G7SA-3A3B110VDC [OMRON]

Power/Signal Relay, 6PST, Momentary, 0.005A (Coil), 110VDC (Coil), 580mW (Coil), 6A (Contact), 125VDC (Contact), DC Input, AC/DC Output, Through Hole-Straight Mount,;
G7SA-3A3B110VDC
型号: G7SA-3A3B110VDC
厂家: OMRON ELECTRONICS LLC    OMRON ELECTRONICS LLC
描述:

Power/Signal Relay, 6PST, Momentary, 0.005A (Coil), 110VDC (Coil), 580mW (Coil), 6A (Contact), 125VDC (Contact), DC Input, AC/DC Output, Through Hole-Straight Mount,

文件: 总7页 (文件大小:578K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
GRela7ysSwithAForcibly Guided Contacts  
CSM_G7SA_DS_E_6_1  
Compact, Slim Relays Conforming to  
EN Standards  
• Relays with forcibly guided contacts  
(EN50205 Class A, certified by VDE).  
• Supports the CE marking of machinery (Machinery  
Directive).  
• Helps avoid hazardous machine status when used as part of  
an interlocking circuit.  
• Four-pole and six-pole Relays are available.  
• The Relay’s terminal arrangement simplifies PWB pattern  
design.  
• Reinforced insulation between inputs and outputs.  
Reinforced insulation between some poles of  
different polarity.  
Be sure to read the “Safety Precautions” on page 6 and the  
“Precautions for All Relays with Forcibly Guided Contacts”.  
Model Number Structure  
Model Number Legend  
G7SA-@A@B  
1
2
1. NO Contact Poles  
2: DPST-NO  
2. NC Contact Poles  
1: SPST-NC  
2: DPST-NC  
3: 3PST-NC  
3: 3PST-NO  
4: 4PST-NO  
5: 5PST-NO  
Ordering Information  
Relays with Forcibly Guided Contacts  
Type  
Sealing  
Poles  
Contact configuration  
3PST-NO, SPST-NC  
DPST-NO, DPST-NC  
5PST-NO, SPST-NC  
4PST-NO, DPST-NC  
3PST-NO, 3PST-NC  
Rated voltage  
Model  
G7SA-3A1B  
G7SA-2A2B  
G7SA-5A1B  
G7SA-4A2B  
G7SA-3A3B  
12 VDC  
18 VDC  
21 VDC  
24 VDC  
48 VDC  
110 VDC  
4 poles  
Standard  
Flux-tight  
6 poles  
Sockets  
Type  
LED indicator  
Poles  
Rated voltage  
Model  
4 poles  
6 poles  
4 poles  
6 poles  
4 poles  
6 poles  
P7SA-10F  
No  
---  
P7SA-14F  
Track-mounting  
Back-mounting  
Track mounting and screw mounting possible  
PCB terminals  
P7SA-10F-ND  
P7SA-14F-ND  
P7SA-10P  
P7SA-14P  
24 VDC  
110 VDC  
Yes  
No  
---  
1
G7SA  
Specifications  
Ratings  
Coil (4 poles)  
Item  
Rated current  
(mA)  
Coil resistance  
Must operate  
voltage (V)  
Must release  
voltage (V)  
Max.  
voltage (V)  
Power consumption  
Rated voltage  
(Ω)  
(mW)  
12 VDC  
18 VDC  
21 VDC  
24 VDC  
48 VDC  
110 VDC  
30  
400  
900  
20  
17.1  
15  
1,225  
1,600  
6,400  
28,810  
Approx.360  
Approx. 420  
75% max.  
10% min.  
110%  
7.5  
3.8  
Coil (6 poles)  
Item  
Rated current  
(mA)  
Coil resistance  
Must operate  
voltage (V)  
Must release  
voltage (V)  
Max.  
voltage (V)  
Power consumption  
(mW)  
Rated voltage  
(Ω)  
12 VDC  
18 VDC  
21 VDC  
24 VDC  
48 VDC  
110 VDC  
41.7  
27.8  
23.8  
20.8  
10.4  
5.3  
288  
648  
882  
Approx.500  
75% max.  
10% min.  
110%  
1,152  
4,606  
20,862  
Approx. 580  
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of ±15%.  
2. Performance characteristics are based on a coil temperature of 23°C.  
3. The maximum voltage is based on an ambient operating temperature of 23°C maximum.  
Contacts  
Item  
Load  
Resistive load  
Rated load  
6 A at 250 VAC, 6 A at 30 VDC  
Rated carry current  
Max. switching voltage  
Max. switching current  
6 A  
250 VAC, 125 VDC  
6 A  
Characteristics of Sockets  
Model  
Continuous current  
Dielectric strength  
Insulation resistance  
P7SA-1@  
6 A *1  
2,500 VAC for 1 min. between poles  
1,000 MΩ min. *2  
Note: Use the P7SA-1@F-ND in the ambient temperature range of 20 to 70°C.  
Use the P7SA-1@F and P7SA-1@F-ND in the ambient humidity range of 45 to 85%.  
*1. When operating the P7SA-1  
@
@
F at a temperature between 55 and 85°C, reduce the continuous current (6 A at 55  
