Advanced Digital Temperature Controller  
E5AN-H/E5EN-H  
(96 x 96 mm and 48 x 96 mm)  
CSM_E5AN-H_E5EN-H_DS_E_3_2  
A New High-performance Controller: High Resolution, High Speed, and  
High Input Accuracy.  
Logic Operations and Preventive Maintenance Function. Plus Infrared  
Port on Front Panel.  
• High-resolution display with 5 digits/0.01°C display.  
• High-speed sampling cycle of 60 ms.  
• High Accuracy  
Thermocouple/Pt input: 0.1% of PV  
Analog input: 0.1% FS  
• Universal inputs on all models (thermocouple, PT, or analog input)  
to handle various sensors with one Controller. Models also  
available with Remote SP.  
• A PV/SV-status display function can be set to automatically  
alternate between displaying the status of the Temperature  
Controller (auto/manual, RUN/STOP, and alarms) and the PV or  
96 × 96 mm  
E5AN-H  
48 × 96 mm  
E5EN-H  
SV.  
• Flexible contact outputs with logic operations (AND, OR, and  
delays) set from the Support Software (CX-Thermo Ver. 4.0)  
• Preventive maintenance for relays in the Temperature Controller  
using a Control Output ON/OFF Counter.  
Refer to Safety Precautions for E5@N/E5@N-H.  
Refer to Operation for E5@N/E5@N-H for operating  
procedures.  
• Model available with position-proportional control  
Main I/O Functions  
E5AN-H  
E5EN-H  
Remote SP Input  
One  
3-level Display  
Event Inputs  
None  
Simultaneously displays set items, such as the  
PV, SV, and MV.  
• Two  
• Four  
5-digit Display with high resolution of 0.01°C  
• Auto/manual switching  
Universal Sensor Inputs  
• Universal thermocouple/  
Pt/analog  
• Temperature Controller  
Auxiliary Outputs  
status display  
• Two  
(current/voltage) inputs.  
• Simple program  
• Three  
Infrared port  
function  
Indication Accuracy  
Thermocouple/Pt input:  
0.1% of PV  
• Logic operations  
• Control output ON/OFF  
count alarm  
Computer Support Software  
USB  
CX-Thermo  
Analog input:  
0.1% FS  
• PV change rate alarm  
Models available with  
RS-485, RS-422, or  
RS-232C  
Control Output 2  
(built-in)  
• SSR outputs  
Output Unit  
• Relay output  
Voltage output (for driving SSR)  
• Current output  
• Linear voltage output  
Sampling Period  
60 ms  
communications  
PF Key  
(Programmable  
key function)  
Control Output 1  
(built-in)  
Output Unit  
• SSR outputs  
• Relay output  
Voltage output (for driving SSR)  
• Current output  
• Linear voltage output  
1
E5AN-H/E5EN-H  
Lineup  
2 auxiliary outputs  
2 auxiliary outputs  
1 control output  
2 control outputs  
E5AN-H/E5EN-H  
Advanced Type  
Terminal block  
Fully universal input  
Note: The Controller can be used for heating/cooling control even if only 1 control output is used.  
Model Number Structure  
Model Number Legend  
Controllers  
Option Units  
E53-@  
E5AN/E5EN-@@@@@@@M@-@-500  
1
1 2 3 4 5 6 7 8 9 10 11  
1. Type  
1. Function  
H: Advanced  
EN01: RS-232C communications  
EN02: RS-422 communications  
EN03: RS-485 communications  
AKB: Event input  
2. Control Mode  
Blank: Standard or heating/cooling control  
P: Position-proportional control  
3. Control Output 1  
A: Control Output Unit  
R: Relay output  
Output Units  
E53-@@  
S: SSR output  
1 2  
4. Control Output 2  
A: Control Output Unit  
R: Relay output  
1. Control Output  
R: Relay output  
Q: Voltage output (for driving SSR)  
S: SSR output  
Q3: Voltage output (for driving SSR) + 24 VDC (NPN)  
Q4: Voltage output (for driving SSR) + 24 VDC (PNP)  
C3: Current output + 4 to 20 mA DC  
C3D: Current output + 0 to 20 mA DC  
V34: Linear voltage output + 0 to 10 VDC  
V35: Linear voltage output + 0 to 5 VDC  
5. Auxiliary Outputs  
2: Two outputs  
3: Three outputs  
6. Option 1  
Blank: None  
H: Heater burnout/SSR failure/Heater overcurrent detection (CT1)  
HH: Heater burnout/SSR failure/Heater overcurrent detection  
(CT2)  
2. Version  
Blank: Available for E5AN-E5EN-H and E5AK/E5EK.  
N: Available only for E5AN-H/E5EN-H.  
7. Option 2  
B: Two event inputs  
BF: Event input + Transfer output  
8. Option 3  
M: Option Unit can be mounted.  
9. Power Supply Voltage  
Blank: 100 to 240 VAC  
D: 24 VAC/VDC  
10.Case Color  
Blank: Black  
W: Silver  
11.Terminal Cover  
-500: With Terminal Cover  
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions  
and other information required for operation before attempting to use the product.  
E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157)  
E5CN-H/E5AN-H/E5EN-H Digital Controllers Communications Manual Advanced Type (Cat. No. H159)  
2
E5AN-H/E5EN-H  
Ordering Information  
E5AN-H  
Optional functions  
Transfer  
Power  
supply  
voltage  
Case  
color  
Control Auxiliary  
Heater  
burnout  
Size  
Control output 1/2  
Model  
Event  
method  
output  
RSP  
inputs  
output  
4 to 20-mA  
input  
Control Output Unit × 2  
SSR outputs × 2  
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
E5AN-HAA2HBM-500  
E5AN-HSS2HBM-500  
4 to 20-mA  
input  
2
4 to 20-mA 4 to 20-mA  
Control Output Unit × 2  
SSR outputs × 2  
E5AN-HAA2HHBFM-500  
E5AN-HSS2HHBFM-500  
