct Use  
Injury may occasionally occur. When the  
The Switch contacts can be used with either standard loads or  
microloads. Once the contacts have been used to switch a load,  
however, they cannot be used to switch smaller loads. The contact  
surfaces will become rough once they have been used and contact  
reliability for smaller loads may be reduced.  
electromagnetic lock function or Switch function is  
damaged, some machines may continue operating in  
situations where they should be stopped. Do not use the  
electromagnetic lock function of the Switch in place of a  
door lock. Always provide a lock separate from the  
Switch, attach a warning seal to prevent people from  
using excessive force to open the door when it is locked,  
or provide an indicator lamp to show the locked/unlocked  
status of the door.  
Release Key  
The release key is used to unlock the Switch in case of emergency  
or if the power supply to the Switch stops.  
If the release key setting is changed from LOCK to UNLOCK, the  
lock will be released and the safety door can be opened  
(mechanical lock models only).  
The release key is set in the unlock position at the factory for the  
D4NL-@@@A/B/C and to the lock position for the D4NL-@@@G/H/  
J.  
!CAUTION  
Electric shock may occasionally occur.  
Do not use metal connectors or metal conduits.  
Do not use the release key to start or stop machines.  
The auxiliary lock must only be released by authorized personnel.  
Do not impose a force exceeding 1 N·m on the release key screws.  
The release key may be damaged and may not operate properly.  
To prevent the release key from being used by unauthorized  
personnel, set it to LOCK and seal it with sealing wax.  
Precautions for Safe Use  
Installation Environment  
Do not use the Switch submersed in oil or water or in locations  
continuously subject to splashes of oil or water. Doing so may  
result in oil or water entering the Switch. (The IP67 degree of  
protection of the Switch specifies the amount of water penetration  
after the Switch is submerged in water for a certain period of time.)  
Figure 1  
D4NL-@@@@-@S  
UNLOCK  
LOCK  
Wiring  
D4NL-@@@@-@4S  
UNLOCK  
Do not switch circuits for two or more standard loads (250 VAC,  
3 A). Doing so may adversely affect insulation performance.  
Always attach the cover after completing wiring and before using  
the Switch. Do not supply power when the cover is not attached.  
Electric shock may occur if the Switch is used without the cover  
attached.  
LOCK  
D4NL-@@@@-@  
D4NL-@@@@-@4  
UNLOCK  
LOCK  
UNLOCK  
LOCK  
Hinged Door  
If an attempt is made to open the door beyond the lock position when  
the Switch is used for a hinged door at a location near to the hinged  
side, where the Operation Key’s insertion radius is comparatively  
small, the force imposed will be much larger than for locations far from  
the hinged side, and the lock may be damaged. Mount the Switch  
close to the handle.  
16  
D4NL  
Attaching a Cover  
Solenoid Lock Models  
When attaching a cover, be sure that the seal rubber is in place and  
that there is no foreign material present. If the cover is attached  
with the seal rubber out of place or if foreign material is stuck to the  
rubber, a proper seal will not be obtained.  
Do not use any screws to connect the cover other than the  
specified ones. The seal characteristics may be reduced.  
The solenoid lock locks the door only when power is supplied to the  
solenoid. Therefore, the door will be unlocked if the power supply to  
the solenoid stops. Therefore, do not use solenoid lock models for  
machines that may be operating and dangerous even after the  
machine stops operating.  
Mounting  
Appropriate Tightening Torque  
Securing the Door  
When the door is closed (with the Operation Key inserted), the  
Operation Key may exceed the set zone because of, for example, the  
door's own weight, machine vibration, or the door cushion rubber.  
Then, when an attempt is made to open the door, it may result in  
damage or malfunction. Also, it may not be possible to unlock the  
Switch if there is weight placed on the Operation Key. Do not rely on  
the Switch to substitute for a door locking device. Secure the door with  
a stopper so that the Operation Key remains within the set zone.  
Be sure to tighten each screw of the Switch properly. Loose screws  
may result in malfunction.  
Type  
Terminal screw  
Appropriate tightening torque  
0.59 to 0.78 N·m  
Cover mounting screw  
Head mounting screw  
Operation Key mounting screw  
Switch mounting screw  
Connector  
0.49 to 0.69 N·m  
0.49 to 0.59 N·m  
2.35 to 2.75 N·m  
0.49 to 0.69 N·m  
