G7SA-3A3B110VDC [OMRON]
Power/Signal Relay, 6PST, Momentary, 0.005A (Coil), 110VDC (Coil), 580mW (Coil), 6A (Contact), 125VDC (Contact), DC Input, AC/DC Output, Through Hole-Straight Mount,;型号: | G7SA-3A3B110VDC |
厂家: | OMRON ELECTRONICS LLC |
描述: | Power/Signal Relay, 6PST, Momentary, 0.005A (Coil), 110VDC (Coil), 580mW (Coil), 6A (Contact), 125VDC (Contact), DC Input, AC/DC Output, Through Hole-Straight Mount, |
文件: | 总7页 (文件大小:578K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
GRela7ysSwithAForcibly Guided Contacts
CSM_G7SA_DS_E_6_1
Compact, Slim Relays Conforming to
EN Standards
• Relays with forcibly guided contacts
(EN50205 Class A, certified by VDE).
• Supports the CE marking of machinery (Machinery
Directive).
• Helps avoid hazardous machine status when used as part of
an interlocking circuit.
• Four-pole and six-pole Relays are available.
• The Relay’s terminal arrangement simplifies PWB pattern
design.
• Reinforced insulation between inputs and outputs.
Reinforced insulation between some poles of
different polarity.
Be sure to read the “Safety Precautions” on page 6 and the
“Precautions for All Relays with Forcibly Guided Contacts”.
Model Number Structure
Model Number Legend
G7SA-@A@B
1
2
1. NO Contact Poles
2: DPST-NO
2. NC Contact Poles
1: SPST-NC
2: DPST-NC
3: 3PST-NC
3: 3PST-NO
4: 4PST-NO
5: 5PST-NO
Ordering Information
Relays with Forcibly Guided Contacts
Type
Sealing
Poles
Contact configuration
3PST-NO, SPST-NC
DPST-NO, DPST-NC
5PST-NO, SPST-NC
4PST-NO, DPST-NC
3PST-NO, 3PST-NC
Rated voltage
Model
G7SA-3A1B
G7SA-2A2B
G7SA-5A1B
G7SA-4A2B
G7SA-3A3B
12 VDC
18 VDC
21 VDC
24 VDC
48 VDC
110 VDC
4 poles
Standard
Flux-tight
6 poles
Sockets
Type
LED indicator
Poles
Rated voltage
Model
4 poles
6 poles
4 poles
6 poles
4 poles
6 poles
P7SA-10F
No
---
P7SA-14F
Track-mounting
Back-mounting
Track mounting and screw mounting possible
PCB terminals
P7SA-10F-ND
P7SA-14F-ND
P7SA-10P
P7SA-14P
24 VDC
110 VDC
Yes
No
---
1
G7SA
Specifications
Ratings
Coil (4 poles)
Item
Rated current
(mA)
Coil resistance
Must operate
voltage (V)
Must release
voltage (V)
Max.
voltage (V)
Power consumption
Rated voltage
(Ω)
(mW)
12 VDC
18 VDC
21 VDC
24 VDC
48 VDC
110 VDC
30
400
900
20
17.1
15
1,225
1,600
6,400
28,810
Approx.360
Approx. 420
75% max.
10% min.
110%
7.5
3.8
Coil (6 poles)
Item
Rated current
(mA)
Coil resistance
Must operate
voltage (V)
Must release
voltage (V)
Max.
voltage (V)
Power consumption
(mW)
Rated voltage
(Ω)
12 VDC
18 VDC
21 VDC
24 VDC
48 VDC
110 VDC
41.7
27.8
23.8
20.8
10.4
5.3
288
648
882
Approx.500
75% max.
10% min.
110%
1,152
4,606
20,862
Approx. 580
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of ±15%.
2. Performance characteristics are based on a coil temperature of 23°C.
3. The maximum voltage is based on an ambient operating temperature of 23°C maximum.
Contacts
Item
Load
Resistive load
Rated load
6 A at 250 VAC, 6 A at 30 VDC
Rated carry current
Max. switching voltage
Max. switching current
6 A
250 VAC, 125 VDC
6 A
Characteristics of Sockets
Model
Continuous current
Dielectric strength
Insulation resistance
P7SA-1@
6 A *1
2,500 VAC for 1 min. between poles
1,000 MΩ min. *2
Note: Use the P7SA-1@F-ND in the ambient temperature range of −20 to 70°C.