E5AN-HAA3BFM-500  
output  
4 to 20-mA 4 to 20-mA  
output input  
4 to 20-mA 4 to 20-mA  
output input  
4 to 20-mA 4 to 20-mA  
input  
Basic  
100 to  
240 VAC  
Control Output Unit × 2  
SSR outputs × 2  
3
2
E5AN-HSS3BFM-500  
output  
input  
4 to 20-mA  
input  
Relay outputs × 2  
E5AN-HPRR2BM-500  
E5AN-HPRR2BFM-500  
E5AN-HAA2HBMD-500  
E5AN-HSS2HBMD-500  
E5AN-HAA2HHBFMD-500  
E5AN-HSS2HHBFMD-500  
E5AN-HAA3BFMD-500  
E5AN-HSS3BFMD-500  
E5AN-HPRR2BMD-500  
E5AN-HPRR2BFMD-500  
E5AN-HAA2HBM-W-500  
E5AN-HAA2HHBFM-W-500  
E5AN-HAA2HBMD-W-500  
Valve  
4 to 20-mA 4 to 20-mA  
Relay outputs × 2  
output  
input  
Black  
4 to 20-mA  
input  
Control Output Unit × 2  
SSR outputs × 2  
1
1
2
2
1/4 DIN  
96 × 96 × 78  
4 to 20-mA  
input  
(W × H × D)  
2
4 to 20-mA 4 to 20-mA  
output input  
Control Output Unit × 2  
SSR outputs × 2  
Basic  
4 to 20-mA 4 to 20-mA  
output input  
24 VAC/  
VDC  
4 to 20-mA 4 to 20-mA  
output input  
Control Output Unit × 2  
SSR outputs × 2  
3
2
4 to 20-mA 4 to 20-mA  
output  
input  
4 to 20-mA  
input  
Relay outputs × 2  
Valve  
Basic  
4 to 20-mA 4 to 20-mA  
Relay outputs × 2  
output  
input  
4 to 20-mA  
input  
Control Output Unit × 2  
Control Output Unit × 2  
Control Output Unit × 2  
1
2
1
100 to  
240 VAC  
4 to 20-mA 4 to 20-mA  
Silver  
2
output  
input  
24 VAC/  
VDC  
4 to 20-mA  
input  
3
E5AN-H/E5EN-H  
E5EN-H  
Optional Functions  
Transfer  
Auxil-  
iary  
output  
Heater  
burn-  
out  
Case  
color  
Power supply  
voltage  
Control  
method  
Size  
Control output 1/2  
Model  
Event  
RSP  
inputs  
output  
4 to 20-mA  
input  
Control Output Unit × 2  
SSR outputs × 2  
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
E5EN-HAA2HBM-500  
E5EN-HSS2HBM-500  
4 to 20-mA  
input  
2
4 to 20-mA 4 to 20-mA  
Control Output Unit × 2  
SSR outputs × 2  
E5EN-HAA2HHBFM-500  
E5EN-HSS2HHBFM-500  
E5EN-HAA3BFM-500  
output  
4 to 20-mA 4 to 20-mA  
output input  
4 to 20-mA 4 to 20-mA  
output input  
4 to 20-mA 4 to 20-mA  
input  
Basic  
Valve  
Basic  
100 to 240 VAC  
Control Output Unit × 2  
SSR outputs × 2  
3
2
E5EN-HSS3BFM-500  
output  
input  
4 to 20-mA  
input  
Relay outputs × 2  
E5EN-HPRR2BM-500  
E5EN-HPRR2BFM-500  
E5EN-HAA2HBMD-500  
E5EN-HSS2HBMD-500  
E5EN-HAA2HHBFMD-500  
E5EN-HSS2HHBFMD-500  
E5EN-HAA3BFMD-500  
E5EN-HSS3BFMD-500  
E5EN-HPRR2BMD-500  
E5EN-HPRR2BFMD-500  
E5EN-HAA2HBM-W-500  
E5EN-HAA2HHBFM-W-500  
E5EN-HAA2HBMD-W-500  
4 to 20-mA 4 to 20-mA  
Relay outputs × 2  
output  
input  
Black  
4 to 20-mA  
input  
Control Output Unit × 2  
SSR outputs × 2  
1
1
2
2
1/8 DIN  
48 × 96 × 78  
(W × H × D)  
4 to 20-mA  
input  
2
4 to 20-mA 4 to 20-mA  
output input  
Control Output Unit × 2  
SSR outputs × 2  
4 to 20-mA 4 to 20-mA  
output input  
24 VAC/VDC  
4 to 20-mA 4 to 20-mA  
output input  
Control Output Unit × 2  
SSR outputs × 2  
3
2
4 to 20-mA 4 to 20-mA  
output  
input  
4 to 20-mA  
input  
Relay outputs × 2  
Valve  
Basic  
4 to 20-mA 4 to 20-mA  
Relay outputs × 2  
output  
input  
4 to 20-mA  
input  
Control Output Unit × 2  
Control Output Unit × 2  
Control Output Unit × 2  
1
2
1
100 to 240 VAC  
24 VAC/VDC  
4 to 20-mA 4 to 20-mA  
Silver  
2
output  
input  
4 to 20-mA  
input  
Accessories (Order Separately)  
Terminal Cover  
Output unit  
Model  
Specifications  
Connectable models  
E5AN-H  
Model  
Relay  
output  
SPST-NO, 250 VAC, 5 A (resistive load),  
electrical life: 100,000 operations  
E53-RN  
E53-COV16  
E5EN-H  
12 VDC (PNP), max. load current:  
40-mA, with short-circuit protection  
E53-QN  
Note: The Terminal Cover comes with the E5CN-@@@-500 models.  
Waterproof Packing  
Voltage  
output  
(for driving  
SSR)  
24 VDC (NPN), max. load current:  
20-mA, with short-circuit protection  
E53-Q3  
Connectable models  
E5AN-H  
Model  
Y92S-P4  
Y92S-P5  
24 VDC (PNP), max. load current:  
20-mA, with short-circuit protection  
E53-Q4  
E5EN-H  
4 to 20-mA DC, load: 600 max.,  
Note: The Waterproof Packing is included with the Controller.  
E53-C3N  
E53-C3DN  
E53-V34N  
E53-V35N  
resolution: approx. 10,000  
Current  
output  
Current Transformers (CTs)  
0 to 20-mA DC, load: 600 max.,  
resolution: approx. 10,000  
Hole diameter  
5.8 dia.  
Model  
0 to 10 VDC, load: 1 kmin., resolution:  
approx. 10,000  
E54-CT1  
E54-CT3  
Linear  
voltage  
output  
12.0 dia.  
0 to 5 VDC, load: 1 kmin., resolution:  
approx. 10,000  
CX-Thermo Support Software  
USB-infrared Conversion Cable  
Model  
EST2-2C-MV4  
Model  
E58-CIFIR  
USB-Serial Conversion Cable  
Model  
E58-CIFQ1  
4
E5AN-H/E5EN-H  
Specifications  
Ratings  
No D in model number: 100 to 240 VAC, 50/60 Hz  
D in model number: 24 VAC, 50/60 Hz; 24 VDC  
Power supply voltage  
Operating voltage range  
Power consumption  
85% to 110% of rated supply voltage  
100 to 240 VAC: 12 VA  
24 VAC/VDC: 8.5 VA (24 VAC)/5.5 W (24 VDC)  
Any of the following can be selected.  
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II  
Platinum resistance thermometer: Pt100 or JPt100  
