Basic-type Digital Temperature Controller  
(48 x 48 mm)  
E5CN/E5CN-U  
CSM_E5CN_E5CN-U_DS_E_4_2  
New 48 x 48-mm Basic Temperature  
Controller with Enhanced Functions and  
Performance. Improved Indication  
Accuracy and Preventive Maintenance  
Function.  
• Indication Accuracy  
48 × 48-mm  
48 × 48-mm  
Thermocouple input: ±±.3% of PV (previous models: ±±.5%)  
Pt input: ±±.2% of PV (previous models: ±±.5%)  
Analog input: ±±.2% FS (previous models: ±±.5%)  
• New E5CN-U Models (Plug-in Models) with analog inputs and  
current outputs.  
E5CN  
E5CN-U  
Refer to Safety Precautions for E5@N/E5@N-H.  
• A PV/SV-status display function can be set to automatically  
alternate between displaying the status of the Temperature  
Controller (auto/manual, RUN/STOP, and alarms) and the PV or SV.  
• Preventive maintenance for relays in the Temperature Controller  
using a Control Output ON/OFF Counter.  
Refer to Operation for E5@N/E5@N-H for operating  
procedures.  
Main I/O Functions  
Event Inputs  
E5CN  
None  
• Two  
4-digit Display  
2-level Display: PV and SV  
Sensor Inputs  
• Auto/manual switching  
• Universal thermocouple/Pt inputs  
(Models with temperature inputs)  
• Analog current/voltage inputs  
(Models with analog inputs)  
Auxiliary Outputs  
None  
• Temperature Controller status display  
• Simple program function  
• One  
• Control output ON/OFF count alarm  
• PV change rate alarm  
Control Output 2  
None  
• Two  
• Models also available with RS-485  
communications  
Voltage output  
(for driving SSR)  
Indication Accuracy  
• Thermocouple input: ±.3% of PV  
• Pt input: ±.2% of PV  
Control Output 1  
• Relay output  
• Analog input: ±.2% FS  
Voltage output (for driving SSR)  
• Current output  
Sampling Period  
• 25± ms  
• Long-life relay output (hybrid)  
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions  
and other information required for operation before attempting to use the product.  
E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156)  
E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers Communications Manual Basic Type (Cat. No. H158)  
1
E5CN/E5CN-U  
Lineup  
0 or 2 auxiliary outputs  
1 control output  
2 control outputs  
1 control output  
2 control outputs  
1 control output  
1 control output  
Temperature input  
Analog input  
2 auxiliary outputs  
Terminal block  
0 or 2 auxiliary outputs  
E5CN  
2 auxiliary outputs  
Basic Type  
0, 1, or 2 auxiliary  
outputs  
Temperature input  
Analog input  
Plug-in  
0, 1, or 2 auxiliary  
outputs  
Note: Models with one control output and one or two auxiliary outputs and models with two control outputs can be used for heating/cooling control.  
Model Number Structure  
Model Number Legend  
Controllers  
Option Units  
E5CN-@@M@@-@-500  
E53-CN@@@  
4
2 3  
1 2 3 4 5  
6
7
1
1. Control Output 1  
1. Applicable Controller  
R: Relay output  
CN: E5CN or E5CN-H  
Q: Voltage output (for driving SSR)  
C: Current output  
Y: Long-life relay output (hybrid) *1  
2. Function 1  
Blank: None  
Q: Control output 2 (voltage for driving SSR)  
P: Power supply for sensor  
2. Auxiliary Outputs *2  
Blank: None  
3. Function 2  
2: Two outputs  
Blank: None  
3. Option  
H: Heater burnout/SSR failure/Heater overcurrent detection (CT1)  
M: Option Unit can be mounted.  
HH: Heater burnout/SSR failure/Heater overcurrent detection  
(CT2)  
B: Two event inputs  
03: RS-485 communications  
H03: Heater burnout/SSR failure/Heater overcurrent detection  
(CT1) + RS-485 communications  
HB: Heater burnout/SSR failure/Heater overcurrent detection  
(CT1) + Two event inputs  
HH03: Heater burnout/SSR failure/Heater overcurrent detection  
(CT2) + RS-485 communications  
4. Input Type  
T: Universal thermocouple/platinum resistance thermometer  
L: Analog current/voltage input  
5. Power Supply Voltage  
Blank: 100 to 240 VAC  
D: 24 VAC/VDC  
6. Case Color  
Blank: Black  
W: Silver  
4. Version  
N2: Applicable only to models released after January 2008  
7. Terminal Cover  
-500: With terminal cover  
Note: Not all combinations of function 1 and function 2 specifications are possible for Option Units (E53-@@@@).  
*1. Always connect an AC load to a long-life relay output. The output will not turn OFF if a DC load is connected because a triac is used for  
switching the circuit. For details, check the conditions in Ratings.  
*2. Auxiliary outputs are contact outputs that can be used to output alarms or results of logic operations.  
2
E5CN/E5CN-U  
Ordering Information  
Controllers with Terminal Blocks  
Power supply  
Size  
Case color  
Input type  
Auxiliary outputs  
Control output 1  
Relay output  
Model  
voltage  
E5CN-RMT-500  
None  
Voltage output (for driving SSR)  
Current output  
E5CN-QMT-500  
E5CN-CMT-500  
Thermocouple or  
Resistance  
thermometer  
100 to 240 VAC  
Relay output  
E5CN-R2MT-500  
E5CN-Q2MT-500  
E5CN-C2MT-500  
E5CN-Y2MT-500  
E5CN-RMTD-500  
E5CN-QMTD-500  
E5CN-CMTD-500  
E5CN-R2MTD-500  
E5CN-Q2MTD-500  
E5CN-C2MTD-500  
E5CN-RML-500  
Voltage output (for driving SSR)  
Current output  
2
Long-life relay output (hybrid)  