1.77 to 2.16 N·m  
Set zone  
(0.5 to 3 mm)  
Cap screw  
1.27 to 1.67 N·m  
When loosening a screw with an electrical screwdriver or similar  
tool while pressing down on the screw head, do not continue  
turning the screw past the point where the threads disengage.  
Doing so may strip the end of the threads.  
Operation key  
Solenoid  
The solenoid will heat when it carries current. Do not touch it.  
A DC solenoid has polarity. Confirm terminal polarity before wiring  
it.  
Switch and Operation Key Mounting  
Use M4 screws and washers to mount the Switch and Operation  
Key, and tighten the screws to a suitable torque.  
To ensure safety, use screws that cannot be easily removed or  
another means to prevent the Switch and Operation Key from  
easily being removed.  
Wiring  
Circuit Connection Example for the D4NL-@F@@-B  
Direct opening contacts used as safety-circuit inputs are indicated  
Mounting Holes for Switches  
Mounting Holes  
for Operation Keys  
with the  
mark. Terminals 11 and 42, and terminals 21 and 22  
have direct opening contacts.  
Horizontal/Vertical Mounting (D4DS-K1/-K2)  
Two, M4  
Three, M4  
Connect terminals 21 and 22 and terminals 51 and 52 in series  
when using as safety-circuit inputs (redundancy circuit for  
terminals 11 and 12 and terminals 41 and 42 below). Connect the  
terminals individually when using as auxiliary-circuit inputs (e.g.,  
terminals 21 and 22 for safety-door open/closed monitoring and  
terminals 51 and 52 for monitoring the lock status).  
In the following connection example, terminals 21 and 22 and  
terminals 51 and 52 are used as auxiliary-circuit inputs.  
Connect the indicators in parallel to the auxiliary circuits or  
terminals E1 and E2 (D4NL-@@@A-B, -@@@G-B, -@@@B-B, and  
-@@@H-B only).  
0.1  
32  
55  
0.1  
15  
0.1  
Adjustable Mounting: Horizontal (D4DS-K3)  
Two, M4  
0.1  
40  
0.1  
79  
Adjustable Mounting: Horizontal/Vertical  
(D4DS-K5)  
Two, M4  
Connecting to contacts with direct opening mechanisms may result  
in short-circuit current flowing if the indicator is destroyed, possibly  
resulting in incorrect equipment operation.  
0.1  
0.1  
or, 43  
41  
If the Switch is back-mounted, the release key can be operated  
only from the bottom and the indicator cannot be used.  
Ensure that the alignment offset between the Operation Key and  
the key hole does not exceed ±1 mm. If the Operation Key is offset  
or at an angle, accelerated wear or damage to the Switch may  
result.  
Observe the specified insertion radius for the Operation Key and  
insert it in a direction perpendicular to the key hole.  
Do not impose excessive force on the Operation Key while the Key  
is inserted into the Switch or drop the Switch with the Operation  
Key inserted. Doing either of these may deform the Key or break  
the Switch.  
51  
12  
41  
42  
Safety  
11  
21  
circuit  
52  
Auxiliary  
circuit  
22  
Auxiliary  
circuit  
34  
Auxiliary  
circuit  
33  
E2 ()  
E1 (+)  
Indicator  
(Orange)  
Head Direction  
Remove the four screws of the head to enable changing the  
mounting direction of the head. The head can be mounted in four  
directions. Ensure that no foreign material enters the interior of the  
Switch.  
O1  
O2  
Do not change the head direction with the cover removed.  
Do not insert or remove the Operation Key with the Switch head  
removed. Doing so may make it impossible to insert the Operation  
Key.  
17  
D4NL  
Wiring Precautions  
Do not wire the Switch while power is being  
supplied. Doing so may result in electric shock.  
Do not let particles, such as small pieces of lead  
wire, enter the switch body when wiring.  
Recommended Connectors  
Use a connector with a screw section not exceeding 11 mm.  
Otherwise the screws will protrude into the case interior. The  
connectors given in the following table have connectors with screw  
sections not exceeding 11 mm.  
When connecting to the terminals via insulating  
tube and M3.5 crimp terminals, cross the crimp  
terminals as shown above so that they do not rise  
up onto the case or the cover.  
Applicable lead wire size: AWG20 to AWG18 (0.5 to 0.75 mm2).  
Use lead wires of an appropriate length. Not doing so may result in  
excess length causing the cover to rise and not fit properly.  
Do not push crimp terminals into gaps in the case interior. Doing so  
may cause damage or deformation of the case.  
Use terminals having the thickness of 0.5 mm or less to avoid the  
contact between the terminal and the interior of the Switch case.  
[Reference] The terminals listed below have thickness of 0.5 mm or  
less.  
Use the following connectors to ensure conformance to IP67.  
