Advanced Digital Temperature Controller
E5AN-H/E5EN-H
(96 x 96 mm and 48 x 96 mm)
CSM_E5AN-H_E5EN-H_DS_E_3_2
A New High-performance Controller: High Resolution, High Speed, and
High Input Accuracy.
Logic Operations and Preventive Maintenance Function. Plus Infrared
Port on Front Panel.
• High-resolution display with 5 digits/0.01°C display.
• High-speed sampling cycle of 60 ms.
• High Accuracy
Thermocouple/Pt input: 0.1% of PV
Analog input: 0.1% FS
• Universal inputs on all models (thermocouple, PT, or analog input)
to handle various sensors with one Controller. Models also
available with Remote SP.
• A PV/SV-status display function can be set to automatically
alternate between displaying the status of the Temperature
Controller (auto/manual, RUN/STOP, and alarms) and the PV or
96 × 96 mm
E5AN-H
48 × 96 mm
E5EN-H
SV.
• Flexible contact outputs with logic operations (AND, OR, and
delays) set from the Support Software (CX-Thermo Ver. 4.0)
• Preventive maintenance for relays in the Temperature Controller
using a Control Output ON/OFF Counter.
Refer to Safety Precautions for E5@N/E5@N-H.
Refer to Operation for E5@N/E5@N-H for operating
procedures.
• Model available with position-proportional control
Main I/O Functions
E5AN-H
E5EN-H
Remote SP Input
• One
3-level Display
Event Inputs
• None
Simultaneously displays set items, such as the
PV, SV, and MV.
• Two
• Four
5-digit Display with high resolution of 0.01°C
• Auto/manual switching
Universal Sensor Inputs
• Universal thermocouple/
Pt/analog
• Temperature Controller
Auxiliary Outputs
status display
• Two
(current/voltage) inputs.
• Simple program
• Three
Infrared port
function
Indication Accuracy
• Thermocouple/Pt input:
0.1% of PV
• Logic operations
• Control output ON/OFF
count alarm
Computer Support Software
USB
CX-Thermo
• Analog input:
0.1% FS
• PV change rate alarm
• Models available with
RS-485, RS-422, or
RS-232C
Control Output 2
(built-in)
• SSR outputs
Output Unit
• Relay output
• Voltage output (for driving SSR)
• Current output
• Linear voltage output
Sampling Period
• 60 ms
communications
PF Key
(Programmable
key function)
Control Output 1
(built-in)
Output Unit
• SSR outputs
• Relay output
• Voltage output (for driving SSR)
• Current output
• Linear voltage output
1
E5AN-H/E5EN-H
Lineup
2 auxiliary outputs
2 auxiliary outputs
1 control output
2 control outputs
E5AN-H/E5EN-H
Advanced Type
Terminal block
Fully universal input
Note: The Controller can be used for heating/cooling control even if only 1 control output is used.
Model Number Structure
Model Number Legend
Controllers
Option Units
E53-@
E5AN/E5EN-@@@@@@@M@-@-500
1
1 2 3 4 5 6 7 8 9 10 11
1. Type
1. Function
H: Advanced
EN01: RS-232C communications
EN02: RS-422 communications
EN03: RS-485 communications
AKB: Event input
2. Control Mode
Blank: Standard or heating/cooling control
P: Position-proportional control
3. Control Output 1
A: Control Output Unit
R: Relay output
Output Units
E53-@@
S: SSR output
1 2
4. Control Output 2
A: Control Output Unit
R: Relay output
1. Control Output
R: Relay output
Q: Voltage output (for driving SSR)
S: SSR output
Q3: Voltage output (for driving SSR) + 24 VDC (NPN)
Q4: Voltage output (for driving SSR) + 24 VDC (PNP)
C3: Current output + 4 to 20 mA DC
C3D: Current output + 0 to 20 mA DC
V34: Linear voltage output + 0 to 10 VDC
V35: Linear voltage output + 0 to 5 VDC
5. Auxiliary Outputs
2: Two outputs
3: Three outputs
6. Option 1
Blank: None
H: Heater burnout/SSR failure/Heater overcurrent detection (CT1)
HH: Heater burnout/SSR failure/Heater overcurrent detection
(CT2)
2. Version
Blank: Available for E5AN-E5EN-H and E5AK/E5EK.
N: Available only for E5AN-H/E5EN-H.
7. Option 2
B: Two event inputs
BF: Event input + Transfer output
8. Option 3
M: Option Unit can be mounted.
9. Power Supply Voltage
Blank: 100 to 240 VAC
D: 24 VAC/VDC
10.Case Color
Blank: Black
W: Silver
11.Terminal Cover
-500: With Terminal Cover
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions
and other information required for operation before attempting to use the product.
