HSoli3d-sCtateRTwi-nFTimers  
DIN 48 × 48-mm Twin Timers  
• Wide power supply ranges of 100 to 240 VAC and 48 to  
125 VDC respectively.  
• ON- and OFF-times can be set independently and so  
combinations of long ON- or OFF-time and short OFF- or ON-  
time settings are possible.  
• Fourteen time ranges from 0.05 s to 30 h or from 1.2 s to 300 h  
depending on the model to be used.  
• Models with a flicker ON start or flicker OFF start are available.  
• Easy sequence checks through instantaneous outputs for a  
zero set value at any time range.  
• Length, when panel-mounted with a Socket, of 80 mm or less.  
• 11-pin and 8-pin models are available.  
Model Number Structure  
Model Number Legend  
H3CR - F @ @ - @ @  
1
2
3
4
5
1. Classification  
F: Twin timers  
2. Configuration  
None: 11-pin socket  
8: 8-pin socket  
3. Twin Timer Mode  
5. Supply Voltage  
100-240AC: 100 to 240 VAC  
24AC/DC: 24 VAC/VDC  
None: Flicker OFF start  
N:  
Flicker ON start  
12DC:  
12 VDC  
4. Time Range  
None: 0.05 s to 30 h models  
300: 1.2 s to 300 h models  
48-125DC: 48 to 125 VDC  
Ordering Information  
List of Models  
Operating  
modes  
Supply  
voltage  
0.05 s to 30 h models  
1.2 s to 300 h models  
11-pin models  
8-pin models  
H3CR-F8 100-240AC  
H3CR-F8 24AC/DC  
H3CR-F8 12DC  
11-pin models  
H3CR-F-300 100-240AC  
H3CR-F-300 24AC/DC  
H3CR-F-300 12DC  
8-pin models  
H3CR-F8-300 100-240AC  
H3CR-F8-300 24AC/DC  
H3CR-F8-300 12DC  
Flicker OFF  
start  
100 to 240 VAC  
24 VAC/DC  
12 VDC  
H3CR-F 100-240AC  
H3CR-F 24AC/DC  
H3CR-F 12DC  
48 to 125 VDC  
H3CR-F 48-125DC  
H3CR-FN 100-240AC  
H3CR-FN 24AC/DC  
H3CR-FN 12DC  
H3CR-F8 48-125DC  
H3CR-F8N 100-240AC  
H3CR-F8N 24AC/DC  
H3CR-F8N 12DC  
H3CR-F-300 48-125DC  
H3CR-FN-300 100-240AC  
H3CR-FN-300 24AC/DC  
H3CR-FN-300 12DC  
H3CR-F8-300 48-125DC  
H3CR-F8N-300 100-240AC  
H3CR-F8N-300 24AC/DC  
H3CR-F8N-300 12DC  
Flicker ON start 100 to 240 VAC  
24 VAC/DC  
12 VDC  
48 to 125 VDC  
H3CR-FN 48-125DC  
H3CR-F8N 48-125DC  
H3CR-FN-300 48-125DC  
H3CR-F8N-300 48-125DC  
Note: Specify both the model number and supply voltage when ordering.  
Example: H3CR-F 100-240AC  
Supply voltage  
(c)Copyright OMRON Corporation 2007 All Rights Reserved.  