Current input: 4 to 20 mA or 0 to 20 mA  
Sensor input  
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V  
Input impedance  
Control method  
Relay output  
Current input: 150 max., Voltage input: 1 Mmin. (Use a 1:1 connection when connecting the ES2-HB.)  
ON/OFF control or 2-PID control (with auto-tuning)  
Voltage output  
(for driving SSR)  
Output Unit (Install the Output Unit (sold separately).)  
Current output  
Control  
Linear voltage output  
output  
Built-in SSR output  
75 to 250 VAC, 1 A (resistive load)  
Relay output for  
position-proportional  
control  
Relay output: Open and close: SPST-NO, 250 VAC, 1 A (including in-rush current), electrical life: 100,000 operations min.  
Potentiometer input: Must be between 100 and 2.5 kfor maximum open position.  
Number of outputs  
Auxiliary  
2 or 3 max.  
Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V,  
10 mA  
output  
Output specifications  
Number of outputs  
2 or 4 (with an E53-AKB)  
Contact input: ON: 1 kmax., OFF: 100 kmin.  
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.  
Current flow: Approx. 7 mA per contact  
Event  
input  
External contact input  
specifications  
Number of operations 8 max.  
Logic operation: Any of the following four patterns can be selected. The input status may be inverted.  
(A and B) or (C and D), (A or C) and (B or D), A or B or C or D, A and B and C and D  
(A, B, C, and D are four inputs.)  
ON delay or OFF delay for the results of the logic operation given above.  
Setting time: 0 to 9999 s or 0 to 9999 min  
Operations  
Output  
Delay:  
Logic  
operations  
Output inversion: Possible  
One work bit per operation  
Work bit  
assignment  
Any of The following can be assigned to up to eight work bits (logic operation results): Event input operations, auxiliary  
outputs, or control outputs.  
Number of outputs  
1 max. (Depends on model. Models with transfer output (F in model number)  
Transfer  
outputs  
Output specifications Current output: 4 to 20 mA DC, Load: 600 max., Resolution at 4 to 20 mA: Approx. 10,000  
Number of inputs  
Signal type  
1
Current input: 4 to 20 mA (input impedance: 150 10%)  
RSP  
input  
Scaling of signal to engineering units (EU)  
19,999 to 30,000 (display: 30,000 max.)  
Analog input scaling  
Accuracy  
( 0.2% of FS) 1 digit max.  
Input sampling period 60 ms  
Setting method  
Set digitally using keys on the front panel or by using the RSP input.  
11-segment digital display and individual indicators (7-segments displays also possible)  
Character height: E5AN-H: PV: 15.8 mm, SV: 9.5 mm, MV: 6.8 mm; E5EN-H: PV: 11.8 mm, SV: 8.1 mm, MV: 5.8 mm  
Content of 3-level display: PV/SV/MV, PV/SV/Bank No., or soak time remain  
Number of digits: 5 for PV and SV, 4 for MV  
Indication method  
Supported (number of banks: 8)  
Local SP, alarm settings, PID sets (PID constants, MV upper limit, MV lower limit, etc.)  
Bank switching  
Other functions  
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout detection, 40%  
AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions, control output  
ON/OFF counter, extraction of square root, MV change rate limit, PV/SV status display, logic operations, automatic cooling  
coefficient adjustment  
Ambient operating temperature  
Ambient operating humidity  
Storage temperature  
10 to 55°C (with no condensation or icing), for 3-year warranty: 10 to 50°C  
25% to 85%  
25 to 65°C (with no condensation or icing)  
5
E5AN-H/E5EN-H  
Input Ranges  
Thermocouple/Platinum Resistance Thermometer (Fully Universal Inputs)  
Input  
type  
Platinum resistance  
Thermocouple  
Analog input  
thermometer  
4 to  
0 to  
PL  
II  
1 to  
5 V  
0 to  
5 V  
0 to  
10 V  
20 m 20 m  
Name  
Pt100  
JPt100  
K
J
T
E
L
U
N
R
S
B
W
A
A
2300.0  
2300  
1800.0  
1800  
1700  
1600  
1500  
1400  
1300  
1200  
1100  
1000  
900  
1700.01700.0  
1300.0  
1300.0  
1300.0  
Usable in the following  
ranges by scaling:  
19999 to 32400,  
850.0  
850.0  
850.0  
1999.9 to 3240.0,  
199.99 to 324.00, or  
19.999 to 32.400  
800  
700  
600.0  
600  
500.0  
500.0  
500.0  
500  
400.0  
400.0 400.0  
400.0 400.0  
400  
300  
200.00  
200.00  
200.00  
200.00  
200  
100.0  
100.0  
0.0  
100  
100.0  
0
0.0  
0.0  
0.0  
0.0  
0.0  
100.0  
200.0  
50.00  
20.0 50.00100.0 20.0 50.00  
50.00  
100.0  
200.0199.9  
199.9  
200.0  
200.0199.9  
200.0  
200.0199.9200.0  
Setting  
number  
0
1
2
24  
3
4
5
6
21  
7
8
22  
9
10 23 11 12 13 14 15 16 17 18 19 20 25 26 27 28 29  
Shaded settings are the default settings.  
The applicable standards for the input types are as follows:  
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1  
L: Fe-CuNi, DIN 43710-1985  
JPt100: JIS C 1604-1989, JIS C 1606-1989  
Pt100: JIS C 1604-1997, IEC 751  
U: Cu-CuNi, DIN 43710-1985  
PL II: According to Platinel II electromotive force charts from BASF (previously  
Engelhard)  
W: W5Re/W26Re, ASTM E988-1990  
6
E5AN-H/E5EN-H  
Alarm Outputs  
Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit.  
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.  
Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the  
following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR  
failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function).  
Alarm output operation  
Set value  
Alarm type  
Alarm function OFF  
Description of function  
When alarm value When alarm value  
X is positive  
X is negative  
0
Output OFF  
No alarm  
L
H
X
Set the deviation in the set point by setting the alarm  
upper limit (H) and alarm lower limit (L).  
ON  
OFF  
1
2
3
4
Upper- and lower-limit *1  
Upper-limit  
*2  
SP  
X
Set the upward deviation in the set point by setting  
the alarm value (X).  
ON  
OFF  
ON  
OFF  
SP  
SP  
X
X
ON  
OFF  
ON  
OFF  
Set the downward deviation in the set point by setting  
the alarm value (X).  
Lower-limit  
SP  
SP  
L
H
H
Set the deviation in the set point by setting the alarm  
upper limit (H) and alarm lower limit (L).  
ON  
OFF  
Upper- and lower-limit range *1  
*3  
SP  
L
ON  
OFF  
Upper- and lower-limit with  
standby sequence *1  
A standby sequence is added to the upper- and  
lower-limit alarm (1). *7  
5
*4  
SP  
*5  
X
X
A standby sequence is added to the upper-limit alarm  
(2). *7  
ON  
OFF  
ON  
OFF  
6
Upper-limit with standby sequence  
Lower-limit with standby sequence  
Absolute-value upper-limit  
SP  
SP  
X
X
ON  
OFF  
A standby sequence is added to the lower-limit alarm  
(3). *7  
ON  
OFF  
7
SP  
X
SP  
X
ON  
OFF  
The alarm will turn ON if the process value is larger  
than the alarm value (X) regardless of the set point.  
ON  
OFF  
8
0
0
0
0
0
0
0
0
X
X
X
X
X
X
ON  
OFF  
ON  
OFF  
The alarm will turn ON if the process value is smaller  
than the alarm value (X) regardless of the set point.  
9
Absolute-value lower-limit  
Absolute-value upper-limit with  
standby sequence  
ON  
OFF  
A standby sequence is added to the absolute-value  
upper-limit alarm (8). *7  
ON  
OFF  
10  
11  
Absolute-value lower-limit with  
standby sequence  
A standby sequence is added to the absolute-value  
lower-limit alarm (9). *7  
ON  
OFF  
ON  
OFF  
*8  
*9  
12  
13  
LBA (alarm 1 type only)  
PV change rate alarm  
---  
---  
The alarm turns ON when the remote SP (RSP) is  
larger than the alarm value (X). This alarm functions  
in both Local SP and Remote SP Modes.  
X
X
X
X
ON  
OFF  
ON  
OFF  
14  
15  
RSP absolute value upper limit *6  
RSP absolute value lower limit *6  
0
0
0
0
The alarm turns ON when the remote SP (RSP) is  
smaller than the alarm value (X). This alarm  
functions in both Local SP and Remote SP Modes.  
ON  
OFF  
ON  
OFF  
*1. With set values 1, 4 and 5, the upper and lower limit values can  
be set independently for each alarm type, and are expressed as  
“L” and “H.”  
*5. Set value: 5, Upper- and lower-limit with standby sequence  
Always OFF when the upper-limit and lower-limit hysteresis  
overlaps.  
*2. Set value: 1, Upper- and lower-limit alarm  
*6. Displayed when there is a remote SP input.  
*7. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature  
Controllers User's Manual Basic Type (Cat. No. H156) for  
information on the operation of the standby sequence.  
*8. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature  
Controllers User's Manual Basic Type (Cat. No. H156) for  
information on the loop burnout alarm (LBA).  
Case 2  
Case 1  
Case 3 (Always ON)  
H < 0, L < 0  
H
SP  
L
SP L  
H
L
H SP  
H < 0, L > 0  
H⏐ ≥ ⏐L⏐  
H < 0, L > 0  
H< L⏐  
H > 0, L < 0  
H> L⏐  
H
L SP  
H > 0, L < 0  
*9. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature  
Controllers User's Manual Basic Type (Cat. No. H156) for  
information on the PV change rate alarm.  
SPH  
L
H⏐ ≤ ⏐L⏐  
*3. Set value: 4, Upper- and lower-limit range  
Case 2  
Case 1  
Case 3 (Always ON)  
H < 0, L < 0  
H
SP  
L
L
H
SP  
SP L  
H
H < 0, L > 0  
H⏐ ≥ ⏐L⏐  
H < 0, L > 0  
H< L⏐  
H > 0, L < 0  
H> L⏐  
H
L SP  
H > 0, L < 0  
H⏐ ≤ ⏐L⏐  
SPH  
L
*4. Set value: 5, Upper- and lower-limit with standby sequence  
For Upper- and Lower-Limit Alarm Described Above  
Case 1 and 2  
Always OFF when the upper-limit and lower-limit hysteresis  
overlaps.  
Case 3: Always OFF  
7
E5AN-H/E5EN-H  
Characteristics  
Thermocouple: ( 0.1% of indicated value or 1°C, whichever is greater) 1 digit max. *1  
Platinum resistance thermometer: ( 0.1% of indicated value or 0.5°C, whichever is greater) 1 digit max.  
Analog input: 0.1% FS 1 digit max.  
CT input: 5% FS 1 digit max.  
Indication accuracy  
Potentiometer input: 5% FS 1 digit max.  
Transfer output accuracy 0.3% FS max.  
Influence of temperature Thermocouple input (R, S, B, W, PL II): ( 1% of PV or 10°C, whichever is greater) 1 digit max.  
*2  
Other thermocouple input: ( 1% of PV or 4°C, whichever is greater) 1 digit max. *3  
Platinum resistance thermometer: ( 1% of PV or 2°C, whichever is greater) 1 digit max.  
Analog input: ( 1%FS) 1 digit max.  
Influence of voltage *2  
Input sampling period  
60 ms  
Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1°C or °F)  