Relay output  
None  
2
Voltage output (for driving SSR)  
Current output  
Thermocouple or  
Resistance  
thermometer  
24 VAC/VDC  
Relay output  
Black  
Voltage output (for driving SSR)  
Current output  
Relay output  
None  
Voltage output (for driving SSR)  
Current output  
E5CN-QML-500  
E5CN-CML-500  
1/16 DIN  
48 × 48 × 78  
(W × H × D)  
Analog  
(current/voltage)  
100 to 240 VAC  
24 VAC/VDC  
Relay output  
E5CN-R2ML-500  
E5CN-Q2ML-500  
E5CN-C2ML-500  
E5CN-Y2ML-500  
E5CN-R2MLD-500  
E5CN-Q2MLD-500  
E5CN-C2MLD-500  
E5CN-RMT-W-500  
E5CN-QMT-W-500  
E5CN-CMT-W-500  
E5CN-R2MT-W-500  
E5CN-Q2MT-W-500  
E5CN-C2MT-W-500  
E5CN-Y2MT-W-500  
E5CN-R2MTD-W-500  
E5CN-Q2MTD-W-500  
E5CN-C2MTD-W-500  
Voltage output (for driving SSR)  
Current output  
2
Long-life relay output (hybrid)  
Relay output  
Analog  
(current/voltage)  
2
Voltage output (for driving SSR)  
Current output  
Relay output  
None  
Voltage output (for driving SSR)  
Current output  
100 to 240 VAC  
24 VAC/VDC  
Relay output  
Thermocouple or  
Resistance  
thermometer  
Voltage output (for driving SSR)  
Current output  
Silver  
2
2
Long-life relay output (hybrid)  
Relay output  
Voltage output (for driving SSR)  
Current output  
Note: Models with analog inputs do not have temperature unit indicators.  
Option Units  
One of the following Option Units can be mounted to provide the E5CN with additional functions.  
Functions  
Model  
Communications  
RS-485  
3-phase heater burnout/SSR failure/  
Heater overcurrent detection  
E53-CNHH03N2  
Heater burnout/SSR failure/Heater  
overcurrent detection  
Event inputs  
Event inputs  
E53-CNHBN2  
E53-CNQ03N2  
Communications  
RS-485  
Control output 2  
(Voltage for driving SSR)  
External power supply for  
ES1B  
E53-CNPBN2  
E53-CNPHN2  
E53-CNP03N2  
E53-CNH03N2  
Heater burnout/SSR failure/Heater  
overcurrent detection  
External power supply for  
ES1B  
Communications  
RS-485  
External power supply for  
ES1B  
Communications  
RS-485  
Heater burnout/SSR failure/Heater  
overcurrent detection  
Communications  
RS-485  
E53-CN03N2  
E53-CNBN2  
E53-CNQHN2  
Event inputs  
Event inputs  
Heater burnout/SSR failure/Heater  
overcurrent detection  
Control output 2  
(Voltage for driving SSR)  
3-phase heater burnout/SSR failure/  
Heater overcurrent detection  
Control output 2  
(Voltage for driving SSR)  
E53-CNQHHN2  
E53-CNQBN2  
Control output 2  
(Voltage for driving SSR)  
Note: Option Units cannot be used for plug-in models.  
These Option Units are applicable only to models released after January 2008.  
3
E5CN/E5CN-U  
Model Number Structure  
Model Number Legend (Plug-in-type Controllers)  
E5CN-@@@U  
1 2 3 4  
1. Output Type  
3. Input Type  
R: Relay output  
T: Universal thermocouple/platinum resistance thermometer  
Q: Voltage output (for driving SSR)  
C: Current output  
2. Number of Alarms  
Blank: No alarm  
L: Analog Input  
4. Plug-in type  
U: Plug-in type  
1: One alarm  
2: Two alarms  
Ordering Information  
Plug-in-type Controllers  
Power supply  
Size  
Case color  
Input type  
Auxiliary outputs  
Control output 1  
Relay output  
Voltage output (for driving SSR) E5CN-QTU  
Model  
voltage  
E5CN-RTU  
None  
Current output  
Relay output  
E5CN-CTU  
E5CN-R1TU  
Thermocouple or  
resistance  
thermometer  
1
Voltage output (for driving SSR) E5CN-Q1TU  
Current output  
Relay output  
E5CN-C1TU  
E5CN-R2TU  
100 to 240 VAC  
2
Voltage output (for driving SSR) E5CN-Q2TU  
Current output  
Relay output  
E5CN-C2TU  
E5CN-R1LU  
1
Voltage output (for driving SSR) E5CN-Q1LU  
Current output  
Relay output  
E5CN-C1LU  
E5CN-R2LU  
Analog  
(current/voltage)  
1/16 DIN  
Black  
2
Voltage output (for driving SSR) E5CN-Q2LU  
Current output  
Relay output  
E5CN-C2LU  
E5CN-RTDU  
None  
Voltage output (for driving SSR) E5CN-QTDU  
Current output  
Relay output  
E5CN-CTDU  
E5CN-R1TDU  
Thermocouple or  
resistance  
thermometer  
24 VAC/VDC  
1
2
Voltage output (for driving SSR) E5CN-Q1TDU  
Current output  
Relay output  
E5CN-C1TDU  
E5CN-R2TDU  
Voltage output (for driving SSR) E5CN-Q2TDU  
Current output E5CN-C2TDU  
Note: Models with analog inputs do not have temperature unit indicators.  
4
E5CN/E5CN-U  
Accessories (Order Separately)  
USB-Serial Conversion Cable  
Adapter  
Model  
Connectable models  
Terminal block models  
Model  
E58-CIFQ1  
Y92F-45  
Note: Use this Adapter when the panel has been previously prepared  
for the E5B@.  
Terminal Cover  
Connectable models  
Model  
Sockets (for Plug-in Models)  
Terminal block models  
E53-COV17  
Type  
Front-connecting Socket  
Model  
Note: The Terminal Cover comes with the E5CN-@@@-500 models.  
P2CF-11  
P2CF-11-E  
P3GA-11  
Waterproof Packing  
Front-connecting Socket with Finger Protection  
Back-connecting Socket  
Model  
Terminal Cover for Back-connecting socket with  
Finger Protection  
Y92S-29  
Y92A-48G  
Note: The Waterproof Packing is included with the Controller only for  
models with terminal blocks.  
Front cover  
Current Transformers (CTs)  
Type  
Hard Front Cover  
Model  
Hole diameter  
5.8 dia.  
Model  
Y92A-48B  
Y92A-48D  
E54-CT1  
E54-CT3  
Soft Front Cover  
12.0 dia.  
CX-Thermo Support Software  
Model  
EST2-2C-MV4  
5
E5CN/E5CN-U  
Specifications  
Ratings  
No D in model number: 100 to 240 VAC, 50/60 Hz  
D in model number: 24 VAC, 50/60 Hz; 24 VDC  
Power supply voltage  
Operating voltage range  
85% to 110% of rated supply voltage  
100 to 240 VAC: 7.5 VA (max.) (E5CN-R2T at 100 VAC: 3.0 VA)  
24 VAC/VDC: 5 VA/3 W (max.) (E5CN-R2TD at 24 VAC: 2.7 VA)  
E5CN  
Power  
consump-  
tion  
100 to 240 VAC: 6 VA (max.)  
24 VAC/VDC: 3 VA/2 W (max.) (models with current output: 4 VA/2 W)  
E5CN-U  
Models with temperature inputs  
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II  
Platinum resistance thermometer: Pt100 or JPt100  
Infrared temperature sensor: 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C  
Voltage input: 0 to 50 mV  
Sensor input  
Models with analog inputs  
Current input: 4 to 20 mA or 0 to 20 mA  
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V  
Input impedance  
Control method  
Current input: 150 max., Voltage input: 1 Mmin. (Use a 1:1 connection when connecting the ES2-HB.)  
ON/OFF control or 2-PID control (with auto-tuning)  
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable  
load: 5 V, 10 mA  
E5CN  
Relay output  
SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load:  
5 V, 10 mA  
E5CN-U  
Control  
outputs  
Voltage output  
(for driving SSR)  
E5CN  
E5CN-U circuit  
Output voltage: 12 VDC 15% (PNP), max. load current: 21 mA, with short-circuit protection  
Current output  
E5CN  
E5CN  
4 to 20 mA DC/0 to 20 mA DC, load: 600 max., resolution: approx. 10,000  
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 1,000,000 operations, load power supply  
voltage: 75 to 250 VAC (DC loads cannot be connected.), minimum applicable load: 5 V, 10 mA,  
leakage current: 5 mA max. (250 VAC, 60 Hz)  
Long-life relay  
output  
Number of outputs 1 or 2 max. (Depends on the model.)  
Auxiliary  
outputs  
Output  
Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum  
applicable load: 5 V, 10 mA  
specifications  
Number of inputs  
2
Contact input: ON: 1 kmax., OFF: 100 kmin.  
Event  
inputs  
External contact  
input  
specifications  
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.  
Current flow: Approx. 7 mA per contact  
External power supply for ES1B 12 VDC 10%, 20 mA, short-circuit protection circuit provided  
Setting method  
Digital setting using front panel keys  
11-segment digital display and individual indicators (7-segment display also possible)  
Character height: PV: 11 mm, SV: 6.5 mm  
Indication method  
Up to four set points (SP0 to SP3) can be saved and selected using event inputs, key operations, or serial  
communications.  
Multi SP  
Bank switching  
Not supported  
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout  
detection, 40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop,  
protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, logic  
operations, PV/SV status display, simple program, automatic cooling coefficient adjustment  
Other functions  
Ambient operating temperature 10 to 55°C (with no condensation or icing), for 3-year warranty: 10 to 50°C  
Ambient operating humidity  
Storage temperature  
25% to 85%  
25 to 65°C (with no condensation or icing)  
6
E5CN/E5CN-U  
Input Ranges  
Thermocouple/Platinum Resistance Thermometer (Universal Inputs)  
Input  
Type  
Platinum resistance  
thermometer  
Infrared temperature Analog  
Thermocouple  
sensor  
input  
115  
140  
to  
260  
°C  
60to  
120  
°C  
PL  
II  
0 to  
50 mV  
10to  
70°C  
to  
165  
°C  
Name  
Pt100  
JPt100  
K
J
T
E
L
U
N
R
S
B
W
2300  
2300  
1800  
1800  
1700  
1600  
1500  
1400  
1300  
1200  
1100  
1000  
900  
1700 1700  
1300  
1300  
1300  
Usable  
in the  
following  
ranges  
by  
850  
850  
850  
800  
scaling:  
1999 to  
9999 or  
199.9  
to 999.9  
700  
600  
600  
500.0  
500.0  
500.0  
500  
400.0 400 400.0  
400 400.0  
400  
260  
300  
120  
0
165  
0
200  
100.0  
0.0  
100.0  
90  
0
100  
100  
0
0.0  
0
0
0
0
0
100.0  
200.0  
20.0 100 20.0  
100  
200 199.9  
199.9  
200  
200 199.9 200  
200 199.9 200  
Setting  
number  
0
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 24 25  
19  
20  
21  
22  
23  
Shaded settings are the default settings.  
The applicable standards for the input types are as follows:  
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1  
L: Fe-CuNi, DIN 43710-1985  
JPt100: JIS C 1604-1989, JIS C 1606-1989  
Pt100: JIS C 1604-1997, IEC 751  
U: Cu-CuNi, DIN 43710-1985  
PL II: According to Platinel II electromotive force charts from BASF (previously  
Engelhard)  
W: W5Re/W26Re, ASTM E988-1990  
Models with Analog Inputs  
Input Type  
Current  
Voltage  
0 to 5 V  
Input specification  
4 to 20mA 0 to 20 mA  
1 to 5 V  
0 to 10 V  
Usable in the following ranges by scaling:  
1999 to 9999, 199.9 to 999.9, 19.99 to 99.99 or 1.999 to 9.999  
Setting range  
Setting number  
0
1
2
3
4
Shaded settings are the default settings.  
7
E5CN/E5CN-U  
Alarm Outputs  
Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit.  
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.  
Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the  
following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR  
failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function).  
Alarm output operation  
Set value  
Alarm type  
Alarm function OFF  
Description of function  
When alarm value When alarm value  
X is positive  
X is negative  
0
Output OFF  
No alarm  
L
H
Set the deviation in the set point by setting the alarm  
upper limit (H) and alarm lower limit (L).  
ON  
OFF  
1 *1  
2
Upper- and lower-limit  
Upper-limit  
*2  
SP  
X
X
Set the upward deviation in the set point by setting  
the alarm value (X).  
ON  
OFF  
ON  
OFF  
SP  
SP  
X
X
ON  
OFF  
ON  
OFF  
Set the downward deviation in the set point by setting  
the alarm value (X).  
3
Lower-limit  
SP  
SP  
L
H
Set the deviation in the set point by setting the alarm  
upper limit (H) and alarm lower limit (L).  
ON  
OFF  
4 *1  
Upper- and lower-limit range  
*3  
*4  
SP  
L
H
ON  
OFF  
Upper- and lower-limit with  
standby sequence  
A standby sequence is added to the upper- and  
lower-limit alarm (1). *6  
5 *1  
SP  
*5  
ON  
X
X
A standby sequence is added to the upper-limit alarm  
(2). *6  
ON  
OFF  
6
7
Upper-limit with standby sequence  
Lower-limit with standby sequence  
OFF  
SP  
SP  
X
X
ON  
OFF  
A standby sequence is added to the lower-limit alarm  
(3). *6  
ON  
OFF  
SP  
X
SP  
X
ON  
OFF  
The alarm will turn ON if the process value is larger  
than the alarm value (X) regardless of the set point.  
ON  
OFF  
8
9
Absolute-value upper-limit  
Absolute-value lower-limit  
0
0
0
0
X
X
ON  
OFF  
ON  
OFF  
The alarm will turn ON if the process value is smaller  
than the alarm value (X) regardless of the set point.  
X
X
X
X
Absolute-value upper-limit with  
standby sequence  
ON  
OFF  
A standby sequence is added to the absolute-value  
upper-limit alarm (8). *6  
ON  
OFF  
10  
11  
0
0
0
0
Absolute-value lower-limit with  
standby sequence  
A standby sequence is added to the absolute-value  
lower-limit alarm (9). *6  
ON  
OFF  
ON  
OFF  
12  
13  
LBA (alarm 1 type only)  
PV change rate alarm  
---  
---  
*7  
*8  
*1. With set values 1, 4 and 5, the upper and lower limit values can  
be set independently for each alarm type, and are expressed as  
“L” and “H.”  
*5. Set value: 5, Upper- and lower-limit with standby sequence  
Always OFF when the upper-limit and lower-limit hysteresis  
overlaps.  
*6. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature  
Controllers User's Manual Basic Type (Cat. No. H156) for  
information on the operation of the standby sequence.  
*7. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature  
Controllers User's Manual Basic Type (Cat. No. H156) for  
information on the loop burnout alarm (LBA).  
*2. Set value: 1, Upper- and lower-limit alarm  
Case 2  
Case 1  
Case 3 (Always ON)  
H < 0, L < 0  
H
SP  
L
SP L  
H
L
H SP  
H < 0, L > 0  
H⏐ ≥ ⏐L⏐  
H < 0, L > 0  
H< L⏐  
H > 0, L < 0  
H> L⏐  
H
L SP  
*8. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature  
Controllers User's Manual Basic Type (Cat. No. H156) for  
information on the PV change rate alarm.  
H > 0, L < 0  
SPH  
L
H⏐ ≤ ⏐L⏐  
*3. Set value: 4, Upper- and lower-limit range  
Case 3 (Always OFF)  
Case 1  
Case 2  
H < 0, L < 0  
H
SP  
L
L
H SP  
SP L  
H
H < 0, L > 0  
H < 0, L > 0  
H > 0, L < 0  
H⏐ ≥ ⏐L⏐  
H
L SP  
H< L⏐  
H> L⏐  
H > 0, L < 0  
H⏐ ≤ ⏐L⏐  
L
SP H  
*4. Set value: 5, Upper- and lower-limit with standby sequence  
For Upper- and Lower-Limit Alarm Described Above  
Case 1 and 2  
Always OFF when the upper-limit and lower-limit hysteresis  
overlaps.  
Case 3: Always OFF  
8
E5CN/E5CN-U  
Characteristics  
Thermocouple: *1  
Terminal block models (E5CN): ( 0.3% of indicated value or 1°C, whichever is greater) 1 digit max.  
Plug-in models (E5CN-U): ( 1% of indicated value or 2°C, whichever is greater) 1 digit max.  
Platinum resistance thermometer input:  
Terminal block models (E5CN) and plug-in models (E5CN-U): ( 0.2% of indicated value or 0.8°C, whichever is greater) 1 digit max.  
Analog input:  
Indication accuracy  
Terminal block models (E5CN) and plug-in models (E5CN-U): 0.2% FS 1 digit max.  
CT input:  
Terminal block models (E5CN): 5% FS 1 digit max.  
Thermocouple input (R, S, B, W, PL II):  
Terminal block models (E5CN): ( 1% of PV or 10°C, whichever is greater) 1 digit max.  
Plug-in models (E5CN-U): ( 2% of PV or 10°C, whichever is greater) 1 digit max.  
Other thermocouple input: *3  
Terminal block models (E5CN): ( 1% of PV or 4°C, whichever is greater) 1 digit max.  
Plug-in models (E5CN-U): ( 2% of PV or 4°C, whichever is greater) 1 digit max.  
Platinum resistance thermometer input:  
Terminal block models (E5CN) and plug-in models (E5CN-U):  
( 1% of PV or 2°C, whichever is greater) 1 digit max.  
Analog input:  
Influence of temperature *2  
Influence of voltage *2  
Terminal block models (E5CN) and plug-in models (E5CN-U): ( 1%FS) 1 digit max.  
Input sampling period  
Hysteresis  
250 ms  
Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 EU) *4  
Models with analog input: 0.01 to 99.99% FS (in units of 0.01% FS)  
Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 EU) *4  
Models with analog input: 0.1 to 999.9% FS (in units of 0.1% FS)  
Proportional band (P)  
Integral time (I)  
0 to 3999 s (in units of 1 s)  
Derivative time (D)  
Control period  
0 to 3999 s (in units of 1 s) *5  
0.5, 1 to 99 s (in units of 1 s)  
Manual reset value  
Alarm setting range  
0.0 to 100.0% (in units of 0.1%)  
1999 to 9999 (decimal point position depends on input type)  
Affect of signal source  
resistance  
Thermocouple: 0.1°C/Ω max. (100 Ω max.)  
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)  
Insulation resistance  
Dielectric strength  
20 MΩ min. (at 500 VDC)  
2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)  
10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions  
10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions  
100 m/s2, 3 times each in X, Y, and Z directions  
Malfunction  
Vibration  
resistance  
Destruction  
Malfunction  
Destruction  
E5CN  
Shock  
resistance  
300 m/s2, 3 times each in X, Y, and Z directions  
Controller: Approx. 150 g, Mounting Bracket: Approx. 10 g  
Controller: Approx. 110 g, Mounting Bracket: Approx. 10 g  
Front panel: IP66, Rear case: IP20, Terminals: IP00  
Front panel: IP50, Rear case: IP20, Terminals: IP00  
Non-volatile memory (number of writes: 1,000,000 times)  
CX-Thermo version 4.0 or higher  
Weight  
E5CN-U  
E5CN  
Degree of  
protection  
E5CN-U  
Memory protection  
Setup Tool  
Provided on the bottom of the E5CN. Use this port to connect a computer to the E5CN when using the Setup Tool. An E58-CIFQ1  
USB-Serial Conversion Cable is required to connect the computer to the E5CN. *6  
Setup Tool port  
Approved  
standards *7  
UL 61010-1, CSA C22.2 No. 1010-1, KOSHA certified (some models) *8  
Standards  
Conformed  
standards  
EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II, Lloyd's standards *9  
EMI:  
EN 61326  
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A  
Noise Terminal Voltage:  
EMS:  
ESD Immunity:  
Electromagnetic Field Immunity:  
Burst Noise Immunity:  
Conducted Disturbance Immunity:  
Surge Immunity:  
EN 55011 Group 1, class A  
EN 61326  
EN 61000-4-2  
EN 61000-4-3  
EN 61000-4-4  
EN 61000-4-6  
EN 61000-4-5  
EN 61000-4-8  
EN 61000-4-11  
EMC  
Power Frequency Magnetic Field Immunity:  
Voltage Dip/Interrupting Immunity:  
*1. The indication accuracy of K thermocouples in the 200 to 1300°C range, T and N thermocouples at a temperature of 100°C max., and U  
and L thermocouples at any temperatures is 2°C 1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max.  
is not specified. The indication accuracy of B thermocouples in the 400 to 800°C range is 3°C max. The indication accuracy of the R and S  
thermocouples at a temperature of 200°C max. is 3°C 1 digit max. The indication accuracy of W thermocouples is 0.3 of PV or 3°C,  
whichever is greater, 1 digit max. The indication accuracy of PL II thermocouples is 0.3 of PV or 2°C, whichever is greater, 1 digit max.  
*2. Ambient temperature: 10°C to 23°C to 55°C, Voltage range: 15% to 10% of rated voltage  
*3. K thermocouple at 100°C max.: 10° max.  
*4. “EU” stands for Engineering Unit and is used as the unit after scaling. For a temperature sensor, the EU is °C or °F.  
*5. When robust tuning (RT) is ON, the differential time is 0.0 to 999.9 (in units of 0.1 s).  
*6. External communications (RS-485) and cable communications for the Setup Tool can be used at the same time.  
*7. The E5CN-U plug-in model is certified for UL listing only when used together with the OMRON P2CF-11 or P2CF-11-E Socket.  
The P3GA-11 is not certified for UL listing.  
*8. Access the following website for information on certified models. http://www.ia.omron.com/support/models/index.html  
*9. Refer to information on maritime standards in Safety Precautions for E5@N/E5@N-H for compliance with Lloyd's Standards.  
9
E5CN/E5CN-U  
USB-Serial Conversion Cable  
Current Transformer (Order Separately)  
Ratings  
Applicable OS  
Windows 2000, XP, or Vista  
Applicable software  
CX-Thermo version 4 or higher  
Dielectric strength  
1,000 VAC for 1 min  
E5AN/E5EN/E5CN/E5CN-U/E5AN-H/  
E5EN-H/E5CN-H/E5GN  
Vibration resistance 50 Hz, 98 m/s2  
Applicable models  
E54-CT1: Approx. 11.5 g,  
Weight  
USB interface standard Conforms to USB Specification 1.1.  
E54-CT3: Approx. 50 g  
DTE speed  
38400 bps  
Accessories  
Armatures (2)  
Plugs (2)  
(E54-CT3 only)  
Computer: USB (type A plug)  
Temperature Controller: Setup Tool port  
(on bottom of Controller)  
Connector  
specifications  
Heater Burnout Alarms, SSR Failure  
Alarms, and Heater Overcurrent Alarms  
Bus power (Supplied from USB host  
controller.)  
Power supply  
Models with detection for single-phase  
heaters: One input  
Models with detection for single-phase  
or three-phase heaters: Two inputs  
CT input  
Power supply voltage  
Current consumption  
5 VDC  
70 mA  
(for heater current  
detection)  
Ambient operating  
temperature  
0 to 55°C (with no condensation or icing)  
10% to 80%  
Maximum heater current 50 A AC  
Ambient operating  
humidity  
Input current indication  
5% FS 1 digit max.  
accuracy  
20 to 60°C (with no condensation or  
icing)  
Heater burnout alarm  
setting range *1  
0.1 to 49.9 A (in units of 0.1 A)  
Minimum detection ON time: 100 ms  
Storage temperature  
Storage humidity  
Altitude  
10% to 80%  
2,000 m max.  
Approx. 100 g  
SSR failure alarm  
setting range *2  
0.1 to 49.9 A (in units of 0.1 A)  
Minimum detection OFF time: 100 ms  
Heater overcurrent  
alarm setting range *3 Minimum detection ON time: 100 ms  
0.1 to 49.9 A (in units of 0.1 A)  
Weight  
Note: A driver must be installed in the personal computer. Refer to  
installation information in the operation manual for the  
Conversion Cable.  
*1. For heater burnout alarms, the heater current will be measured  
when the control output is ON, and the output assigned to the  
alarm 1 function will turn ON if the heater current is lower than the  
set value (i.e., heater burnout detection current value).  
*2. For SSR failure alarms, the heater current will be measured when  
the control output is OFF, and the output assigned to the alarm 1  
function will turn ON if the heater current is higher than the set  
value (i.e., SSR failure detection current value).  
*3. For heater overcurrent alarms, the heater current will be  
measured when the control output is ON, and the output assigned  
to the alarm 1 function will turn ON if the heater current is higher  
than the set value (i.e., heater overcurrent detection current  
value).  
Communications Specifications  
Transmission line  
RS-485: Multipoint  
connection method  
Communications  
RS-485 (two-wire, half duplex)  
Synchronization  
method  
Start-stop synchronization  
Protocol  
CompoWay/F, SYSWAY, or Modbus  
1200, 2400, 4800, 9600, 19200, 38400, or  
57600 bps  
Baud rate  
Electrical Life Expectancy Curve for  
Relays (Reference Values)  
Transmission code ASCII  
Data bit length *  
Stop bit length *  
7 or 8 bits  
500  
1 or 2 bits  
300  
Vertical parity (none, even, odd)  
Frame check sequence (FCS) with SYSWAY  
Block check character (BCC) with  
CompoWay/F or CRC-16 Modbus  
100  
Error detection  
50  
30  
Flow control  
Interface  
None  
RS-485  
None  
10  
Retry function  
Communications  
buffer  
5
E5CN  
250 VAC, 30 VDC  
(resistive load)  
cosφ = 1  
217 bytes  
0 to 99 ms  
3
Communications  
response wait time Default: 20 ms  
1
0
1
2
3
4
5
6
* The baud rate, data bit length, stop bit length, and vertical parity can  
be individually set using the Communications Setting Level.  
Switching current (A)  
Note: Do not connect a DC load to a Controller with a Long-life Relay  
Output.  
10  
E5CN/E5CN-U  
External Connections  
A voltage output (control output, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple,  
do not connect any of the control output terminals to ground. (If the control output terminals are connected to ground, errors will occur in the  
measured temperature values as a result of leakage current.)  
Consult with your OMRON representative before using the external power supply for the ES1B for any other purpose.  
E5CN  
Controllers  
Control output 1  
The E5@N-@@@T@ is set for a K-type  
thermocouple (input type = 5) by default. An  
input error (s.err) will occur if the input type  
setting does not agree with the temperature  
sensor. Check the input type.  
Long-life relay output  
250 VAC, 3 A (resistive load)  
Relay output  
250 VAC, 3 A (resistive load)  
Voltage output (for driving SSR)  
12 VDC, 21 mA  
Auxiliary outputs (relay outputs)  
250 VAC, 3 A  
(resistive load)  
Current output  
0 to 20 mA DC  
4 to 20 mA DC  
Load: 600 Ω max.  
Auxiliary outputs  
(relay outputs)  
Control output 1  
Auxiliary output 2  
Auxiliary output 1  
Control output 2  
Voltage output (for driving SSR)  
12 VDC, 21 mA  
A
B
B
DO NOT  
USE  
DO NOT  
USE  
mA  
A heater burnout alarm, heater short alarm,  
heater overcurrent alarm, or input alarm is  
sent to the output to which the alarm 1  
function is assigned.  
V
Input power supply  
DO NOT  
USE  
• 100 to 240 VAC  
• 24 VAC/VDC (no polarity)  
TC/Pt  
universal input  
Analog input  
Option Units  
E53-CNPHN2  
External Power  
Supply and CT  
E53-CNP03N2  
Communications (RS-485)  
and External Power Supply  
E53-CNPBN2  
Event Inputs and  
External Power Supply  
E53-CNHH03N2  
Communications  
(RS-485) and CT2  
E53-CNHBN2  
Event inputs  
and CT  
E53-CNQ03N2  
Communications  
(RS-485) and  
Control Output 2  
B(+)  
11  
RS-485  
B(+)  
11  
11  
11  
B(+)  
11  
RS-485  
+
External  
11  
12  
13  
14  
15  
12 VDC,  
20 mA  
RS-485  
power supply  
12  
12  
12  
13  
14  
15  
12  
A()  
EV1  
EV1  
EV2  
A()  
12  
A()  
13  
13  
DO NOT  
13  
14  
15  
DO NOT  
EV2  
DO NOT  
13  
USE  
USE  
CT2  
USE  
14  
15  
+
14  
15  
+
External  
External  
+
12 VDC,  
20 mA  
CT1  
12 VDC,  
20 mA  
14  
CT1  
power supply  
power supply  
CT1  
Control output 2  
15  
E53-CNH03N2  
Communications  
(RS-485) and CT  
E53-CN03N2  
Communications  
(RS-485)  
E53-CNBN2  
Event inputs  
E53-CNQHN2  
Control Output 2  
and CT  
E53-CNQHHN2  
Control Output 2  
and CT2  
E53-CNQBN2  
Event Inputs and  
Control Output 2  
B(+)  
11  
RS-485  
+
B(+)  
11  
RS-485  
+
11  
11  
11  
11  
Control output 2  
Control output 2  
12  
12  
12  
12  
12  
12  
A()  
EV1  
A()  
EV1  
DO NOT  
DO NOT  
13  
13  
14  
15  
13  
13  
14  
15  
DO NOT  
USE  
DO NOT  
USE  
13  
13  
EV2  
+
USE  
EV2  
DO NOT  
USE  
CT2  
14  
15  
14  
14  
14  
USE  
CT1  
Control output 2  
CT1  
CT1  
DO NOT  
15  
15  
15  
DO NOT  
USE  
USE  
E5CN-U  
The E5@N-@@@T@ is set for a  
K-type thermocouple (input type = 5)  
by default. An input error (s.err) will  
occur if the input type setting does  
not agree with the temperature  
sensor. Check the input type.  
Auxiliary output  
250 VAC, 3 A (resistive load)  
(Relay outputs)  
Control output 1  
Control output 1  
Auxiliary output 1  
Auxiliary output 2  
Relay output  
(three terminals used)  
SPDT, 250 VAC, 3 A  
(resistive load)  
Voltage output  
(for driving SSR)  
(Control output (cooling side))  
A
B
DO NOT  
USE  
DO NOT  
USE  
An input error is sent to the  
output to which the alarm 1  
function is assigned.  
mA  
12 VDC, 21 mA  
Current output  
4 to 20 mA DC  
0 to 20 mA DC  
Load: 600 W max.  
V
DO NOT  
USE  
Input power supply  
B
• 100 to 240 VAC  
• 24 VAC/VDC (no polarity)  
Analog input  
TC/Pt  
universal input  
Note: For the Wiring Socket, purchase the P2CF-11 or PG3A-11 separately.  
11  
E5CN/E5CN-U  
Nomenclature  
E5CN  
Temperature unit  
E5CN-U  
The front panel is the same for the E5CN and E5CN-U.  
No.1 display  
Operation indicators  
No. 2 display  
Up Key  
Level Key  
Mode Key  
Down Key  
Dimensions  
(Unit: mm)  
E5CN  
Panel Cutout  
Terminal Models  
Mounted Separately  
Group Mounted  
91  
(48 × number of units 2.5)+1.0  
0
6
78  
48 × 48  
1.5  
45+0.6  
0
Group mounting does not  
allow waterproofing.  
58  
60 min.  
44.8 × 44.8 48.8  
Recommended panel thickness is 1 to  
5 mm.  
45+0.6  
0
Group mounting is not possible in the  
vertical direction. (Maintain the specified  
mounting space between Controllers.)  
To mount the Controller so that it is  
waterproof, insert the waterproof packing  
onto the Controller.  
Waterproof  
Packing  
(Accessory)  
Mounting Adapter  
(Accessory)  
Terminal Cover  
(E53-COV17)  
(Accessory)  
45+0.6  
0
When two or more Controllers are  
mounted, make sure that the surrounding  
temperature does not exceed the  
allowable operating temperature  
specified in the specifications.  
Note: The terminal block cannot be removed.  
E5CN-U  
Plug-in Models  
Panel Cutout  
Mounted Separately  
(84.7)  
Group Mounted  
14.2  
(48 × number of units 2.5)+1.0  
6
48 × 48  
70.5  
0
45+0.6  
0
58  
44.8 × 44.8  
60 min.  
Recommended panel thickness is 1 to 5  
mm.  
Group mounting is not possible in the  
vertical direction. (Maintain the specified  
mounting space between Controllers.)  
When two or more Controllers are  
mounted, make sure that the surrounding  
temperature does not exceed the  
allowable operating temperature specified  
in the specifications.  
45+0.6  
0
Mounting Adapter  
(Accessory)  
45+0.6  
0
Accessories (Order Separately)  
USB-Serial Conversion Cable  
E58-CIFQ1  
(2,100)  
LED indicator (SD)  
1,765  
250  
USB connector (type A plug)  
Serial connector  
LED indicator (RD)  
12  
E5CN/E5CN-U  
Waterproof Packing  
Y92S-29 (for DIN 48 × 48)  
Terminal Cover  
E53-COV17  
Order the Waterproof Packing separately if it becomes lost or  
damaged.  
The Waterproof Packing can be used to achieve an IP66 degree of  
protection.  
Note: The E53-COV10  
cannot be used.  
(Deterioration, shrinking, or hardening of the waterproof packing may  
occur depending on the operating environment. Therefore, periodic  
replacement is recommended to ensure the level of waterproofing  
specified in IP66. The time for periodic replacement depends on the  
operating environment. Be sure to confirm this point at your site.  
Consider one year a rough standard. OMRON shall not be liable for  
the level of water resistance if the customer does not perform periodic  
replacement.)  
48  
48.8  
The Waterproof Packing does not need to be attached if a waterproof  
structure is not required.  
22  
9.1  
Current Transformers  
E54-CT1  
E54-CT1  
21  
15  
Thru-current (Io) vs. Output Voltage  
(Eo) (Reference Values)  
2.8  
5.8 dia.  
7.5  
Maximum continuous heater current: 50 A (50/60 Hz)  
Number of windings: 400 2  
Winding resistance: 18 2 Ω  
25  
3
100 V  
50 Hz  
10.5  
1 k  
10  
40  
Distortion  
factor 10%  
Two, 3.5 dia.  
1
100 mV  
10  
3%  
1%  
10  
30  
30  
100 Ω  
E54-CT3  
RL = 10 Ω  
1
2.36 dia.  
12 dia.  
100 µV  
9
10  
1
10  
100 mA  
1
10  
100 1,000 A  
Thru-current (Io) A (r.m.s.)  
40 × 40  
E54-CT3  
Thru-current (Io) vs. Output Voltage  
(Eo) (Reference Values)  
Two, M3 (depth: 4)  
Maximum continuous heater current: 120 A (50/60 Hz)  
(Maximum continuous heater current for the  
Temperature Controller is 50 A.)  
15  
Number of windings: 400 2  
Winding resistance: 8 0.8 Ω  
30  
100 V  
50 Hz  
Distor-  
E54-CT3 Accessory  
Armature  
tion  
Connection Example  
10  
factor  
10%  
3%  
1 kΩ  
500 Ω  
Armature  
Plug  
Approx. 3 dia.  
1%  
1
100 mV  
10  
Lead  
100 Ω  
50 Ω  
18  
RL = 10 Ω  
1
Plug  
100 µV  
Approx. 6 dia.  
10  
1
10  
100 mA  
1
10  
100 1,000 A  
(22)  
Thru-current (Io) A (r.m.s.)  
13  
E5CN/E5CN-U  
Adapter  
Y92F-45  
Note: 1. Note: 1. Use this Adapter when the panel has already been prepared for the E5B@.  
2. The Adapter is available only in black.  
Fixture (Accessory)  
4.7  
76  
69.6 to 77.6  
72 × 72  
67 × 67 87  
Mounted to E5CN  
Panel (1 to 8 mm)  
72 × 72  
48 × 48  
2.2  
4.7  
77.3 (to back of E5CN)  
E5CN-U Wiring Socket  
Front-connecting Socket  
P2CF-11  
Terminal Layout/Internal Connections  
(Top View)  
3
4.5  
Eleven, M3.5 × 7.5  
sems screws  
7.8  
8
7 6 5  
Mounting Holes  
4
Two, 4.5 dia. mounting holes  
35.4  
70 max.  
Two,  
4.5-dia.  
holes  
0.2  
40  
9
3
10 11 1 2  
Note: Can also be mounted to a DIN track.  
4
50 max.  
31.2 max.  
Note: A model with finger protection (P2CF-11-E) is also available.  
Back-connecting Socket  
P3GA-11  
Terminal Layout/Internal Connections  
(Bottom View)  
27 dia.  
4
7
3
5
6
7 8  
4
45  
25.6  
3
9
2
1
11 10  
45  
4.5 16.3 6.2  
6
8.7  
Note: 1. Using any other sockets will adversely affect accuracy. Use only the specified sockets.  
2. A Protective Cover for finger protection (Y92A-48G) is also available.  
14  
Read and Understand This Catalog  
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or  
comments.  
Warranty and Limitations of Liability  
WARRANTY  
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)  
from date of sale by OMRON.  
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR  
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS  
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER  
WARRANTIES, EXPRESS OR IMPLIED.  
LIMITATIONS OF LIABILITY  
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS  
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT  
LIABILITY.  
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.  
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS  
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT  
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.  
Application Considerations  
SUITABILITY FOR USE  
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's  
application or use of the products.  
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the  
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,  
machine, system, or other application or use.  
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible  
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:  
·
·
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.  
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,  
safety equipment, and installations subject to separate industry or government regulations.  
·
Systems, machines, and equipment that could present a risk to life or property.  
Please know and observe all prohibitions of use applicable to the products.  
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE  
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND  
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.  
PROGRAMMABLE PRODUCTS  
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.  
Disclaimers  
CHANGE IN SPECIFICATIONS  
Product specifications and accessories may be changed at any time based on improvements and other reasons.  
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.  
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or  
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual  
specifications of purchased products.  
DIMENSIONS AND WEIGHTS  
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.  
PERFORMANCE DATA  
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the  
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON  
Warranty and Limitations of Liability.  
ERRORS AND OMISSIONS  
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,  
typographical, or proofreading errors, or omissions.  
2009.11  
In the interest of product improvement, specifications are subject to change without notice.  
OMRON Corporation  
Industrial Automation Company  
http://www.ia.omron.com/  
(c)Copyright OMRON Corporation 2009 All Right Reserved.  

相关型号:

E5CN-Q1TDU

Basic-type Digital Temperature Controller
OMRON

E5CN-Q1TU

Digital Temperature Controllers
OMRON

E5CN-Q2LU

Basic-type Digital Temperature Controller
OMRON

E5CN-Q2ML-500

Digital Temperature Controllers
OMRON

E5CN-Q2MLD-500

Basic-type Digital Temperature Controller
OMRON

E5CN-Q2MT-500

Digital Temperature Controllers
OMRON

E5CN-Q2MT-W-500

Basic-type Digital Temperature Controller
OMRON

E5CN-Q2MTD-500

Basic-type Digital Temperature Controller
OMRON

E5CN-Q2MTD-W-500

Basic-type Digital Temperature Controller
OMRON

E5CN-Q2TDU

Basic-type Digital Temperature Controller
OMRON

E5CN-Q2TU

Digital Temperature Controllers
OMRON

E5CN-QML-500

Digital Temperature Controllers
OMRON