Use the P7SA-1@F and P7SA-1@F-ND in the ambient humidity range of 45 to 85%.
*1. When operating the P7SA-1
@
@
F at a temperature between 55 and 85°C, reduce the continuous current (6 A at 55
°
C or less) by 0.1 A for each degree above 55°C.
When operating the P7SA-1
F-ND at a temperature between 50 and 70°C, reduce the continuous current (6 A at 50°C or less) by 0.3 A for each degree above 50°C.
*2. Measurement conditions: Measurement of the same points as for the dielectric strength at 500 VDC.
Characteristics
Contact resistance *1
Operating time *2
Response time *3
Release time *2
100 mΩ max.
20 ms max.
10 ms max.
20 ms max.
Mechanical
Rated load
36,000 operations/h
1,800 operations/h
1,000 MΩ min.
Maximum operating
frequency
Note: The above values are initial values.
*1. The contact resistance was measured with 1 A at 5
VDC using the voltage-drop method.
Insulation resistance *4
*2. These times were measured at the rated voltage and
an ambient temperature of 23°C. Contact bounce
time is not included.
Between coil contacts/different poles (except for poles 3-4 in
4-pole Relays and poles 3-5, 4-6, and 5-6 in 6-pole Relays):
4,000 VAC, 50/60 Hz for 1 min.
Between different poles (poles 3-4 in 4-pole Relays and poles
3-5, 4-6, and 5-6 in 6-pole Relays):
*3. The response time is the time it takes for the normally
open contacts to open after the coil voltage is turned
OFF. Contact bounce time is
Dielectric strength *5 *6
included. Measurement conditions: Rated voltage
operation, Ambient temperature: 23°C
2,500 VAC, 50/60 Hz for 1 min.
Between contacts of same polarity: 1,500 VAC, 50/60 Hz for 1 min.
*4. The insulation resistance was measured with a 500-
VDC megohmmeter at the same locations as the
dielectric strength was measured.
10 to 55 to 10 Hz, 0.75-mm single amplitude
(1.5-mm double amplitude)
Vibration resistance
*5. Pole 3 refers to terminals 31-32 or 33-34, pole 4
refers to terminals 43-44, pole 5 refers to terminals
53-54, and pole 6 refers to terminals 63-64.
*6. When using a P7SA Socket, the dielectric strength
between coil contacts/different poles is 2,500 VAC,
50/60 Hz for 1 min.
Destruction
1,000 m/s2
100 m/s2
Shock resistance
Malfunction
10,000,000 operations min.
(at approx. 36,000 operations/h)
Mechanical
*7. The durability is for an ambient temperature of 15 to
Durability *7
100,000 operations min.
(at the rated load and approx. 1,800 operations/h)
35×C and an ambient humidity of 25% to 75%.
*8. The failure rate is based on an operating frequency
of 300 operations/min.
Electrical
Failure rate (P level)
(reference value *8)
*9. 12 to 48 VDC:
5 VDC, 1 mA
When operating between 70 and 85°C, reduce the
rated carry current of 6 A by 0.1 A for each degree
above 70°C.
12 to 48 VDC: -40 to 85°C (with no icing or condensation)
110 VDC:
Ambient operating temperature *9
Ambient operating humidity
Weight
-40 to 60°C (with no icing or condensation)
110 VDC:
5% to 85%
When operating between 40 and 60°C, reduce the
rated carry current of 6 A by 0.27 A for each degree
above 40°C.
4 poles: Approx. 22 g
6 poles: Approx. 25 g
2
G7SA
Engineering Data
Durability Curve
1,000
700
500
DC1, 24 VDC
300
AC1, 240 VAC
100
70
50
DC13, 24 VDC
30
AC15, 240 VAC
10
7
5
3
1
0.1
0.3 0.5 0.7
1
3
5
7
10
Contact current (A)
Dimensions
(Unit: mm)
Relays with Forcibly Guided Contacts
G7SA-3A1B
G7SA-2A2B
Terminal Arrangement/
Internal Connection Diagram
(Bottom View)
Printed Circuit Board
Design Diagram
(Bottom View)
(±0.1 tolerance)
G7SA-3A1B
13 max.