°
C or less) by 0.1 A for each degree above 55°C.  
When operating the P7SA-1  
F-ND at a temperature between 50 and 70°C, reduce the continuous current (6 A at 50°C or less) by 0.3 A for each degree above 50°C.  
*2. Measurement conditions: Measurement of the same points as for the dielectric strength at 500 VDC.  
Characteristics  
Contact resistance *1  
Operating time *2  
Response time *3  
Release time *2  
100 mΩ max.  
20 ms max.  
10 ms max.  
20 ms max.  
Mechanical  
Rated load  
36,000 operations/h  
1,800 operations/h  
1,000 MΩ min.  
Maximum operating  
frequency  
Note: The above values are initial values.  
*1. The contact resistance was measured with 1 A at 5  
VDC using the voltage-drop method.  
Insulation resistance *4  
*2. These times were measured at the rated voltage and  
an ambient temperature of 23°C. Contact bounce  
time is not included.  
Between coil contacts/different poles (except for poles 3-4 in  
4-pole Relays and poles 3-5, 4-6, and 5-6 in 6-pole Relays):  
4,000 VAC, 50/60 Hz for 1 min.  
Between different poles (poles 3-4 in 4-pole Relays and poles  
3-5, 4-6, and 5-6 in 6-pole Relays):  
*3. The response time is the time it takes for the normally  
open contacts to open after the coil voltage is turned  
OFF. Contact bounce time is  
Dielectric strength *5 *6  
included. Measurement conditions: Rated voltage  
operation, Ambient temperature: 23°C  
2,500 VAC, 50/60 Hz for 1 min.  
Between contacts of same polarity: 1,500 VAC, 50/60 Hz for 1 min.  
*4. The insulation resistance was measured with a 500-  
VDC megohmmeter at the same locations as the  
dielectric strength was measured.  
10 to 55 to 10 Hz, 0.75-mm single amplitude  
(1.5-mm double amplitude)  
Vibration resistance  
*5. Pole 3 refers to terminals 31-32 or 33-34, pole 4  
refers to terminals 43-44, pole 5 refers to terminals  
53-54, and pole 6 refers to terminals 63-64.  
*6. When using a P7SA Socket, the dielectric strength  
between coil contacts/different poles is 2,500 VAC,  
50/60 Hz for 1 min.  
Destruction  
1,000 m/s2  
100 m/s2  
Shock resistance  
Malfunction  
10,000,000 operations min.  
(at approx. 36,000 operations/h)  
Mechanical  
*7. The durability is for an ambient temperature of 15 to  
Durability *7  
100,000 operations min.  
(at the rated load and approx. 1,800 operations/h)  
35×C and an ambient humidity of 25% to 75%.  
*8. The failure rate is based on an operating frequency  
of 300 operations/min.  
Electrical  
Failure rate (P level)  
(reference value *8)  
*9. 12 to 48 VDC:  
5 VDC, 1 mA  
When operating between 70 and 85°C, reduce the  
rated carry current of 6 A by 0.1 A for each degree  
above 70°C.  
12 to 48 VDC: -40 to 85°C (with no icing or condensation)  
110 VDC:  
Ambient operating temperature *9  
Ambient operating humidity  
Weight  
-40 to 60°C (with no icing or condensation)  
110 VDC:  
5% to 85%  
When operating between 40 and 60°C, reduce the  
rated carry current of 6 A by 0.27 A for each degree  
above 40°C.  
4 poles: Approx. 22 g  
6 poles: Approx. 25 g  
2
G7SA  
Engineering Data  
Durability Curve  
1,000  
700  
500  
DC1, 24 VDC  
300  
AC1, 240 VAC  
100  
70  
50  
DC13, 24 VDC  
30  
AC15, 240 VAC  
10  
7
5
3
1
0.1  
0.3 0.5 0.7  
1
3
5
7
10  
Contact current (A)  
Dimensions  
(Unit: mm)  
Relays with Forcibly Guided Contacts  
G7SA-3A1B  
G7SA-2A2B  
Terminal Arrangement/  
Internal Connection Diagram  
(Bottom View)  
Printed Circuit Board  
Design Diagram  
(Bottom View)  
(±0.1 tolerance)  
G7SA-3A1B  
13 max.  
40 max.  
Ten, 1.4 dia.  
24 max.  
0.5  
1
0.5  
3.5  
Note: 1. Terminals 23-24, 33-34,  
and 43-44 are normally  
G7SA-2A2B  
open. Terminals 11-12 and  
21-22 are normally closed.  
2. The colors of the cards  
inside the Relays are as  
follows: G7SA-3A1B: Blue  
and G7SA-2A2B: White.  
G7SA-5A1B  
G7SA-4A2B  
G7SA-3A3B  
Terminal Arrangement/  
Internal Connection Diagram  
(Bottom View)  
Printed Circuit Board  
Design Diagram  
(Bottom View)  
(±0.1 tolerance)  
G7SA-5A1B  
Fourteen, 1.4 dia.  
13 max.  
50 max.  
24 max.  
3.5  
0.5  
G7SA-4A2B  
0.5  
1
Note: 1. Terminals 23-24, 33-34,  
43-44, 53-54, and 63-64  
are normally open.  
Terminals 11-12, 21-22,  
and 31-32 are normally  
closed.  
G7SA-3A3B  
2. The colors of the cards  
inside the Relays are as  
follows: G7SA-5A1B: Blue,  
G7SA-4A2B: White, and  
G7SA-3A3B: Yellow.  
3
G7SA  
Sockets  
Track-mounting Socket  
P7SA-10F, P7SA-10F-ND  
Terminal Arrangement/Internal Connection Diagram  
(Top View)  
G7SA-3A1B  
Mounted  
G7SA-2A2B  
Mounted  
44 33 34  
44 33 34  
43  
24  
43  
22  
*
*
23  
12  
21  
12  
*
This display circuit is  
available only for  
"-ND" models.  
11  
1
0
11  
1
0
22.5 max.  
2R  
60.5 max.  
Note: Terminals 23-24,  
33-34, and 43-44  
are normally  
Ten,  
M3 × 8  
9 max.  
5
open. Terminals  
11-12 and 21-22  
are normally  
Mounting Hole Placement Diagram  
(Top View)  
14.5±0.2  
closed.  
Two, 4 dia. or M3.5  
72 max.  
LED  
indicator  
80±0.2  
9 max.  
4 dia.  
Note 1: The socket is shown with the finger cover removed.  
2: Only the -ND Sockets have LED indicators (orange)  
Track-mounting Socket  
P7SA-14F, P7SA-14F-ND  
Terminal Arrangement/Internal Connection Diagram  
(Top View)  
G7SA-5A1B  
Mounted  
G7SA-4A2B  
Mounted  
G7SA-3A3B  
Mounted  
64  
63  
44  
54  
53  
34  
64  
63  
44  
54  
53  
34  
64  
63  
44  
54  
53  
32  
*
*
*
43  
24  
23  
33  
12  
11  
43  
22  
21  
33  
12  
11  
43  
22  
21  
31  
12  
11  
2R  
60.5 max.  
30 max.  
Fourteen,  
1
0
1
0
1
0
M3 × 8  
9 max.  
5
Mounting Hole Placement Diagram  
*
This display circuit is  
available only for  
"-ND" models.  
(Top View)  
22±0.2  
Two, 4 dia. or M3.5  
Note: Terminals 23-24,  
33-34, 43-44,  
72 max.  
LED  
indicator  
53-54, and 63-64  
are normally open.  
Terminals 11-12,  
21-22, and 31-32  
are normally  
closed.  
80±0.2  
9 max.  
4 dia.  
Note 1: The socket is shown with the finger cover removed.  
2: Only the -ND Sockets have LED indicators (orange).  
4
G7SA  
Back-mounting Socket (for PCB)  
P7SA-10P  
0.5  
50 max.  
0.5  
Terminal Arrangement/Internal Mounting Hole Placement  
Connection Diagram  
(Bottom View)  
(Bottom View)  
15 max.  
(±0.1 tolerance)  
G7SA-3A1B Mounted  
11 12  
33 34  
0
1
Three, 3.2 dia.  
(for M3 tapping screws)  
41.5 max.  
23 24  
43 44  
G7SA-2A2B Mounted  
0
11 12  
33 34  
3.5  
Ten, 1.1 dia.  
(11.1)  
4.1  
0.4 (11.1)  
1
21 22  
43 44  
Three, 2.6 dia.  
(for M3 tapping screws)  
Note: Terminals 23-24, 33-34, and 43-44  
are normally open. Terminals 11-12  
and 21-22 are normally closed.  
24.8  
39.9  
Back-mounting Socket (for PCB)  
P7SA-14P  
Terminal Arrangement/Internal  
Connection Diagram  
(Bottom View)  
Mounting Hole Placement  
(Bottom View)  
0.5  
60 max.  
0.5  
(±0.1 tolerance)  
15 max.  
G7SA-5A1B Mounted  
0
11 12  
33 34 53 54  
Three, 3.2 dia.  
(for M3 tapping  
screws)  
Fourteen,  
1.1 dia.  
1
23 24  
43 44 63 64  
41.5 max.  
G7SA-4A2B Mounted  
0
11 12  
33 34 53 54  
0.4  
3.5  
(11.1)  
(11.1)  
1
21 22  
43 44 63 64  
Three, 2.6 dia.  
(for M3 tapping screws)  
G7SA-3A3B Mounted  
Note: Terminals 23-24, 33-34, 43-44,  
53-54, and 63-64 are normally  
open. Terminals 11-12, 21-22,  
and 31-32 are normally closed.  
0
11 12  
31 32 53 54  
4.1  
24.8  
1
21 22  
43 44 63 64  
49.9  
Certified Standards  
Forcibly Guided Contacts (from EN50205)  
G7SA  
If an NO contact becomes welded, all NC contacts will maintain a  
minimum distance of 0.5 mm when the coil is not energized. Likewise  
if an NC contact becomes welded, all NO contacts will maintain a  