E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157)
E5CN-H/E5AN-H/E5EN-H Digital Controllers Communications Manual Advanced Type (Cat. No. H159)
2
E5AN-H/E5EN-H
Ordering Information
E5AN-H
Optional functions
Transfer
Power
supply
voltage
Case
color
Control Auxiliary
Heater
burnout
Size
Control output 1/2
Model
Event
method
output
RSP
inputs
output
4 to 20-mA
input
Control Output Unit × 2
SSR outputs × 2
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
E5AN-HAA2HBM-500
E5AN-HSS2HBM-500
4 to 20-mA
input
2
4 to 20-mA 4 to 20-mA
Control Output Unit × 2
SSR outputs × 2
E5AN-HAA2HHBFM-500
E5AN-HSS2HHBFM-500
E5AN-HAA3BFM-500
output
4 to 20-mA 4 to 20-mA
output input
4 to 20-mA 4 to 20-mA
output input
4 to 20-mA 4 to 20-mA
input
Basic
100 to
240 VAC
Control Output Unit × 2
SSR outputs × 2
3
2
E5AN-HSS3BFM-500
output
input
4 to 20-mA
input
Relay outputs × 2
E5AN-HPRR2BM-500
E5AN-HPRR2BFM-500
E5AN-HAA2HBMD-500
E5AN-HSS2HBMD-500
E5AN-HAA2HHBFMD-500
E5AN-HSS2HHBFMD-500
E5AN-HAA3BFMD-500
E5AN-HSS3BFMD-500
E5AN-HPRR2BMD-500
E5AN-HPRR2BFMD-500
E5AN-HAA2HBM-W-500
E5AN-HAA2HHBFM-W-500
E5AN-HAA2HBMD-W-500
Valve
4 to 20-mA 4 to 20-mA
Relay outputs × 2
output
input
Black
4 to 20-mA
input
Control Output Unit × 2
SSR outputs × 2
1
1
2
2
1/4 DIN
96 × 96 × 78
4 to 20-mA
input
(W × H × D)
2
4 to 20-mA 4 to 20-mA
output input
Control Output Unit × 2
SSR outputs × 2
Basic
4 to 20-mA 4 to 20-mA
output input
24 VAC/
VDC
4 to 20-mA 4 to 20-mA
output input
Control Output Unit × 2
SSR outputs × 2
3
2
4 to 20-mA 4 to 20-mA
output
input
4 to 20-mA
input
Relay outputs × 2
Valve
Basic
4 to 20-mA 4 to 20-mA
Relay outputs × 2
output
input
4 to 20-mA
input
Control Output Unit × 2
Control Output Unit × 2
Control Output Unit × 2
1
2
1
100 to
240 VAC
4 to 20-mA 4 to 20-mA
Silver
2
output
input
24 VAC/
VDC
4 to 20-mA
input
3
E5AN-H/E5EN-H
E5EN-H
Optional Functions
Transfer
Auxil-
iary
output
Heater
burn-
out
Case
color
Power supply
voltage
Control
method
Size
Control output 1/2
Model
Event
RSP
inputs
output
4 to 20-mA
input
Control Output Unit × 2
SSR outputs × 2
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
E5EN-HAA2HBM-500
E5EN-HSS2HBM-500
4 to 20-mA
input
2
4 to 20-mA 4 to 20-mA
Control Output Unit × 2
SSR outputs × 2
E5EN-HAA2HHBFM-500
E5EN-HSS2HHBFM-500
E5EN-HAA3BFM-500
output
4 to 20-mA 4 to 20-mA
output input
4 to 20-mA 4 to 20-mA
output input
4 to 20-mA 4 to 20-mA
input
Basic
Valve
Basic
100 to 240 VAC
Control Output Unit × 2
SSR outputs × 2
3
2
E5EN-HSS3BFM-500
output
input
4 to 20-mA
input
Relay outputs × 2
E5EN-HPRR2BM-500
E5EN-HPRR2BFM-500
E5EN-HAA2HBMD-500
E5EN-HSS2HBMD-500
E5EN-HAA2HHBFMD-500
E5EN-HSS2HHBFMD-500
E5EN-HAA3BFMD-500
E5EN-HSS3BFMD-500
E5EN-HPRR2BMD-500
E5EN-HPRR2BFMD-500
E5EN-HAA2HBM-W-500
E5EN-HAA2HHBFM-W-500
E5EN-HAA2HBMD-W-500
4 to 20-mA 4 to 20-mA
Relay outputs × 2
output
input
Black
4 to 20-mA
input
Control Output Unit × 2
SSR outputs × 2
1
1
2
2
1/8 DIN
48 × 96 × 78
(W × H × D)
4 to 20-mA
input
2
4 to 20-mA 4 to 20-mA
output input
Control Output Unit × 2
SSR outputs × 2
4 to 20-mA 4 to 20-mA
output input
24 VAC/VDC
4 to 20-mA 4 to 20-mA
output input
Control Output Unit × 2
SSR outputs × 2
3
2
4 to 20-mA 4 to 20-mA
output
input
4 to 20-mA
input
Relay outputs × 2
Valve
Basic
4 to 20-mA 4 to 20-mA
Relay outputs × 2
output
input
4 to 20-mA
input
Control Output Unit × 2
Control Output Unit × 2
Control Output Unit × 2
1
2
1
100 to 240 VAC
24 VAC/VDC
4 to 20-mA 4 to 20-mA
Silver
2
output
input
4 to 20-mA
input
Accessories (Order Separately)
Terminal Cover
Output unit
Model
Specifications
Connectable models
E5AN-H
Model
Relay
output
SPST-NO, 250 VAC, 5 A (resistive load),
electrical life: 100,000 operations
E53-RN
E53-COV16
E5EN-H
12 VDC (PNP), max. load current:
40-mA, with short-circuit protection
E53-QN
Note: The Terminal Cover comes with the E5CN-@@@-500 models.