40 max.
Ten, 1.4 dia.
24 max.
0.5
1
0.5
3.5
Note: 1. Terminals 23-24, 33-34,
and 43-44 are normally
G7SA-2A2B
open. Terminals 11-12 and
21-22 are normally closed.
2. The colors of the cards
inside the Relays are as
follows: G7SA-3A1B: Blue
and G7SA-2A2B: White.
G7SA-5A1B
G7SA-4A2B
G7SA-3A3B
Terminal Arrangement/
Internal Connection Diagram
(Bottom View)
Printed Circuit Board
Design Diagram
(Bottom View)
(±0.1 tolerance)
G7SA-5A1B
Fourteen, 1.4 dia.
13 max.
50 max.
24 max.
3.5
0.5
G7SA-4A2B
0.5
1
Note: 1. Terminals 23-24, 33-34,
43-44, 53-54, and 63-64
are normally open.
Terminals 11-12, 21-22,
and 31-32 are normally
closed.
G7SA-3A3B
2. The colors of the cards
inside the Relays are as
follows: G7SA-5A1B: Blue,
G7SA-4A2B: White, and
G7SA-3A3B: Yellow.
3
G7SA
Sockets
Track-mounting Socket
P7SA-10F, P7SA-10F-ND
Terminal Arrangement/Internal Connection Diagram
(Top View)
G7SA-3A1B
Mounted
G7SA-2A2B
Mounted
44 33 34
44 33 34
43
24
43
22
*
*
23
12
21
12
*
This display circuit is
available only for
"-ND" models.
11
1
0
11
1
0
22.5 max.
2R
60.5 max.
Note: Terminals 23-24,
33-34, and 43-44
are normally
Ten,
M3 × 8
9 max.
5
open. Terminals
11-12 and 21-22
are normally
Mounting Hole Placement Diagram
(Top View)
14.5±0.2
closed.
Two, 4 dia. or M3.5
72 max.
LED
indicator
80±0.2
9 max.
4 dia.
Note 1: The socket is shown with the finger cover removed.
2: Only the -ND Sockets have LED indicators (orange)
Track-mounting Socket
P7SA-14F, P7SA-14F-ND
Terminal Arrangement/Internal Connection Diagram
(Top View)
G7SA-5A1B
Mounted
G7SA-4A2B
Mounted
G7SA-3A3B
Mounted
64
63
44
54
53
34
64
63
44
54
53
34
64
63
44
54
53
32
*
*
*
43
24
23
33
12
11
43
22
21
33
12
11
43
22
21
31
12
11
2R
60.5 max.
30 max.
Fourteen,
1
0
1
0
1
0
M3 × 8
9 max.
5
Mounting Hole Placement Diagram
*
This display circuit is
available only for
"-ND" models.
(Top View)
22±0.2
Two, 4 dia. or M3.5
Note: Terminals 23-24,
33-34, 43-44,
72 max.
LED
indicator
53-54, and 63-64
are normally open.
Terminals 11-12,
21-22, and 31-32
are normally
closed.
80±0.2
9 max.
4 dia.
Note 1: The socket is shown with the finger cover removed.
2: Only the -ND Sockets have LED indicators (orange).
4
G7SA
Back-mounting Socket (for PCB)
P7SA-10P
0.5
50 max.
0.5
Terminal Arrangement/Internal Mounting Hole Placement
Connection Diagram
(Bottom View)
(Bottom View)
15 max.
(±0.1 tolerance)
G7SA-3A1B Mounted
11 12
33 34
0
1
Three, 3.2 dia.
(for M3 tapping screws)
41.5 max.
23 24
43 44
G7SA-2A2B Mounted
0
11 12
33 34
3.5
Ten, 1.1 dia.
(11.1)
4.1
0.4 (11.1)
1
21 22
43 44
Three, 2.6 dia.
(for M3 tapping screws)
Note: Terminals 23-24, 33-34, and 43-44
are normally open. Terminals 11-12
and 21-22 are normally closed.
24.8
39.9
Back-mounting Socket (for PCB)
P7SA-14P
Terminal Arrangement/Internal
Connection Diagram
(Bottom View)
Mounting Hole Placement
(Bottom View)
0.5
60 max.
0.5
(±0.1 tolerance)
15 max.
G7SA-5A1B Mounted
0
11 12
33 34 53 54
Three, 3.2 dia.
(for M3 tapping
screws)
Fourteen,
1.1 dia.
1
23 24
43 44 63 64
41.5 max.
G7SA-4A2B Mounted
0
11 12
33 34 53 54
0.4
3.5
(11.1)
(11.1)
1
21 22
43 44 63 64
Three, 2.6 dia.
(for M3 tapping screws)
G7SA-3A3B Mounted
Note: Terminals 23-24, 33-34, 43-44,
53-54, and 63-64 are normally
open. Terminals 11-12, 21-22,
and 31-32 are normally closed.
0
11 12
31 32 53 54
4.1
24.8
1
21 22
43 44 63 64
49.9
Certified Standards
Forcibly Guided Contacts (from EN50205)
G7SA
If an NO contact becomes welded, all NC contacts will maintain a
minimum distance of 0.5 mm when the coil is not energized. Likewise
if an NC contact becomes welded, all NO contacts will maintain a
minimum distance of 0.5 mm when the coil is energized.
• EN Standards, VDE Certified
EN61810-1 (Electromechanical non-specified time all-or-nothing
relays)
EN50205 (Relays with forcibly guided (linked) contacts)
• UL standard UL508 Industrial Control Devices
• CSA standard CSA C22.2 No. 14 Industrial Control Devices
5
G7SA
Safety Precautions
Refer to the “Precautions for All Relays” and “Precautions for All Relays with Forcibly Guided Contacts”.
Precautions for Correct Use
Wiring
• Use one of the following wires to connect to the
P7SA-10F/10F-ND/14F/14F-ND.
Stranded wire: 0.75 to 1.5 mm2
Solid wire:
1.0 to 1.5 mm2
• Tighten each screw of the P7SA-10F/10F-ND/14F/14F-ND to a
torque of 0.78 to 0.98 N·m.
• Wire the terminals correctly with no mistakes in coil polarity,
otherwise the G7SA will not operate.
Cleaning
The G7SA is not of enclosed construction. Therefore, do not wash the
G7SA with water or detergent.
6
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
·
·
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
·
Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2010.11
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2010 All Right Reserved.
相关型号:
G7SA-3A3B12VDC
Power/Signal Relay, 6PST, Momentary, 0.042A (Coil), 12VDC (Coil), 500mW (Coil), 6A (Contact), 125VDC (Contact), DC Input, AC/DC Output, Through Hole-Straight Mount,
OMRON
G7SA-3A3B24VDC
Power/Signal Relay, 6PST, Momentary, 0.021A (Coil), 24VDC (Coil), 500mW (Coil), 6A (Contact), 125VDC (Contact), DC Input, AC/DC Output, Through Hole-Straight Mount,
OMRON
G7SA-4A2B21VDC
Power/Signal Relay, 6PST, Momentary, 0.024A (Coil), 21VDC (Coil), 500mW (Coil), 6A (Contact), 125VDC (Contact), DC Input, AC/DC Output, Through Hole-Straight Mount,
OMRON
G7SA-5A1B21VDC
Power/Signal Relay, 6PST, Momentary, 0.024A (Coil), 21VDC (Coil), 500mW (Coil), 6A (Contact), 125VDC (Contact), DC Input, AC/DC Output, Through Hole-Straight Mount,
OMRON
G7SA-5A1B48VDC
Power/Signal Relay, 6PST, Momentary, 0.011A (Coil), 48VDC (Coil), 500mW (Coil), 6A (Contact), 125VDC (Contact), DC Input, AC/DC Output, Through Hole-Straight Mount,
OMRON
G7SB-2A2BDC24
Power/Signal Relay, 4PST, Momentary, 0.015A (Coil), 24VDC (Coil), 360mW (Coil), 6A (Contact), 125VDC (Contact), DC Input, AC/DC Output, Through Hole-Straight Mount
OMRON
©2020 ICPDF网 联系我们和版权申明