minimum distance of 0.5 mm when the coil is energized.  
EN Standards, VDE Certified  
EN61810-1 (Electromechanical non-specified time all-or-nothing  
relays)  
EN50205 (Relays with forcibly guided (linked) contacts)  
UL standard UL508 Industrial Control Devices  
CSA standard CSA C22.2 No. 14 Industrial Control Devices  
5
G7SA  
Safety Precautions  
Refer to the “Precautions for All Relays” and “Precautions for All Relays with Forcibly Guided Contacts”.  
Precautions for Correct Use  
Wiring  
Use one of the following wires to connect to the  
P7SA-10F/10F-ND/14F/14F-ND.  
Stranded wire: 0.75 to 1.5 mm2  
Solid wire:  
1.0 to 1.5 mm2  
Tighten each screw of the P7SA-10F/10F-ND/14F/14F-ND to a  
torque of 0.78 to 0.98 N·m.  
Wire the terminals correctly with no mistakes in coil polarity,  
otherwise the G7SA will not operate.  
Cleaning  
The G7SA is not of enclosed construction. Therefore, do not wash the  
G7SA with water or detergent.  
6
Read and Understand This Catalog  
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or  
comments.  
Warranty and Limitations of Liability  
WARRANTY  
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)  
from date of sale by OMRON.  
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR  
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS  
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER  
WARRANTIES, EXPRESS OR IMPLIED.  
LIMITATIONS OF LIABILITY  
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS  
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT  
LIABILITY.  
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.  
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS  
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT  
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.  
Application Considerations  
SUITABILITY FOR USE  
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's  
application or use of the products.  
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the  
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,  
machine, system, or other application or use.  
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible  
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:  
·
·
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.  
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,  
safety equipment, and installations subject to separate industry or government regulations.  
·
Systems, machines, and equipment that could present a risk to life or property.  
Please know and observe all prohibitions of use applicable to the products.  
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE  
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND  
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.  
PROGRAMMABLE PRODUCTS  
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.  
Disclaimers  
CHANGE IN SPECIFICATIONS  
Product specifications and accessories may be changed at any time based on improvements and other reasons.  
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.  
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or  
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual  
specifications of purchased products.  
DIMENSIONS AND WEIGHTS  
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.  
PERFORMANCE DATA  
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the  
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON  
Warranty and Limitations of Liability.  
ERRORS AND OMISSIONS  
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,  
typographical, or proofreading errors, or omissions.  
2010.11  
In the interest of product improvement, specifications are subject to change without notice.  
OMRON Corporation  
Industrial Automation Company  
http://www.ia.omron.com/  
(c)Copyright OMRON Corporation 2010 All Right Reserved.  

相关型号:

G7SA-3A3B12VDC

Power/Signal Relay, 6PST, Momentary, 0.042A (Coil), 12VDC (Coil), 500mW (Coil), 6A (Contact), 125VDC (Contact), DC Input, AC/DC Output, Through Hole-Straight Mount,
OMRON

G7SA-3A3B24VDC

Power/Signal Relay, 6PST, Momentary, 0.021A (Coil), 24VDC (Coil), 500mW (Coil), 6A (Contact), 125VDC (Contact), DC Input, AC/DC Output, Through Hole-Straight Mount,
OMRON

G7SA-3A3BDC24

Compact, Slim Relays Conforming to EN Standards
OMRON

G7SA-4A2B

Compact, Slim Relays Conforming to EN Standards
OMRON

G7SA-4A2B21VDC

Power/Signal Relay, 6PST, Momentary, 0.024A (Coil), 21VDC (Coil), 500mW (Coil), 6A (Contact), 125VDC (Contact), DC Input, AC/DC Output, Through Hole-Straight Mount,
OMRON

G7SA-4A2BDC24

Compact, Slim Relays Conforming to EN Standards
OMRON

G7SA-5A1B

Compact, Slim Relays Conforming to EN Standards
OMRON

G7SA-5A1B21VDC

Power/Signal Relay, 6PST, Momentary, 0.024A (Coil), 21VDC (Coil), 500mW (Coil), 6A (Contact), 125VDC (Contact), DC Input, AC/DC Output, Through Hole-Straight Mount,
OMRON

G7SA-5A1B48VDC

Power/Signal Relay, 6PST, Momentary, 0.011A (Coil), 48VDC (Coil), 500mW (Coil), 6A (Contact), 125VDC (Contact), DC Input, AC/DC Output, Through Hole-Straight Mount,
OMRON

G7SA-5A1BDC24

Compact, Slim Relays Conforming to EN Standards
OMRON

G7SB-2A2B

Power/Signal Relay
OMRON

G7SB-2A2BDC24

Power/Signal Relay, 4PST, Momentary, 0.015A (Coil), 24VDC (Coil), 360mW (Coil), 6A (Contact), 125VDC (Contact), DC Input, AC/DC Output, Through Hole-Straight Mount