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)  
Hysteresis  
Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1°C or °F)  
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)  
Proportional band (P)  
Integral time (I)  
0.0 to 3240.0 s (in units of 0.1 s)  
Derivative time (D)  
Control period  
0.0 to 3240.0 s (in units of 0.1 s)  
0.5, 1 to 99 s (in units of 1 s)  
Manual reset value  
Alarm setting range  
0.0 to 100.0% (in units of 0.1%)  
19999 to 32400 (decimal point position depends on input type)  
Affect of signal source  
resistance  
Thermocouple: 0.1°C/Ω max. (100 Ω max.)  
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)  
Insulation resistance  
20 MΩ min. (at 500 VDC)  
Dielectric strength  
2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)  
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions  
Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions  
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions  
Vibration  
resistance  
Shock  
resistance  
Destruction 300 m/s2, 3 times each in X, Y, and Z directions  
E5AN-H  
E5EN-H  
Controller: Approx. 310 g, Mounting Bracket: Approx. 100 g  
Controller: Approx. 260 g, Mounting Bracket: Approx. 100 g  
Front panel: IP66, Rear case: IP20, Terminals: IP00  
Non-volatile memory (number of writes: 1,000,000 times)  
CX-Thermo version 4.0 or higher  
Weight  
Degree of protection  
Memory protection  
Setup Tool  
Provided on the bottom of the E5AN-H and E5EN-H.  
An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5AN-H and E5EN-H.  
Provided on the front of the E5AN-H and E5EN-H. An E58-CIFIR USB-infrared Conversion Cable is required to  
connect the computer to the E5AN-H or E5EN-H. *4  
Setup Tool port  
Approved  
UL 61010-1, CSA C22.2 No. 1010-1  
standards  
Standards  
Conformed  
EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II, Lloyd's standards *5  
standards  
EMI:  
EN 61326  
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A  
Noise Terminal Voltage:  
EMS:  
ESD Immunity:  
Electromagnetic Field Immunity:  
Burst Noise Immunity:  
Conducted Disturbance Immunity:  
Surge Immunity:  
EN 55011 Group 1, class A  
EN 61326  
EN 61000-4-2  
EN 61000-4-3  
EN 61000-4-4  
EN 61000-4-6  
EN 61000-4-5  
EN 61000-4-8  
EN 61000-4-11  
EMC  
Power Frequency Magnetic Field Immunity:  
Voltage Dip/Interrupting Immunity:  
*1. The indication accuracy of K thermocouples in the 200 to 1300°C range, T and N thermocouples at a temperature of 100°C max., and U  
and L thermocouples at any temperatures is 2°C 1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max.  
is not specified. The indication accuracy of B thermocouples in the 400 to 800°C range is 3°C max. The indication accuracy of the R and S  
thermocouples at a temperature of 200°C max. is 3°C 1 digit max. The indication accuracy of W thermocouples is 0.3% of PV or 3°C,  
whichever is greater, 1 digit max.  
The indication accuracy of PL II thermocouples is 0.3% of PV or 2°C, whichever is greater, 1 digit max.  
*2. Ambient temperature: 10°C to 23°C to 55°C, Voltage range: 15% to 10% of rated voltage  
*3. K thermocouple at 100°C max.: 10°C max.  
*4. External communications (RS-232C, RS-485, or RS-422) and cable communications for the Setup Tool can be used at the same time.  
*5. Refer to information on maritime standards in Safety Precautions for E5@N/E5@N-H for compliance with Lloyd's Standards.  
8
E5AN-H/E5EN-H  
USB-Serial Conversion Cable  
Current Transformer (Order Separately)  
Ratings  
Applicable OS  
Windows 2000, XP, or Vista  
Applicable software  
CX-Thermo version 4 or higher  
Dielectric strength  
1,000 VAC for 1 min  
E5AN/E5EN/E5CN/E5CN-U/  
E5AN-H/E5EN-H/E5CN-H/E5GN  
Vibration resistance  
50 Hz, 98 m/s2  
Applicable models  
E54-CT1: Approx. 11.5 g,  
E54-CT3: Approx. 50 g  
Weight  
USB interface standard  
DTE speed  
Conforms to USB Specification 1.1.  
38400 bps  
Armatures (2)  
Plugs (2)  
Accessories (E54-CT3 only)  
Computer: USB (type A plug)  
Temperature Controller: Setup  
Tool port (on bottom of Controller)  
Connector specifications  
USB-Infrared Conversion Cable  
Applicable OS  
Bus power (Supplied from USB  
host controller.)  
Windows 2000, XP, or Vista  
Power supply  
Applicable software  
Applicable models  
USB interface standard  
DTE speed  
CX-Thermo version 4.0 or higher  
E5AN-H/E5EN-H  
Power supply voltage  
Current consumption  
5 VDC  
70 mA  
Conforms to USB Specification 1.1.  
38400 bps  
Ambient operating  
temperature  
0 to 55°C (with no condensation or  
icing)  
Computer: USB (type A plug)  
Temperature Controller: Infrared  
port (on front of Controller)  
Ambient operating humidity 10% to 80%  
Connector specifications  
20 to 60°C (with no condensation  
or icing)  
Storage temperature  
Bus power (Supplied from USB  
host controller.)  
Power supply  
Storage humidity  
Altitude  
10% to 80%  
2,000 m max.  
Approx. 100 g  
Power supply voltage  
Current consumption  
5 VDC  
80 mA  
Weight  
Note: A driver must be installed in the personal computer. Refer to  
installation information in the operation manual for the  
Conversion Cable.  
Ambient operating  
temperature  
0 to 55°C (with no condensation or  
icing)  
Ambient operating humidity 10% to 80%  
Communications Specifications  
Transmission line RS-485, RS-422: Multipoint  
connection method RS-232C: Point-to-point  
20 to 60°C (with no condensation  
Storage temperature  
or icing)  
Storage humidity  
Altitude  
10% to 80%  
2,000 m max.  
RS-485 (two-wire, half duplex)  
Communications  
RS-422 (four-wire, half duplex) or RS-232C  
Approx. 130 g (with mounting  
adaptor)  
Weight  
Synchronization  
Start-stop synchronization  
method  
Note: A driver must be installed in the personal computer. Refer to  
installation information in the operation manual for the  
Conversion Cable.  
Protocol  
CompoWay/F, SYSWAY, or Modbus  
1200, 2400, 4800, 9600, 19200, 38400, or  
57600 bps  
Baud rate  
Heater Burnout Alarms, SSR Failure  
Alarms, and Heater Overcurrent Alarms  
ASCII (CompoWay/F, SYSWAY)  
RTU (Modbus)  
Transmission code  
Models with detection for single-phase  
heaters: One input  
Models with detection for single-phase  
or three-phase heaters: Two inputs  
Data bit length *  
Stop bit length *  
7 or 8 bits  
1 or 2 bits  
CT input  
(for heater current  
detection)  
Vertical parity (none, even, odd)  
Frame check sequence (FCS) with SYSWAY  
Block check character (BCC) with  
CompoWay/F or CRC-16 Modbus  
Maximum heater current 50 A AC  
Error detection  
Input current indication  
5% FS 1 digit max.  
accuracy  
Flow control  
Interface  
None  
Heater burnout alarm  
setting range *1  
0.1 to 49.9 A (in units of 0.1 A)  
Minimum detection ON time: 100 ms  
RS-485, RS-422, or RS-232C  
None  
Retry function  
SSR failure alarm setting 0.1 to 49.9 A (in units of 0.1 A)  
range *2 Minimum detection OFF time: 100 ms  
Communications  
buffer  
217 bytes  
Heater overcurrent alarm 0.1 to 49.9 A (in units of 0.1 A)  
setting range *3 Minimum detection ON time: 100 ms  
Communications  
0 to 99 ms  
response wait time Default: 20 ms  
* The baud rate, data bit length, stop bit length, and vertical parity can  
be individually set using the Communications Setting Level.  
*1. For heater burnout alarms, the heater current will be measured  
when the control output is ON, and the output assigned to the  
alarm 1 function will turn ON if the heater current is lower than the  
set value (i.e., heater burnout detection current value).  
*2. For SSR failure alarms, the heater current will be measured when  
the control output is OFF, and the output assigned to the alarm 1  
function will turn ON if the heater current is higher than the set  
value (i.e., SSR failure detection current value).  
*3. For heater overcurrent alarms, the heater current will be  
measured when the control output is ON, and the output assigned  
to the alarm 1 function will turn ON if the heater current is higher  
than the set value (i.e., heater overcurrent detection current  
value).  
9
E5AN-H/E5EN-H  
Electrical Life Expectancy Curve for  
Relays (Reference Values)  
SSR Outputs (OUT1/OUT2) Ratings  
Rated load voltage: 75 to 250 VAC  
Rated load current: 1 A (resistive load)  
500  
Note: 1. The load current must be within the derating curve.  
2. There is no zero-cross function.  
300  
E5AN-H/E5EN-H  
Derating Curve for SSR Outputs (Reference Values)  
100  
250 VAC, 30 VDC  
(resistive load)  
cosφ = 1  
1.5  
50  
30  
1.25  
Condition B  
10  
1
5
3
0.75  
0.5  
1
0
1
2
3
4
5
6
Condition A  
Switching current (A)  
0.25  
0
10  
0
10  
20  
30  
40 45 50 55 60  
Ambient temperature (°C)  
Condition A: SSR outputs 100% ON  
Condition B: SSR outputs 50% ON with 2-s control cycle  
10  
E5AN-H/E5EN-H  
External Connections  
Control output 1 and control output 2 are functionally isolated from the internal circuits.  
Controllers  
Option Units  
The Temperature Controller is set  
for a K-type thermocouple (input  
type = 5) by default. An input error  
(s.err) will occur if the input type  
setting does not agree with the  
temperature sensor. Check the  
input type.  
Communications  
E53-EN01  
RS-232C  
E53-EN02  
RS-422  
E53-EN03  
RS-485  
E53-AKB  
Event Inputs  
11  
11  
11  
11  
SD  
RDB  
RDA  
SG  
B (+)  
EV2  
12  
13  
21  
22  
12  
13  
21  
22  
12  
13  
21  
22  
12  
13  
21  
22  
RD  
A ()  
EV1  
SG  
DO NOT USE  
B (+)  
DO NOT USE  
SDB  
SDA  
100 to 240 VAC  
24 VAC/VDC (no polarity)  
A ()  
DO NOT USE  
Event Inputs  
1
2
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
Input power  
supply  
EV2  
EV1  
3
Potentiometer  
Control output 1  
Control output 2  
Auxiliary output 2  
Auxiliary output 1  
CT2  
CT1  
CT2  
O
W
C
4
14  
15  
Auxiliary output 3  
Auxiliary output 3  
5
Relay output  
SPDT, 250 VAC, 3 A  
(resistive load)  
16  
6
DO NOT DO NOT  
DO NOT  
USE  
7
USE  
USE  
A heater burnout alarm, SSR  
failure, heater overcurrent  
alarm, input alarm, or Remote  
SP Input Error is sent to the  
output to which the alarm 1  
function is assigned.  
A
DO NOT  
USE  
DO NOT  
USE  
8
V
mA  
B
B
9
DO NOT  
USE  
DO NOT  
USE  
10  
Event input/  
Transfer output/  
Remote SP  
Models with Position-  
proportional Control  
Control Output Unit  
SSR Outputs  
Control outputs 1, 2  
Control Output Unit  
Control outputs 1, 2  
Refer to page 4  
1
1
1
21  
22  
23  
Input power  
Input power  
supply  
Input power  
supply  
supply  
2
2
3
2
3
SSR Outputs  
75 to 250 VAC, 1 A  
(resistive load)  
+
3
EV3  
EV4  
Output unit  
SSR  
SSR  
Open  
Models with Position-  
proportional Control  
Relay output  
250 VAC, 1 A  
(including inrush  
4
4
4
24  
25  
26  
27  
28  
29  
30  
+
5
5
5
Output unit  
Closed  
Auxiliary output 2  
Auxiliary output 1  
6
6
6
DO NOT USE  
current)  
+
7
Auxiliary output 2  
8
7
7
4 to 20 mA DC  
(Load: 600 Ω max.)  
Auxiliary output 2  
Transfer output  
Auxiliary outputs 1, 2, 3  
8
8
Relay output  
SPST-NO,  
250 VAC, 3 A  
(resistive load)  
+
9
9
9
4 to 20 mA DC  
Auxiliary output 1  
Auxiliary output 1  
Remote SP input  
10  
10  
10  
Note: Wire all voltage input terminals correctly. The Controller may fail if voltage input terminals are wired incorrectly.  
11  
E5AN-H/E5EN-H  
Nomenclature  
E5AN-H  
E5EN-H  
Temperature unit  
Operation indicators  
Temperature unit  
SUB1 SUB2  
HA SUB3  
SUB1  
SUB2  
SUB3  
PV  
PV  
No.1 display  
Operation indicators  
No.1 display  
HA  
SV  
SV  
No.2 display  
No.3 display  
No.2 display  
RSP  
OUT1 RSP STOP  
OUT2  
OUT1 STOP  
MV  
MV  
No.3 display  
Operation indicators  
OUT2 CMW MANU  
CMW MANU  
Up Key  
Mode Key  
Level Key  
Programmable  
Function Key/  
Up Key  
Programmable  
Function Key/  
Auto/Manual Key  
Auto/Manual Key  
Ir  
Ir  
E5EN-H  
E5AN-H  
Down Key  
Down Key  
Level Key  
Mode Key  
Dimensions  
(Unit: mm)  
E5AN-H  
Mounted Separately  
Group Mounted *  
(96 × number of units − 3.5)+1.0  
92+0.8  
0
0
92+0.8  
0
Group mounting does not  
allow waterproofing.  
120 min.  
6
Recommended panel thickness is 1 to  
8 mm.  
79.2  
2
Group mounting is not possible in the  
vertical direction. (Maintain the specified  
mounting space between Controllers.)  
To mount the Controller so that it is  
waterproof, insert the waterproof  
packing onto the Controller.  
When two or more Controllers are  
mounted, make sure that the  
surrounding temperature does not  
exceed the allowable operating  
temperature specified in the  
specifications.  
92+0.8  
0
96 × 96  
112  
91  
* Group mounting is not possible if an SSR output is used for  
control output 1 or 2 and the E53-C3N or E53-C3DN Output Unit  
is used. For these combinations, maintain the following mounting  
space between Controllers.  
Terminal Cover  
(E53-COV16)  
(Accessory)  
Waterproof  
Packing  
Mounting Bracket  
(Accessory)  
110 min.  
92+0.8  
0
(Accessory)  
Crimp terminal size: M3.5  
92+0.8  
0
120 min.  
12  
E5AN-H/E5EN-H  
E5EN-H  
Mounted Separately  
Group Mounted *  
(48 × number of units − 2.5)+1.0  
0
45+0.6  
0
92+0.8  
0
Group mounting does not  
allow waterproofing.  
120 min.  
Recommended panel thickness is 1 to 8 mm.  
Group mounting is not possible in the vertical direction.  
(Maintain the specified mounting space between  
Controllers.)  
92+0.8  
0
6
When two or more Controllers are mounted, make  
sure that the surrounding temperature does not  
exceed the allowable operating temperature specified  
in the specifications.  
79.2  
48  
2
* Group mounting is not possible if an SSR output is used for control  
output 1 or 2 and the E53-C3N or E53-C3DN Output Unit is used.  
For these combinations, maintain the following mounting space  
between Controllers.  
112  
96  
91  
60 min.  
45+0.6  
0
92+0.8  
0
Terminal Cover  
(E53-COV16)  
(Accessory)  
Waterproof  
Packing  
(Accessory)  
Mounting Bracket  
(Accessory)  
Crimp terminal size: M3.5  
120 min.  
13  
E5AN-H/E5EN-H  
Accessories (Order Separately)  
USB-Infrared Conversion Cable  
E58-CIFIR  
USB-Infrared Conversion Cable  
(2,000)  
54  
35.8  
4.6 dia.  
USB connector (type A plug)  
LED indicator: RD LED indicator: SD  
17.8  
With Mounting Adapter Connected  
Mounting Adapter  
39  
16  
18.5  
Mounting Adapter  
(Accessory)  
99.2  
23.1  
21.8  
(75)  
USB-Serial Conversion Cable  
E58-CIFQ1  
(2,100)  
LED indicator: SD  
1,765  
250  
USB connector (type A plug)  
Serial connector  
LED indicator: RD  
Terminal Covers  
E53-COV16 (Six Covers provided.)  
1.2 3.2  
10  
44.8  
14  
E5AN-H/E5EN-H  
Waterproof Packing  
Y92S-P4 (for DIN 96 × 96)  
Order the Waterproof Packing separately if it becomes lost or  
damaged.  
Y92S-P5 (for DIN 48 × 96)  
The Waterproof Packing can be used to achieve an IP66 degree of  
protection.  
(Deterioration, shrinking, or hardening of the waterproof packing may  
occur depending on the operating environment. Therefore, periodic  
replacement is recommended to ensure the level of waterproofing  
specified in IP66. The time for periodic replacement depends on the  
operating environment. Be sure to confirm this point at your site.  
Consider one year a rough standard. OMRON shall not be liable for  
the level of water resistance if the customer does not perform periodic  
replacement.)  
The Waterproof Packing does not need to be attached if a waterproof  
structure is not required.  
Current Transformers  
E54-CT1  
E54-CT1  
21  
2.8  
Thru-current (Io) vs. Output Voltage  
(Eo) (Reference Values)  
Maximum continuous heater current: 50 A (50/60 Hz)  
Number of windings: 400 2  
15  
5.8 dia.  
7.5  
Winding resistance: 18 2 Ω  
25  
3
100 V  
10.5  
50 Hz  
10  
40  
Distortion  
factor 10%  
1 kΩ  
Two, 3.5 dia.  
1
3%  
10  
1%  
100 mV  
30  
100 Ω  
10  
1
E54-CT3  
RL = 10 Ω  
2.36 dia.  
30  
12 dia.  
100 µV  
9
10  
1
10  
100 mA  
1
10  
100 1,000 A  
40 × 40  
Thru-current (Io) A (r.m.s.)  
E54-CT3  
Thru-current (Io) vs. Output Voltage  
(Eo) (Reference Values)  
Two, M3 (depth 4)  
Maximum continuous heater current: 120 A (50/60 Hz)  
(Maximum continuous heater current for an OMRON  
Temperature Controller is 50 A.)  
15  
30  
Number of windings: 400 2  
Winding resistance: 8 0.8 Ω  
E54-CT3 Accessory  
Armature  
100 V  
50 Hz  
Distor-  
Connection Example  
tion  
10  
factor  
10%  
3%  
1 kΩ  
Armature  
500 Ω  
Plug  
Approx. 3 dia.  
1%  
1
100 mV  
10  
Lead  
100 Ω  
50 Ω  
18  
RL = 10 Ω  
Plug  
1
100 µV  
Approx. 6 dia.  
10  
1
10  
100 mA  
1
10  
100 1,000 A  
(22)  
Thru-current (Io) A (r.m.s.)  
15  
Read and Understand This Catalog  
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or  
comments.  
Warranty and Limitations of Liability  
WARRANTY  
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)  
from date of sale by OMRON.  
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR  
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS  
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER  
WARRANTIES, EXPRESS OR IMPLIED.  
LIMITATIONS OF LIABILITY  
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS  
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT  
LIABILITY.  
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.  
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS  
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT  
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.  
Application Considerations  
SUITABILITY FOR USE  
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's  
application or use of the products.  
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the  
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,  
machine, system, or other application or use.  
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible  
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:  
·
·
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.  
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,  
safety equipment, and installations subject to separate industry or government regulations.  
·
Systems, machines, and equipment that could present a risk to life or property.  
Please know and observe all prohibitions of use applicable to the products.  
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE  
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND  
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.  
PROGRAMMABLE PRODUCTS  
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.  
Disclaimers  
CHANGE IN SPECIFICATIONS  
Product specifications and accessories may be changed at any time based on improvements and other reasons.  
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.  
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or  
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual  
specifications of purchased products.  
DIMENSIONS AND WEIGHTS  
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.  
PERFORMANCE DATA  
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the  
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON  
Warranty and Limitations of Liability.  
ERRORS AND OMISSIONS  
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,  
typographical, or proofreading errors, or omissions.  
2009.11  
In the interest of product improvement, specifications are subject to change without notice.  
OMRON Corporation  
Industrial Automation Company  
http://www.ia.omron.com/  
(c)Copyright OMRON Corporation 2009 All Right Reserved.  

相关型号:

E5AN-HPRR2BM-500

Advanced Digital Temperature Controller
OMRON

E5AN-HPRR2BMD-500

Advanced Digital Temperature Controller
OMRON

E5AN-HSS2HBM-500

Advanced Digital Temperature Controller
OMRON

E5AN-HSS2HBMD-500

Advanced Digital Temperature Controller
OMRON

E5AN-HSS2HHBFM-500

Advanced Digital Temperature Controller
OMRON

E5AN-HSS2HHBFMD-500

Advanced Digital Temperature Controller
OMRON

E5AN-HSS3BFM-500

Advanced Digital Temperature Controller
OMRON

E5AN-HSS3BFMD-500

Advanced Digital Temperature Controller
OMRON

E5AN-Q3HHMT-500-N

Basic-type Digital Temperature Controller
OMRON

E5AN-Q3HHMTD-500-N

Basic-type Digital Temperature Controller
OMRON

E5AN-Q3HML-500-N

Basic-type Digital Temperature Controller
OMRON

E5AN-Q3HMP-500

Digital Temperature Controllers
OMRON