Waterproof Packing
Voltage
output
(for driving
SSR)
24 VDC (NPN), max. load current:
20-mA, with short-circuit protection
E53-Q3
Connectable models
E5AN-H
Model
Y92S-P4
Y92S-P5
24 VDC (PNP), max. load current:
20-mA, with short-circuit protection
E53-Q4
E5EN-H
4 to 20-mA DC, load: 600 Ω max.,
Note: The Waterproof Packing is included with the Controller.
E53-C3N
E53-C3DN
E53-V34N
E53-V35N
resolution: approx. 10,000
Current
output
Current Transformers (CTs)
0 to 20-mA DC, load: 600 Ω max.,
resolution: approx. 10,000
Hole diameter
5.8 dia.
Model
0 to 10 VDC, load: 1 kΩ min., resolution:
approx. 10,000
E54-CT1
E54-CT3
Linear
voltage
output
12.0 dia.
0 to 5 VDC, load: 1 kΩ min., resolution:
approx. 10,000
CX-Thermo Support Software
USB-infrared Conversion Cable
Model
EST2-2C-MV4
Model
E58-CIFIR
USB-Serial Conversion Cable
Model
E58-CIFQ1
4
E5AN-H/E5EN-H
Specifications
Ratings
No D in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Power supply voltage
Operating voltage range
Power consumption
85% to 110% of rated supply voltage
100 to 240 VAC: 12 VA
24 VAC/VDC: 8.5 VA (24 VAC)/5.5 W (24 VDC)
Any of the following can be selected.
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Current input: 4 to 20 mA or 0 to 20 mA
Sensor input
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Input impedance
Control method
Relay output
Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.)
ON/OFF control or 2-PID control (with auto-tuning)
Voltage output
(for driving SSR)
Output Unit (Install the Output Unit (sold separately).)
Current output
Control
Linear voltage output
output
Built-in SSR output
75 to 250 VAC, 1 A (resistive load)
Relay output for
position-proportional
control
Relay output: Open and close: SPST-NO, 250 VAC, 1 A (including in-rush current), electrical life: 100,000 operations min.
Potentiometer input: Must be between 100 Ω and 2.5 kΩ for maximum open position.
Number of outputs
Auxiliary
2 or 3 max.
Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V,
10 mA
output
Output specifications
Number of outputs
2 or 4 (with an E53-AKB)
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Current flow: Approx. 7 mA per contact
Event
input
External contact input
specifications
Number of operations 8 max.
• Logic operation: Any of the following four patterns can be selected. The input status may be inverted.
(A and B) or (C and D), (A or C) and (B or D), A or B or C or D, A and B and C and D
(A, B, C, and D are four inputs.)
ON delay or OFF delay for the results of the logic operation given above.
Setting time: 0 to 9999 s or 0 to 9999 min
Operations
Output
• Delay:
Logic
operations
• Output inversion: Possible
One work bit per operation
Work bit
assignment
Any of The following can be assigned to up to eight work bits (logic operation results): Event input operations, auxiliary
outputs, or control outputs.
Number of outputs
1 max. (Depends on model. Models with transfer output (F in model number)
Transfer
outputs
Output specifications Current output: 4 to 20 mA DC, Load: 600 Ω max., Resolution at 4 to 20 mA: Approx. 10,000
Number of inputs
Signal type
1
Current input: 4 to 20 mA (input impedance: 150 Ω 10%)
RSP
input
Scaling of signal to engineering units (EU)
−19,999 to 30,000 (display: 30,000 max.)
Analog input scaling
Accuracy
( 0.2% of FS) 1 digit max.
Input sampling period 60 ms
Setting method
Set digitally using keys on the front panel or by using the RSP input.
11-segment digital display and individual indicators (7-segments displays also possible)
Character height: E5AN-H: PV: 15.8 mm, SV: 9.5 mm, MV: 6.8 mm; E5EN-H: PV: 11.8 mm, SV: 8.1 mm, MV: 5.8 mm
Content of 3-level display: PV/SV/MV, PV/SV/Bank No., or soak time remain
Number of digits: 5 for PV and SV, 4 for MV
Indication method
Supported (number of banks: 8)
Local SP, alarm settings, PID sets (PID constants, MV upper limit, MV lower limit, etc.)