Applicable cable  
Size  
Manufacturer  
Model  
ST-PF1/2  
5380-1002  
OA-W1609  
OA-W1611  
diameter  
LAPP  
6.0 to 12.0 mm  
G1/2  
7.0 to 9.0 mm  
9.0 to 11.0 mm  
OHM  
ELECTRIC CO.  
ST-13.5  
5301-5030  
Pg13.5  
M20  
LAPP  
LAPP  
6.0 to 12.0 mm  
7.0 to 13.0 mm  
ST-M20 × 1.5  
5311-1020  
Use LAPP connectors together with Seal Packing (JPK-16,  
GP-13.5, or GPM20), and tighten to the applicable torque. Seal  
Packing is sold separately.  
• LAPP is a German manufacturer.  
• OHM Electric Co. is a Japanese manufacturer.  
Manufacturer  
J.S.T. Mfg Co.  
Model  
FN0.5-3.7 (F Type)  
No. 5-3.7 (Straight Type)  
D dia.  
dz dia.  
Processing the Conduit Opening  
Connect a recommended connector to the opening of the conduit  
and tighten the connector to the proper torque. The case may be  
damaged if excessive tightening torque is applied.  
Make sure that the outer diameter of the cable connected to the  
connector is correct.  
Attach a conduit cap to the unused conduit opening when wiring  
and tighten it to a suitable torque. The conduit cap is provided with  
the Switch.  
18  
Read and Understand This Catalog  
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or  
comments.  
Warranty and Limitations of Liability  
WARRANTY  
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)  
from date of sale by OMRON.  
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR  
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS  
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER  
WARRANTIES, EXPRESS OR IMPLIED.  
LIMITATIONS OF LIABILITY  
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS  
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT  
LIABILITY.  
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.  
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS  
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT  
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.  
Application Considerations  
SUITABILITY FOR USE  
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's  
application or use of the products.  
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the  
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,  
machine, system, or other application or use.  
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible  
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:  
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.  
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,  
safety equipment, and installations subject to separate industry or government regulations.  
Systems, machines, and equipment that could present a risk to life or property.  
Please know and observe all prohibitions of use applicable to the products.  
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE  
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND  
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.  
PROGRAMMABLE PRODUCTS  
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.  
Disclaimers  
CHANGE IN SPECIFICATIONS  
Product specifications and accessories may be changed at any time based on improvements and other reasons.  
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.  
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or  
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual  
specifications of purchased products.  
DIMENSIONS AND WEIGHTS  
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.  
PERFORMANCE DATA  
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the  
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON  
Warranty and Limitations of Liability.  
ERRORS AND OMISSIONS  
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,  
typographical, or proofreading errors, or omissions.  
2012.1  
In the interest of product improvement, specifications are subject to change without notice.  
OMRON Corporation  
Industrial Automation Company  
http://www.ia.omron.com/  
(c)Copyright OMRON Corporation 2012 All Right Reserved.  

相关型号:

SI9130DB

5- and 3.3-V Step-Down Synchronous Converters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1-E3

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135_11

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9136_11

Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130CG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130LG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130_11

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137DB

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137LG

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9122E

500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification Drivers

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY