G7L-1A-BUBJ12VAC [OMRON]

Power/Signal Relay, SPST, Momentary, 1700mW (Coil), AC Input, AC Output, Panel Mount;
G7L-1A-BUBJ12VAC
型号: G7L-1A-BUBJ12VAC
厂家: OMRON ELECTRONICS LLC    OMRON ELECTRONICS LLC
描述:

Power/Signal Relay, SPST, Momentary, 1700mW (Coil), AC Input, AC Output, Panel Mount

文件: 总15页 (文件大小:357K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
General Purpose Relay – G7L  
A High-capacity, High-dielectric-  
strength Relay Compatible with  
Momentary Voltage Drops  
No contact chattering for momentary voltage  
drops up to 50% of rated voltage.  
Wide-range AC-activated coil that handles  
100 to 120 or 200 to 240 VAC at either 50 or  
60 Hz.  
Miniature hinge for maximum switching power,  
particularly for inductive loads.  
Flame-resistance materials (UL94V-0-  
RCE  
qualifying) used for all insulation material.  
Quick-connect, screw, and PCB terminals,  
and DIN track mounting available.  
Ordering Information  
Mounting Type  
Contact form  
Quick-connect  
terminals  
Screw terminals  
terminals  
PCB terminals  
E-bracket  
SPST-NO  
G7L-1A-T  
G7L-1A-B  
DPST-NO  
SPST-NO  
DPST-NO  
SPST-NO  
DPST-NO  
SPST-NO  
DPST-NO  
SPST-NO  
DPST-NO  
G7L-2A-T  
G7L-1A-TJ  
G7L-2A-TJ  
G7L-1A-TUB  
G7L-2A-TUB  
G7L-1A-TUBJ  
G7L-2A-TUBJ  
G7L-2A-B  
G7L-1A-BJ  
G7L-2A-BJ  
G7L-1A-BUB  
G7L-2A-BUB  
G7L-1A-BUBJ  
G7L-2A-BUBJ  
E-bracket (with  
test button)  
Upper bracket  
Upper bracket  
(with test button)  
PCB mounting  
G7L-1A-P  
G7L-2A-P  
Note: 1. When ordering, add the rated coil voltage to the model number.  
Example: G7L-1A-T 12 VAC (~)  
Rated coil voltage  
465  
General Purpose Relay – G7L  
Accessories (Order Separately)  
Terminals  
Contact form  
Model  
P99-07  
E-brackets  
P7LF-D DIN  
Track Mounting  
Adapter  
P7LF-06  
Front Connecting  
Socket  
Quick-connect  
terminals  
SPST-NO  
G7L-1A-T  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
G7L-1A-TJ  
G7L-2A-T  
G7L-2A-TJ  
G7L-1A-B  
G7L-1A-BJ  
G7L-2A-B  
G7L-2A-BJ  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
No  
No  
No  
DPST-NO  
SPST-NO  
DPST-NO  
Screw terminals  
Applicable Relay  
Name  
Model  
G7L-1A-T/G7L-1A-TJ/G7L-1A-B/G7L-1A-BJ  
G7L-2A-T/G7L-2A-TJ/G7L-2A-B/G7L-2A-BJ  
E-bracket  
Adapter  
R99-07  
P7LF-D  
P7LF-06  
P7LF-C  
G7L-1A-T/G7L-1A-TJ/G7L-2A-T/G7L-2A-TJ  
Front-connecting Socket  
Cover  
G7L-1A-B/G7L-1A-BJ/G7L-1A-BUB/G7L-1A-BUBJ  
G7L-2A-B/G7L-2A-BJ/G7L-2A-BUB/G7L-2A-BUBJ  
Model Number Legend  
G7L -  
-
1
2
3
4 , 5  
1. Contact Form  
1A: SPST-NO  
2A: DPST-NO  
5. Rated Coil Voltage  
AC: 12, 24, 50, 100 to 120, 200 to 240  
DC: 6, 12, 24, 48, 100  
3. Mounting Construction  
Blank: E-bracket  
UB:  
Upper bracket  
2.Terminal Shape  
T: Quick-connect terminals  
P: PCB terminals  
B: Screw terminals  
4. Special Functions  
Blank: Standard mode  
J:  
With test button  
Application Examples  
• Compressors for air conditioners and heater switching  
controllers.  
• Switching controllers for power tools or motors.  
• Power controllers for water heaters.  
• Power controllers for dryers.  
• Lamp controls, motor drivers, and power supply switching in  
copy machines, facsimile machines, and other office  
equipment.  
• Lighting controllers.  
• Power controllers for packers or food processing equipment.  
• Magnetron control in microwaves.  
466  
General Purpose Relay – G7L  
Specifications  
Coil Ratings  
Rated Voltage  
Rated  
current  
Coil  
resistance  
Must operate  
voltage  
Must release Max. voltage  
voltage  
Power  
consumption  
(approx.)  
AC (~)  
12 V  
24 V  
50 V  
142 mA  
75% max. of  
rated voltage  
15% min. of  
rated voltage  
110% of  
rated voltage  
1.7 to 2.5 VA  
(60 Hz)  
71 mA  
34 mA  
100 to 120 V  
7.0 to  
20.4 mA  
75 V  
18 V  
36 V  
132 V  
264 V  
200 to 240 V  
8.5 to  
150 V  
10.2 mA  
DC (=)  
6 V  
317 mA  
158 mA  
79 mA  
40 mA  
19 mA  
18.9 Ω  
75 Ω  
75% max. of  
rated voltage  
15% min. of  
rated voltage  
110% of  
rated voltage  
1.9 W  
12 V  
24 V  
48 V  
100 V  
303 Ω  
1220 Ω  
5260  
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/–20% for AC rated  
current and 15% for DC coil resistance.  
2. Performance characteristic data are measured at a coil temperature of 23°C.  
3. ~ indicates AC and = indicates DC (IEC417 publications).  
Contact Ratings  
Model  
G7L-1A-T@/G7L-1A-B@  
G7L-2A-T@/G7L-2A-B@  
G7L-1A-P/G7L-2A-P  
Resistive load Inductive load  
Resistive load  
Inductive load  
Resistive load  
Inductive load  
(cosϕ = 1)  
(cosϕ = 0.4)  
(cosϕ = 1)  
(cosϕ = 0.4)  
(cosϕ = 1)  
(cosϕ = 0.4)  
Rated Load  
30 A, 220 VAC  
(~)  
25 A, 220 VAC  
(~)  
25 A, 220 VAC  
(~)  
25 A, 220 VAC  
(~)  
Carry Current  
30 A  
25 A  
20 A  
Max. switching 250 VAC (~)  
250 VAC (~)  
250 VAC (~)  
voltage  
Max. switching 30 A  
25 A  
20 A  
current  
Max. switching 6,600 VAC (~)  
power  
5,500 VAC (~)  
5,500 VAC (~)  
100 mA, 5 VDC (~)  
4,400 VAC (~)  
100 mA, 5 VDC (~)  
Failure rate*  
100 mA, 5 VDC (~)  
(reference value)  
*Note: P level: λ = 0.1 x 10-6/operation  
60  
467  
General Purpose Relay – G7L  
Characteristics  
Contact resistance  
50 mmax.  
30 ms max.  
30 ms max.  
Operate time  
Release time  
Max. operating frequency  
Mechanical: 1,800 operations/hr  
Electrical: 1,800 operations/hr (under rated load)  
Insulation resistance  
Dielectric strength  
1,000 Mmin. (at 500 VDC)  
4,000 VAC min., 50/60 Hz for 1 min between coil and contacts  
2,000 VAC, 50/60 Hz for 1 min between contacts of same polarity  
2,000 VAC, 50/60 Hz for 1 min between contacts of different polarity (DPST-NO model)  
Impulse withstand voltage  
Vibration resistance  
10,000 V between coil and contact (with 1.2 x 50 µs impulse wave)  
Destruction: 10 to 55 to, 0.75 mm single amplitude (1.5 mm double amplitude)  
Malfunction: 10 to 55 to, 0.75 mm single amplitude (1.5 mm double amplitude)  
Shock resistance  
Endurance  
Destruction: 1,000 m/s2  
Malfunction: 100 m/s2  
Mechanical: 1,000,000 operations min. (at 1,800 operations/hr)  
Electrical: 100,000 operations min. (at 1,800 operations/hr under rated load)  
Ambient temperature  
Ambient humidity  
Weight  
Operating: –25°C to 60°C (with no icing)  
Operating: 5% to 85%  
Quick-connect terminal models: approx. 90 g  
PCB terminal models: approx. 100 g  
Screw terminal models: approx. 120 g  
Note: The values given above are initial values  
468  
General Purpose Relay – G7L  
Approved by Standards  
UL 508, 1950 Recognitions (File No. E41643)  
CSA 22.2 No.14 Listings (File No.LR35535)  
Model  
Contact Form  
Coil ratings  
Contact ratings  
Operations  
100 x 103  
G7L-1A-T@  
G7L-1A-B@  
SPST-NO  
12 to 240 VAC  
5 to 220 VDC  
30 A, 277 VAC (RES)  
25 A, 277 VAC (GEN)  
30 A, 120 VAC (GEN)  
1.5 kW, 120 VAC (T)  
1.5 HP, 120 VAC  
6 x 103  
3 HP, 277 VAC  
100 x 103  
(CSA; 6 x 103)  
20 FLA/120 LRA, 120 VAC  
17 FLA/102 LRA, 265 VAC  
30 x 103  
G7L-2A-T@  
G7L-2A-B@  
DPST-NO  
SPST-NO  
DPST-NO  
TV-10, 120 VAC  
25 x 103  
25 A, 277 VAC (RES)  
25 A, 277 VAC (GEN)  
25 A, 120 VAC (GEN)  
100 x 103  
1.3 kW, 120 VAC (T)  
1 HP, 120 VAC  
6 x 103  
2 HP, 277 VAC  
100 x 103  
(CSA; 6 x 103)  
20 FLA/120 LRA, 120 VAC  
17 FLA/102 LRA, 265 VAC  
30 x 103  
G7L-1A-P  
TV-8, 120 VAC  
25 x 103  
20 A, 277 VAC (RES)  
20 A, 277 VAC (GEN)  
20 A, 120 VAC (GEN)  
100 x 103  
1.5 kW, 120 VAC (T)  
1.5 HP, 120 VAC  
6 x 103  
3 HP, 277 VAC  
100 x 103  
(CSA; 6 x 103)  
20 FLA/120 LRA, 120 VAC  
17 FLA/102 LRA, 265 VAC  
30 x 103  
G7L-2A-P  
TV-10, 120 VAC  
25 x 103  
20 A, 277 VAC (RES)  
20 A, 277 VAC (GEN)  
20 A, 120 VAC (GEN)  
100 x 103  
1.3 kW, 120 VAC (T)  
1 HP, 120 VAC  
6 x 103  
2 HP, 277 VAC  
100 x 103  
20 FLA/120 LRA, 120 VAC  
17 FLA/102 LRA, 265 VAC  
30 x 103  
25 x 103  
TV-8, 120 VAC  
469  
General Purpose Relay – G7L  
TÜV: File No. R9051158 (VDE 0435, IEC 255, IEC 950, EN60950)  
Model  
Contact Form  
Coil ratings  
Contact ratings  
Operations  
100 x 103  
G7L-1A-B@  
SPST-NO  
6, 12, 24, 48, 100, 110,  
200, 220 VDC  
12, 24, 50, 100 to 120,  
200 to 240 VAC  
30 A, 240 VAC (cosϕ = 1.0)  
25 A, 240 VAC (cosϕ = 0.4)  
30 A, 120 VAC (cosϕ = 0.4)  
G7L-2A-B@  
G7L-1A-T@  
G7L-2A-T@  
G7L-1A-P  
DPST-NO  
SPST-NO  
DPST-NO  
SPST-NO  
DPST-NO  
25 A, 240 VAC (cosϕ = 1.0)  
25 A, 240 VAC (cosϕ = 0.4)  
25 A, 240 VAC (cosϕ = 1.0)  
25 A, 240 VAC (cosϕ = 0.4)  
25 A, 240 VAC (cosϕ = 1.0)  
25 A, 240 VAC (cosϕ = 0.4)  
20 A, 240 VAC (cosϕ = 1.0)  
20 A, 240 VAC (cosϕ = 0.4)  
G7L-2A-P  
20 A, 240 VAC (cosϕ = 1.0)  
20 A, 240 VAC (cosϕ = 0.4)  
Engineering Data  
G7L-1A-T/G7L-1A-B  
Maximum Switching Power  
Endurance  
AC resistive load  
AC inductive load  
(cosφ = 0.4)  
220 VAC resistive load  
220 VAC  
inductive load  
(cosφ = 0.4)  
Switching voltage (V)  
Switching current (A)  
G7L-2A-T/G7L-2A-B  
Maximum Switching Power  
Endurance  
AC resistive load  
AC inductive load  
(cosφ = 0.4)  
220 VAC resistive load  
220 VAC  
inductive load  
(cosφ = 0.4)  
Switching current (A)  
Switching voltage (V)  
470  
General Purpose Relay – G7L  
Engineering Data  
G7L-1A-P/G7L-2A-P  
Maximum Switching Power  
Endurance  
AC resistive load  
AC inductive load  
(cosφ = 0.4)  
220 VAC resistive load  
220 VAC  
inductive load  
(cosφ = 0.4)  
Switching current (A)  
Switching voltage (V)  
Dimensions  
Note: 1. All units are in millimetres unless otherwise indicated.  
2. E-brackets are sold separately.  
Quick-connect Terminals with E-bracket  
G7L-1A-T  
Terminal Arrangement/  
Internal Connections  
(Top View)  
Mounting Holes  
Two, 4.5-dia. hole or  
M4 tapped holes  
G7L-2A-T  
G7L-1A-TJ  
with Test Button  
471  
General Purpose Relay – G7L  
Quick-connect Terminals with E-bracket (contd)  
G7L-2A-TJ  
with Test Button  
Quick-connect Terminals with DIN Track Mounting Adapter  
Note: 1. The DIN Track Mounting Adapter and DIN tracks are sold separately.  
2. The DIN Track Mounting Adapter can be track-mounted or screw-mounted.  
P7LF-D  
G7L-1A-T  
PFP-@N  
Terminal Arrangement/ Mounting Holes  
G7L  
Internal Connections  
(Top View)  
Two, M4 or  
4.5-dia. holes  
51.5 max.  
0
1
4
6
40 0.1  
55.5 max.  
63 max.  
66.5 max.  
5
G7L-2A-T  
Terminal Arrangement/  
Internal Connections  
(Top View)  
Mounting Holes  
PFP-@N  
P7LF-D  
G7L  
Two, M4 or  
4.5-dia. holes  
0
2
1
8
51.5 max.  
4
6
40 0.1  
55.5 max.  
63 max.  
5
66.5 max.  
G7L-1A-TJ  
with Test Button  
P7LF-D  
PFP-@N  
G7L  
0
1
51.5 max.  
4
6
2
Test button  
55.5 max.  
63 max.  
5
66.5 max.  
G7L-2A-TJ  
with Test Button  
P7LF-D  
PFP-@N  
G7L  
0
2
1
8
51.5 max.  
4
6
2
Test button  
63 max.  
55.5 max.  
5
66.5 max.  
472  
General Purpose Relay – G7L  
Quick-connect Terminals with Front-connecting Socket  
Note: 1. The Front-connecting Socket and DIN tracks are sold separately.  
2. The Front-connecting Socket can be track-mounted or screw-mounted.  
Two, M3.5 screws  
for coil  
G7L-1A-T  
Terminal Arrangement/  
Internal Connections  
(Top View)  
Mounting Holes  
P7LF-06  
PFP-@N  
G7L  
Two, M4 or  
4.5-dia. holes  
51.5 max.  
0
1
40 0.1  
4
6
55.5 max.  
Four, M4 screws  
61.5 max.  
65 max.  
5
for contact  
G7L-2A-T  
Two, M3.5 screws  
for coil  
P7LF-06  
PFP-@N  
G7L  
0
2
1
8
51.5 max.  
4
6
55.5 max.  
61.5 max.  
65 max.  
5
Four, M4 screws  
for contact  
Two, M3.5 screws  
for coil  
G7L-1A-TJ  
with Test Button  
P7LF-06  
PFP-@N  
Terminal Arrangement/ Mounting Holes  
Internal Connections  
(Top View)  
G7L  
51.5 max.  
Two, M4 or  
4.5-dia. holes  
0
1
2
Test button  
4
6
40 0.1  
55.5 max.  
61.5 max.  
65 max.  
5
Two, M4 screws  
for contact  
P7LF-06  
Two, M3.5 screws  
for coil  
G7L-2A-TJ  
with Test Button  
PFP-@N  
G7L  
51.5 max.  
0
2
1
8
4
6
2
Test button  
61.5 max.  
65 max.  
55.5 max.  
5
Four, M4 screws  
for contact  
473  
General Purpose Relay – G7L  
Quick-connect Terminals with Upper Bracket  
G7L-1A-TUB  
Mounting Holes  
Terminal Arrangement/  
Internal Connections  
(Top View)  
Two, 4.5-dia. hole or  
M4 tapped holes  
G7L-2A-TUB  
Terminal Arrangement/  
Internal Connections  
(Top View)  
G7L-1A-TUBJ  
with Test Button  
Terminal Arrangement/  
Internal Connections  
(Top View)  
Test button  
G7L-2A-TUBJ  
with Test Button  
Terminal Arrangement/  
Internal Connections  
(Top View)  
Mounting Holes  
Two, 4.5-dia. hole or  
M4 tapped holes  
Test button  
Screw Terminals with E-bracket  
Note: E-brackets are sold separately.  
G7L-1A-B  
Two, M4 screws  
for contact  
Two, M3.5 screws  
for coil  
Mounting Holes  
Terminal Arrangement/  
Internal Connections  
(Top View)  
Two, 4.5-dia. hole  
or M4 tapped holes  
474  
General Purpose Relay – G7L  
Screw Terminals with E-bracket (contd)  
E-brackets are sold separately.  
G7L-2A-B  
Four, M4 screws  
for contact  
Two, M3.5 screws  
for coil  
G7L-1A-BJ  
with Test Button  
Two, M4 screws  
for contact  
Two, M3.5 screws  
for coil  
Test button  
G7L-2A-BJ  
with Test Button  
Two, M3.5 screws  
for coil  
Four, M4 screws  
for contact  
Test button  
Screw Terminals with DIN Track Mounting Adapter  
Note: 1. The DIN Track Mounting Adapter and DIN tracks are sold separately.  
2. The DIN Track Mounting Adapter can be track-mounted or screw-mounted.  
P7LF-D  
G7L-1A-B  
PFP-@N  
Terminal Arrangement/  
Mounting Holes  
G7L  
Internal Connections  
(Top View)  
Two, M4 or  
4.5-dia. holes  
51.5 max.  
0
1
4
6
40 0.1  
65.5 max.  
69 max.  
55.5 max.  
5
G7L-2A-B  
P7LF-D  
PFP-@N  
G7L  
51.5 max.  
0
2
1
8
4
6
55.5 max.  
65.5 max.  
69 max.  
5
475  
General Purpose Relay – G7L  
Screw Terminals with DIN Track Mounting Adapter (contd)  
Note: 1. The DIN Track Mounting Adapter and DIN tracks are sold separately.  
2. The DIN Track Mounting Adapter can be track-mounted or screw-mounted.  
P7LF-D  
G7L-1A-BJ  
with Test Button  
PFP-@N  
G7L  
51.5 max.  
0
1
4
6
2
Test button  
65.5 max.  
55.5 max.  
5
69 max.  
G7L-2A-BJ  
with Test Button  
P7LF-D  
PFP-@N  
G7L  
0
2
1
8
51.5 max.  
4
6
2
Test button  
55.5 max.  
65.5 max.  
69 max.  
5
Screw Terminals with Upper Bracket  
G7L-1A-BUB  
Two, M3.5 screws  
for coil  
Two, M4 screwsTerminal Arrangement/ Mounting Holes  
Internal Connections  
for contact  
Two, 4.5-dia. hole  
(Top View)  
or M4 tapped holes  
G7L-2A-BUB  
Two, M3.5 screws  
for coil  
Four, M4 screws  
for contact  
Mounting Holes  
Terminal Arrangement/  
Internal Connections  
(Top View)  
Two, 4.5-dia. hole  
or M4 tapped holes  
G7L-1A-BUBJ  
with Test Button  
Two, M3.5 screws  
for coil  
Two, M4 screws  
for contactTerminal Arrangement/  
Internal Connections  
(Top View)  
Test button  
476  
General Purpose Relay – G7L  
Screw Terminals with Upper Bracket (contd)  
G7L-2A-BUBJ  
with Test Button  
Two, M3.5 screws  
for coil  
Four, M4 screws  
for contact  
Terminal Arrangement/  
Internal Connections  
(Top View)  
Test button  
PCB Terminals with PCB Mounting  
G7L-1A-P  
Mounting Holes  
(Bottom View)  
Terminal Arrangement/  
Internal Connections  
(Top View)  
G7L-2A-P  
Mounting Holes  
(Bottom View)  
Terminal Arrangement/  
Internal Connections  
(Top View)  
Two, 4.5-dia.  
holes  
R99-07G5D  
E-bracket  
40  
Mounting Holes  
(Bottom View)  
26 24 17.8  
Two, M4 or  
4.5-dia. holes  
46  
10  
3
24  
7
19.7  
40+0.1  
5
5
30  
50  
4.4  
Mounting Holes  
(Bottom View)  
P7LF-D Adapter  
Two, M4 or  
4.5-dia. holes  
51.5 max.  
14.5  
5
40+0.1  
40 0.1  
35.2 max.  
55.5 max.  
477  
General Purpose Relay – G7L  
PCB Terminals with PCB Mounting (contd)  
P7LF-06  
Front-connecting  
Socket  
Two, M3.5 screws  
for coil  
8
Mounting Holes  
(Bottom View)  
Two, M4 or  
4.5-dia. holes  
51.5 max.  
Four, M4 screws  
for contact  
40 0.1  
9.2  
25  
46 max.  
5
40 0.1  
55.5 max.  
P7LF-C Cover  
34.5 max.  
Put the P7LF-C cover onto the terminals in order  
to protect the user from electric shock.  
1
50.5 max.  
6 max.  
Internal Coil Circuit  
DC Operating Coil  
AC Operating Coil  
478  
General Purpose Relay – G7L  
Precautions  
HANDLING  
RATED CURRENT FLOW  
To preserve performance, do not drop or otherwise subject the  
Power Relay to shock.  
• When using B-series (screw) products, the rated current from  
the screw terminals (M4) should be 20 A or less according to jet  
standard (electrical appliance and material control law of  
Japan).  
• The case is not designed to be removed during normal handling  
and operation. Doing so may affect performance.  
• Use the Power Relay in a dry environment free from excessive  
dust, SO2, H2S, or organic gas.  
OPERATING COIL  
• As a rule, either a DC battery or a DC power supply with a  
maximum of 5% ripple must be used for the operating voltage  
for DC Relays. Before using a rectified AC supply, confirm that  
the ripple is not greater than 5%. Ripple greater than this can  
lead to variations in the operating and reset voltages.  
• Do not allow a voltage greater than the maximum allowable coil  
voltage to be applied continuously.  
• Do not use the Power Relay outside of specified voltages and  
currents.  
• Do not allow the ambient operating temperature to exceed the  
specified limit.  
As excessive ripple can generate pulses, the insertion of a  
smoothing capacitor is recommended as shown below.  
INSTALLATION  
• Although there are not specific limits on the installation site, it  
should be as dry and dust-free as possible.  
Smoothing  
capacitor  
Relay  
• PCB Terminal-equipped Relays weigh approximately 100 g. Be  
sure that the PCB is strong enough to support them. We  
recommend dual-side through-hole PCBs to reduce solder  
cracking from heat stress.  
Ripple  
• Quick-connect terminals can be connected to Faston  
receptacle #250 and positive-lock connectors.  
DC fraction  
E mean  
E min.  
E max.  
• Allow suitable slack on leads when wiring, and do not subject  
the terminals to excessive force.  
• G7L Relays with test buttons must be mounted facing down.  
E max. E min.  
% of ripple =  
x 100  
E mean  
• Be careful not to touch the test button accidentally. Doing so  
may turn ON the contact.  
E max.: Max. ripple  
E min.: Min. ripple  
E mean: Mean DC value  
• Use the test button only to check the electrical conductivity. Do  
not switch the load directly by pushing the test button.  
CLEANING PCB TERMINALS  
• PCB terminals have flux-tight construction which prevents flux  
from penetrating into the Relay base housing, e.g., due to  
capillary action up the terminals when Relay is soldered onto the  
PCB. This type of Relay cannot be immersed for cleaning.  
• When driving  
connect a bleeder resistor if necessary.  
a transistor, check the leakage current and  
DIN TRACK MOUNTING ADAPTER AND  
FRONT-CONNECTING SOCKET  
CONNECTING  
DIN Track Mounting  
• Use a DIN-conforming 50-cm track or 1-m track (both are sold  
separately) for mounting a number of G7L Relays.  
• Refer to the following table when connecting a wire with a  
crimp-style terminal to the G7L.  
• Cut and shorten the track to an appropriate length if the required  
track length is less than 50 cm.  
Terminals  
Screw  
terminals  
Front-connecting  
Socket  
• The DIN Track Mounting Adapter and Front-connecting Socket  
can be mounted on the G7L with just one hand and dismounted  
with ease by using a screwdriver.  
Coil  
8
8
6.5  
5.3  
5.8  
To support the G7L mounted on a DIN Track Mounting Adapter  
or Front-connecting Socket, use the PFP-M End Plate. Put the  
End Plate onto the DIN Track Mounting Adapter or Front-  
connecting Socket so that the surface mark of the End Plate  
faces upwards. Then tighten the screw of the End Plate securely  
with a screwdriver.  
5
M3.5  
M4  
M3.5  
M4  
Contact  
5.5  
6.5  
5.5  
7
Screw Mounting  
• Screw-mount the DIN Track Mounting Adapter or Front-  
connecting Socket securely after opening screw mounting holes  
on them.  
9.2  
9.2  
• When cutting or opening holes on the panel after the Front-  
connecting Socket is mounted, take proper measures so that  
the cutting chips will not fall onto the Relay terminals. When  
cutting or opening holes on the upper part of the panel, mask  
the Front-connecting Socket properly with a cover.  
CAT. No. J055-E2-04  
479  

相关型号:

G7L-1A-BUBJ200/240VAC

Power/Signal Relay, SPST, Momentary, 2448mW (Coil), AC Input, AC Output, Panel Mount
OMRON

G7L-1A-BUBJ48VDC

Power/Signal Relay, SPST, Momentary, 0.04A (Coil), 48VDC (Coil), 1900mW (Coil), DC Input, AC Output, Panel Mount,
OMRON

G7L-1A-BUBJ50VAC

Power/Signal Relay, SPST, Momentary, 1700mW (Coil), AC Input, AC Output, Panel Mount
OMRON

G7L-1A-BUBJDC12

Power/Signal Relay
OMRON

G7L-1A-BUBJDC48

Power/Signal Relay
OMRON

G7L-1A-BUBJDC6

Power/Signal Relay,
OMRON