Bank switching
Other functions
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout detection, 40%
AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions, control output
ON/OFF counter, extraction of square root, MV change rate limit, PV/SV status display, logic operations, automatic cooling
coefficient adjustment
Ambient operating temperature
Ambient operating humidity
Storage temperature
−10 to 55°C (with no condensation or icing), for 3-year warranty: −10 to 50°C
25% to 85%
−25 to 65°C (with no condensation or icing)
5
E5AN-H/E5EN-H
Input Ranges
Thermocouple/Platinum Resistance Thermometer (Fully Universal Inputs)
Input
type
Platinum resistance
Thermocouple
Analog input
thermometer
4 to
0 to
PL
II
1 to
5 V
0 to
5 V
0 to
10 V
20 m 20 m
Name
Pt100
JPt100
K
J
T
E
L
U
N
R
S
B
W
A
A
2300.0
2300
1800.0
1800
1700
1600
1500
1400
1300
1200
1100
1000
900
1700.01700.0
1300.0
1300.0
1300.0
Usable in the following
ranges by scaling:
−19999 to 32400,
850.0
850.0
850.0
−1999.9 to 3240.0,
−199.99 to 324.00, or
−19.999 to 32.400
800
700
600.0
600
500.0
500.0
500.0
500
400.0
400.0 400.0
400.0 400.0
400
300
200.00
200.00
200.00
200.00
200
100.0
100.0
0.0
100
100.0
0
0.0
0.0
0.0
0.0
0.0
−100.0
−200.0
−50.00
−20.0 −50.00−100.0 −20.0 −50.00
−50.00
−100.0
−200.0−199.9
−199.9
−200.0
−200.0−199.9
−200.0
−200.0−199.9−200.0
Setting
number
0
1
2
24
3
4
5
6
21
7
8
22
9
10 23 11 12 13 14 15 16 17 18 19 20 25 26 27 28 29
Shaded settings are the default settings.
The applicable standards for the input types are as follows:
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1
L: Fe-CuNi, DIN 43710-1985
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 751
U: Cu-CuNi, DIN 43710-1985
PL II: According to Platinel II electromotive force charts from BASF (previously
Engelhard)
W: W5Re/W26Re, ASTM E988-1990
6
E5AN-H/E5EN-H
Alarm Outputs
Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit.
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the
following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR
failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function).
Alarm output operation
Set value
Alarm type
Alarm function OFF
Description of function
When alarm value When alarm value
X is positive
X is negative
0
Output OFF
No alarm
L
H
X
Set the deviation in the set point by setting the alarm
upper limit (H) and alarm lower limit (L).
ON
OFF
1
2
3
4
Upper- and lower-limit *1
Upper-limit
*2
SP
X
Set the upward deviation in the set point by setting
the alarm value (X).
ON
OFF
ON
OFF
SP
SP
X
X
ON
OFF
ON
OFF
Set the downward deviation in the set point by setting
the alarm value (X).
Lower-limit
SP
SP
L
H
H
Set the deviation in the set point by setting the alarm
upper limit (H) and alarm lower limit (L).
ON
OFF
Upper- and lower-limit range *1
*3
SP
L
ON
OFF
Upper- and lower-limit with
standby sequence *1
A standby sequence is added to the upper- and
lower-limit alarm (1). *7
5
*4
SP
*5
X
X
A standby sequence is added to the upper-limit alarm
(2). *7
ON
OFF
ON
OFF
6
Upper-limit with standby sequence
Lower-limit with standby sequence
Absolute-value upper-limit
SP
SP
X
X
ON
OFF
A standby sequence is added to the lower-limit alarm
(3). *7
ON
OFF
7
SP
X
SP
X
ON
OFF
The alarm will turn ON if the process value is larger
than the alarm value (X) regardless of the set point.
ON
OFF
8
0
0
0
0
0
0
0
0
X
X
X
X
X
X
ON
OFF
ON
OFF
The alarm will turn ON if the process value is smaller
than the alarm value (X) regardless of the set point.
9
Absolute-value lower-limit
Absolute-value upper-limit with
standby sequence
ON
OFF
A standby sequence is added to the absolute-value
upper-limit alarm (8). *7
ON
OFF
10
11
Absolute-value lower-limit with
standby sequence
A standby sequence is added to the absolute-value
lower-limit alarm (9). *7
ON
OFF
ON
OFF
*8
*9
12
13
LBA (alarm 1 type only)
PV change rate alarm
---
---
The alarm turns ON when the remote SP (RSP) is
larger than the alarm value (X). This alarm functions
in both Local SP and Remote SP Modes.
X
X
X
X
ON
OFF
ON
OFF
14
15
RSP absolute value upper limit *6
RSP absolute value lower limit *6
0
0
0
0
The alarm turns ON when the remote SP (RSP) is
smaller than the alarm value (X). This alarm
functions in both Local SP and Remote SP Modes.
ON
OFF
ON
OFF
*1. With set values 1, 4 and 5, the upper and lower limit values can
be set independently for each alarm type, and are expressed as
“L” and “H.”
*5. Set value: 5, Upper- and lower-limit with standby sequence
Always OFF when the upper-limit and lower-limit hysteresis
overlaps.
*2. Set value: 1, Upper- and lower-limit alarm
*6. Displayed when there is a remote SP input.
*7. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature
Controllers User's Manual Basic Type (Cat. No. H156) for
information on the operation of the standby sequence.
*8. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature
Controllers User's Manual Basic Type (Cat. No. H156) for
information on the loop burnout alarm (LBA).
Case 2
Case 1
Case 3 (Always ON)
H < 0, L < 0
H
SP
L
SP L
H
L
H SP
H < 0, L > 0
⏐H⏐ ≥ ⏐L⏐
H < 0, L > 0
⏐H⏐ < ⏐L⏐
H > 0, L < 0
⏐H⏐ > ⏐L⏐
H
L SP
H > 0, L < 0
*9. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature
Controllers User's Manual Basic Type (Cat. No. H156) for
information on the PV change rate alarm.
SPH
L
⏐H⏐ ≤ ⏐L⏐
*3. Set value: 4, Upper- and lower-limit range
Case 2
Case 1
Case 3 (Always ON)
H < 0, L < 0
H
SP
L
L
H
SP
SP L
H
H < 0, L > 0
⏐H⏐ ≥ ⏐L⏐
H < 0, L > 0
⏐H⏐ < ⏐L⏐
H > 0, L < 0
⏐H⏐ > ⏐L⏐
H
L SP
H > 0, L < 0
⏐H⏐ ≤ ⏐L⏐
SPH
L
*4. Set value: 5, Upper- and lower-limit with standby sequence
For Upper- and Lower-Limit Alarm Described Above
• Case 1 and 2
Always OFF when the upper-limit and lower-limit hysteresis
overlaps.
• Case 3: Always OFF
7
E5AN-H/E5EN-H
Characteristics
Thermocouple: ( 0.1% of indicated value or 1°C, whichever is greater) 1 digit max. *1
Platinum resistance thermometer: ( 0.1% of indicated value or 0.5°C, whichever is greater) 1 digit max.
Analog input: 0.1% FS 1 digit max.
CT input: 5% FS 1 digit max.
Indication accuracy
Potentiometer input: 5% FS 1 digit max.
Transfer output accuracy 0.3% FS max.
Influence of temperature Thermocouple input (R, S, B, W, PL II): ( 1% of PV or 10°C, whichever is greater) 1 digit max.
*2
Other thermocouple input: ( 1% of PV or 4°C, whichever is greater) 1 digit max. *3
Platinum resistance thermometer: ( 1% of PV or 2°C, whichever is greater) 1 digit max.
Analog input: ( 1%FS) 1 digit max.
Influence of voltage *2
Input sampling period
60 ms
Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1°C or °F)
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Hysteresis
Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1°C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Proportional band (P)
Integral time (I)
0.0 to 3240.0 s (in units of 0.1 s)
Derivative time (D)
Control period
0.0 to 3240.0 s (in units of 0.1 s)
0.5, 1 to 99 s (in units of 1 s)
Manual reset value
Alarm setting range
0.0 to 100.0% (in units of 0.1%)
−19999 to 32400 (decimal point position depends on input type)
Affect of signal source
resistance
Thermocouple: 0.1°C/Ω max. (100 Ω max.)
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
Insulation resistance
20 MΩ min. (at 500 VDC)
Dielectric strength
2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Vibration
resistance
Shock
resistance
Destruction 300 m/s2, 3 times each in X, Y, and Z directions
E5AN-H
E5EN-H
Controller: Approx. 310 g, Mounting Bracket: Approx. 100 g
Controller: Approx. 260 g, Mounting Bracket: Approx. 100 g
Front panel: IP66, Rear case: IP20, Terminals: IP00
Non-volatile memory (number of writes: 1,000,000 times)
CX-Thermo version 4.0 or higher
Weight
Degree of protection
Memory protection
Setup Tool
Provided on the bottom of the E5AN-H and E5EN-H.
An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5AN-H and E5EN-H.
Provided on the front of the E5AN-H and E5EN-H. An E58-CIFIR USB-infrared Conversion Cable is required to
connect the computer to the E5AN-H or E5EN-H. *4
Setup Tool port
Approved
UL 61010-1, CSA C22.2 No. 1010-1
standards
Standards
Conformed
EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II, Lloyd's standards *5
standards
EMI:
EN 61326
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage:
EMS:
ESD Immunity:
Electromagnetic Field Immunity:
Burst Noise Immunity:
Conducted Disturbance Immunity:
Surge Immunity:
EN 55011 Group 1, class A
EN 61326
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-6
EN 61000-4-5
EN 61000-4-8
EN 61000-4-11
EMC
Power Frequency Magnetic Field Immunity:
Voltage Dip/Interrupting Immunity:
*1. The indication accuracy of K thermocouples in the −200 to 1300°C range, T and N thermocouples at a temperature of −100°C max., and U
and L thermocouples at any temperatures is 2°C 1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max.
is not specified. The indication accuracy of B thermocouples in the 400 to 800°C range is 3°C max. The indication accuracy of the R and S
thermocouples at a temperature of 200°C max. is 3°C 1 digit max. The indication accuracy of W thermocouples is 0.3% of PV or 3°C,
whichever is greater, 1 digit max.
The indication accuracy of PL II thermocouples is 0.3% of PV or 2°C, whichever is greater, 1 digit max.
*2. Ambient temperature: −10°C to 23°C to 55°C, Voltage range: −15% to 10% of rated voltage
*3. K thermocouple at −100°C max.: 10°C max.
*4. External communications (RS-232C, RS-485, or RS-422) and cable communications for the Setup Tool can be used at the same time.
*5. Refer to information on maritime standards in Safety Precautions for E5@N/E5@N-H for compliance with Lloyd's Standards.
8
E5AN-H/E5EN-H
USB-Serial Conversion Cable
Current Transformer (Order Separately)
Ratings
Applicable OS
Windows 2000, XP, or Vista
Applicable software
CX-Thermo version 4 or higher
Dielectric strength
1,000 VAC for 1 min
E5AN/E5EN/E5CN/E5CN-U/
E5AN-H/E5EN-H/E5CN-H/E5GN
Vibration resistance
50 Hz, 98 m/s2
Applicable models
E54-CT1: Approx. 11.5 g,
E54-CT3: Approx. 50 g
Weight
USB interface standard
DTE speed
Conforms to USB Specification 1.1.
38400 bps
Armatures (2)
Plugs (2)
Accessories (E54-CT3 only)
Computer: USB (type A plug)
Temperature Controller: Setup
Tool port (on bottom of Controller)
Connector specifications
USB-Infrared Conversion Cable
Applicable OS
Bus power (Supplied from USB
host controller.)
Windows 2000, XP, or Vista
Power supply
Applicable software
Applicable models
USB interface standard
DTE speed
CX-Thermo version 4.0 or higher
E5AN-H/E5EN-H
Power supply voltage
Current consumption
5 VDC
70 mA
Conforms to USB Specification 1.1.
38400 bps
Ambient operating
temperature
0 to 55°C (with no condensation or
icing)
Computer: USB (type A plug)
Temperature Controller: Infrared
port (on front of Controller)
Ambient operating humidity 10% to 80%
Connector specifications
−20 to 60°C (with no condensation
or icing)
Storage temperature
Bus power (Supplied from USB
host controller.)
Power supply
Storage humidity
Altitude
10% to 80%
2,000 m max.
Approx. 100 g
Power supply voltage
Current consumption
5 VDC
80 mA
Weight
Note: A driver must be installed in the personal computer. Refer to
installation information in the operation manual for the
Conversion Cable.
Ambient operating
temperature
0 to 55°C (with no condensation or
icing)
Ambient operating humidity 10% to 80%
Communications Specifications
Transmission line RS-485, RS-422: Multipoint
connection method RS-232C: Point-to-point
−20 to 60°C (with no condensation
Storage temperature
or icing)
Storage humidity
Altitude
10% to 80%
2,000 m max.
RS-485 (two-wire, half duplex)
Communications
RS-422 (four-wire, half duplex) or RS-232C
Approx. 130 g (with mounting
adaptor)
Weight
Synchronization
Start-stop synchronization
method
Note: A driver must be installed in the personal computer. Refer to
installation information in the operation manual for the
Conversion Cable.
Protocol
CompoWay/F, SYSWAY, or Modbus
1200, 2400, 4800, 9600, 19200, 38400, or
57600 bps
Baud rate
Heater Burnout Alarms, SSR Failure
Alarms, and Heater Overcurrent Alarms
ASCII (CompoWay/F, SYSWAY)
RTU (Modbus)
Transmission code
Models with detection for single-phase
heaters: One input
Models with detection for single-phase
or three-phase heaters: Two inputs
Data bit length *
Stop bit length *
7 or 8 bits
1 or 2 bits
CT input
(for heater current
detection)
Vertical parity (none, even, odd)
Frame check sequence (FCS) with SYSWAY
Block check character (BCC) with
CompoWay/F or CRC-16 Modbus
Maximum heater current 50 A AC
Error detection
Input current indication
5% FS 1 digit max.
accuracy
Flow control
Interface
None
Heater burnout alarm
setting range *1
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms
RS-485, RS-422, or RS-232C
None
Retry function
SSR failure alarm setting 0.1 to 49.9 A (in units of 0.1 A)
range *2 Minimum detection OFF time: 100 ms
Communications
buffer
217 bytes
Heater overcurrent alarm 0.1 to 49.9 A (in units of 0.1 A)
setting range *3 Minimum detection ON time: 100 ms
Communications
0 to 99 ms
response wait time Default: 20 ms
* The baud rate, data bit length, stop bit length, and vertical parity can
be individually set using the Communications Setting Level.
*1. For heater burnout alarms, the heater current will be measured
when the control output is ON, and the output assigned to the
alarm 1 function will turn ON if the heater current is lower than the
set value (i.e., heater burnout detection current value).
*2. For SSR failure alarms, the heater current will be measured when
the control output is OFF, and the output assigned to the alarm 1
function will turn ON if the heater current is higher than the set
value (i.e., SSR failure detection current value).
*3. For heater overcurrent alarms, the heater current will be
measured when the control output is ON, and the output assigned
to the alarm 1 function will turn ON if the heater current is higher
than the set value (i.e., heater overcurrent detection current
value).
9
E5AN-H/E5EN-H
Electrical Life Expectancy Curve for
Relays (Reference Values)
SSR Outputs (OUT1/OUT2) Ratings
• Rated load voltage: 75 to 250 VAC
• Rated load current: 1 A (resistive load)
500
Note: 1. The load current must be within the derating curve.
2. There is no zero-cross function.
300
E5AN-H/E5EN-H
Derating Curve for SSR Outputs (Reference Values)
100
250 VAC, 30 VDC
(resistive load)
cosφ = 1
1.5
50
30
1.25
Condition B
10
1
5
3
0.75
0.5
1
0
1
2
3
4
5
6
Condition A
Switching current (A)
0.25
0
−10
0
10
20
30
40 45 50 55 60
Ambient temperature (°C)
Condition A: SSR outputs 100% ON
Condition B: SSR outputs 50% ON with 2-s control cycle
10
E5AN-H/E5EN-H
External Connections
Control output 1 and control output 2 are functionally isolated from the internal circuits.
Controllers
Option Units
The Temperature Controller is set
for a K-type thermocouple (input
type = 5) by default. An input error
(s.err) will occur if the input type
setting does not agree with the
temperature sensor. Check the
input type.
Communications
E53-EN01
RS-232C
E53-EN02
RS-422
E53-EN03
RS-485
E53-AKB
Event Inputs
11
11
11
11
SD
RDB
RDA
SG
B (+)
EV2
12
13
21
22
12
13
21
22
12
13
21
22
12
13
21
22
RD
A (−)
EV1
SG
DO NOT USE
B (+)
DO NOT USE
SDB
SDA
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
A (−)
DO NOT USE
Event Inputs
1
2
21
22
23
24
25
26
27
28
29
30
11
12
13
14
15
16
17
18
19
20
Input power
supply
EV2
EV1
3
Potentiometer
Control output 1
Control output 2
Auxiliary output 2
Auxiliary output 1
CT2
CT1
CT2
O
W
C
4
14
15
Auxiliary output 3
Auxiliary output 3
5
Relay output
SPDT, 250 VAC, 3 A
(resistive load)
16
6
DO NOT DO NOT
DO NOT
USE
7
USE
USE
A heater burnout alarm, SSR
failure, heater overcurrent
alarm, input alarm, or Remote
SP Input Error is sent to the
output to which the alarm 1
function is assigned.
A
DO NOT
USE
DO NOT
USE
8
V
mA
B
B
9
DO NOT
USE
DO NOT
USE
10
Event input/
Transfer output/
Remote SP
Models with Position-
proportional Control
Control Output Unit
SSR Outputs
Control outputs 1, 2
Control Output Unit
Control outputs 1, 2
Refer to page 4
1
1
1
21
22
23
Input power
Input power
supply
Input power
supply
supply
2
2
3
2
3
SSR Outputs
75 to 250 VAC, 1 A
(resistive load)
+
3
EV3
EV4
Output unit
SSR
SSR
Open
Models with Position-
proportional Control
Relay output
250 VAC, 1 A
(including inrush
4
4
4
24
25
26
27
28
29
30
−
+
5
5
5
Output unit
Closed
Auxiliary output 2
Auxiliary output 1
6
6
6
DO NOT USE
−
current)
+
7
Auxiliary output 2
8
7
7
4 to 20 mA DC
(Load: 600 Ω max.)
Auxiliary output 2
Transfer output
Auxiliary outputs 1, 2, 3
8
8
−
Relay output
SPST-NO,
250 VAC, 3 A
(resistive load)
+
9
9
9
4 to 20 mA DC
Auxiliary output 1
Auxiliary output 1
Remote SP input
10
10
10
−
Note: Wire all voltage input terminals correctly. The Controller may fail if voltage input terminals are wired incorrectly.
11
E5AN-H/E5EN-H
Nomenclature
E5AN-H
E5EN-H
Temperature unit
Operation indicators
Temperature unit
SUB1 SUB2
HA SUB3
SUB1
SUB2
SUB3
PV
PV
No.1 display
Operation indicators
No.1 display
HA
SV
SV
No.2 display
No.3 display
No.2 display
RSP
OUT1 RSP STOP
OUT2
OUT1 STOP
MV
MV
No.3 display
Operation indicators
OUT2 CMW MANU
CMW MANU
Up Key
Mode Key
Level Key
Programmable
Function Key/
Up Key
Programmable
Function Key/
Auto/Manual Key
Auto/Manual Key
Ir
Ir
E5EN-H
E5AN-H
Down Key
Down Key
Level Key
Mode Key
Dimensions
(Unit: mm)
E5AN-H
Mounted Separately
Group Mounted *
(96 × number of units − 3.5)+1.0
92+0.8
0
0
92+0.8
0
Group mounting does not
allow waterproofing.
120 min.
6
•
Recommended panel thickness is 1 to
8 mm.
79.2
2
•
Group mounting is not possible in the
vertical direction. (Maintain the specified
mounting space between Controllers.)
To mount the Controller so that it is
waterproof, insert the waterproof
packing onto the Controller.
When two or more Controllers are
mounted, make sure that the
surrounding temperature does not
exceed the allowable operating
temperature specified in the
specifications.
92+0.8
0
•
•
96 × 96
112
91
* Group mounting is not possible if an SSR output is used for
control output 1 or 2 and the E53-C3N or E53-C3DN Output Unit
is used. For these combinations, maintain the following mounting
space between Controllers.
Terminal Cover
(E53-COV16)
(Accessory)
Waterproof
Packing
Mounting Bracket
(Accessory)
110 min.
92+0.8
0
(Accessory)
Crimp terminal size: M3.5
92+0.8
0
120 min.
12
E5AN-H/E5EN-H
E5EN-H
Mounted Separately
Group Mounted *
(48 × number of units − 2.5)+1.0
0
45+0.6
0
92+0.8
0
Group mounting does not
allow waterproofing.
120 min.
•
•
Recommended panel thickness is 1 to 8 mm.
Group mounting is not possible in the vertical direction.
(Maintain the specified mounting space between
Controllers.)
92+0.8
0
6
•
When two or more Controllers are mounted, make
sure that the surrounding temperature does not
exceed the allowable operating temperature specified
in the specifications.
79.2
48
2
* Group mounting is not possible if an SSR output is used for control
output 1 or 2 and the E53-C3N or E53-C3DN Output Unit is used.
For these combinations, maintain the following mounting space
between Controllers.
112
96
91
60 min.
45+0.6
0
92+0.8
0
Terminal Cover
(E53-COV16)
(Accessory)
Waterproof
Packing
(Accessory)
Mounting Bracket
(Accessory)
Crimp terminal size: M3.5
120 min.
13
E5AN-H/E5EN-H
Accessories (Order Separately)
USB-Infrared Conversion Cable
E58-CIFIR
USB-Infrared Conversion Cable
(2,000)
54
35.8
4.6 dia.
USB connector (type A plug)
LED indicator: RD LED indicator: SD
17.8
With Mounting Adapter Connected
Mounting Adapter
39
16
18.5
Mounting Adapter
(Accessory)
99.2
23.1
21.8
(75)
USB-Serial Conversion Cable
E58-CIFQ1
(2,100)
LED indicator: SD
1,765
250
USB connector (type A plug)
Serial connector
LED indicator: RD
Terminal Covers
E53-COV16 (Six Covers provided.)
1.2 3.2
10
44.8
14
E5AN-H/E5EN-H
Waterproof Packing
Y92S-P4 (for DIN 96 × 96)
Order the Waterproof Packing separately if it becomes lost or
damaged.
Y92S-P5 (for DIN 48 × 96)
The Waterproof Packing can be used to achieve an IP66 degree of
protection.
(Deterioration, shrinking, or hardening of the waterproof packing may
occur depending on the operating environment. Therefore, periodic
replacement is recommended to ensure the level of waterproofing
specified in IP66. The time for periodic replacement depends on the
operating environment. Be sure to confirm this point at your site.
Consider one year a rough standard. OMRON shall not be liable for
the level of water resistance if the customer does not perform periodic
replacement.)
The Waterproof Packing does not need to be attached if a waterproof
structure is not required.
Current Transformers
E54-CT1
E54-CT1
21
2.8
Thru-current (Io) vs. Output Voltage
(Eo) (Reference Values)
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 400 2
15
5.8 dia.
7.5
Winding resistance: 18 2 Ω
25
3
100 V
10.5
50 Hz
∞
10
40
Distortion
factor 10%
1 kΩ
Two, 3.5 dia.
1
3%
10
1%
100 mV
30
100 Ω
10
1
E54-CT3
RL = 10 Ω
2.36 dia.
30
12 dia.
100 µV
9
10
1
10
100 mA
1
10
100 1,000 A
40 × 40
Thru-current (Io) A (r.m.s.)
E54-CT3
Thru-current (Io) vs. Output Voltage
(Eo) (Reference Values)
Two, M3 (depth 4)
Maximum continuous heater current: 120 A (50/60 Hz)
(Maximum continuous heater current for an OMRON
Temperature Controller is 50 A.)
15
30
Number of windings: 400 2
Winding resistance: 8 0.8 Ω
E54-CT3 Accessory
• Armature
100 V
50 Hz
Distor-
Connection Example
tion
∞
10
factor
10%
3%
1 kΩ
Armature
500 Ω
Plug
Approx. 3 dia.
1%
1
100 mV
10
Lead
100 Ω
50 Ω
18
RL = 10 Ω
• Plug
1
100 µV
Approx. 6 dia.
10
1
10
100 mA
1
10
100 1,000 A
(22)
Thru-current (Io) A (r.m.s.)
15
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
·
·
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
·
Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2009.11
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2009 All Right Reserved.
相关型号:
©2020 ICPDF网 联系我们和版权申明