http://www.ia.omron.com/  
1
H3CR-F  
Accessories (Order Separately)  
Name/specifications  
Models  
Flush Mounting Adapter  
Y92F-30  
Y92F-73  
Y92F-74  
PFP-50N  
PFP-100N  
PFP-100N2  
PFP-M  
Mounting Track  
50 cm (l) × 7.3 mm (t)  
1 m (l) × 7.3 mm (t)  
1 m (l) × 16 mm (t)  
End Plate  
Spacer  
PFP-S  
Protective Cover  
Y92A-48B  
P2CF-08  
P2CF-08-E  
P2CF-11  
P2CF-11-E  
P3G-08  
Track Mounting/  
Front Connecting Socket  
8-pin  
8-pin, finger safe type  
11-pin  
11-pin, finger safe type  
8-pin  
Back Connecting Socket  
8-pin, finger safe type  
11-pin  
P3G-08 with Y92A-48G (See note 1)  
P3GA-11  
11-pin, finger safe type  
For PL08 and PL11 Sockets  
For PF085A Socket  
P3GA-11 with Y92A-48G (See note 1)  
Hold-down Clip (See note 2)  
Y92H-7  
Y92H-8  
Note: 1. Y92A-48G is a finger safe terminal cover which is attached to the P3G-08 or P3GA-11 Socket.  
2. Hold-down Clips are sold in sets of two.  
Specifications  
General  
Item  
Operating mode  
Pin type  
H3CR-F  
Flicker OFF start  
11-pin  
H3CR-F8  
H3CR-FN  
Flicker ON start  
11-pin  
H3CR-F8N  
8-pin  
8-pin  
Operating/Reset method  
Output type  
Time-limit operation/Time-limit reset or self-reset  
Relay output (DPDT)  
Mounting method  
Approved standards  
DIN track mounting, surface mounting, and flush mounting  
UL508, CSA C22.2 No.14, NK, Lloyds  
Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2.  
Output category according to EN60947-5-1.  
Time Ranges  
0.05 s to 30 h Models  
Time unit  
s (sec)  
×10 s (10 sec)  
1.2 to 12  
min (min)  
0.12 to 1.2  
h (hrs)  
Setting  
1.2  
3
0.05 to 1.2  
0.3 to 3  
3 to 30  
0.3 to 3  
1.2 to 12  
3 to 30  
12  
30  
1.2 to 12  
3 to 30  
12 to 120  
30 to 300  
Note: Instantaneous output is available at any time range. To obtain instantaneous output, set to below 0.  
1.2 s to 300 h Models  
Time unit  
1.2  
×10 s (10 sec)  
1.2 to 12  
×10 min (10 min)  
1.2 to 12  
h (hrs)  
×10 h (10 hrs)  
1.2 to 12  
3 to 30  
Setting  
0.12 to 1.2  
0.3 to 3  
3
3 to 30  
3 to 30  
12  
30  
12 to 120  
30 to 300  
12 to 120  
30 to 300  
1.2 to 12  
3 to 30  
12 to 120  
30 to 300  
Note: Instantaneous output is available at any time range. To obtain instantaneous output, set to below 0.  
(c)Copyright OMRON Corporation 2007 All Rights Reserved.  
http://www.ia.omron.com/  
2
H3CR-F  
Ratings  
Rated supply voltage (See notes 1, 2, and 3.) 100 to 240 VAC (50/60 Hz),12 VDC, 24 VAC/DC (50/60 Hz), 48 to 125 VDC  
Operating voltage range  
Power reset  
85% to 110% of rated supply voltage; 90% to 110% with 12-VDC models  
Minimum power-opening time: 0.1 s  
Power consumption  
100 to 240 VAC: approx. 10 VA (2.1 W) at 240 VAC  
24 VAC/VDC:  
approx. 2 VA (1.7 W) at 24 VAC  
approx. 1 W at 24 VDC  
48 to 125 VDC: approx. 1.5 W at 125 VDC  
12 VDC: approx. 1 W at 12 VDC  
Contact output: 5 A at 250 VAC/30 VDC, resistive load (cosφ = 1)  
Control outputs  
Note: 1. A power supply with a ripple of 20% max. (single-phase power supply with full-wave rectification) can be used with each DC Model.  
2. Do not use an inverter output as the power supply. Refer to Safety Precautions for All Timers for details.  
3. Refer to Safety Precautions for All Timers when using the Timer together with a 2-wire AC proximity sensor.  
Characteristics  
Accuracy of operating  
time  
0.2% FS max. ( 0.2% FS 10 ms max. in ranges of 1.2 and 3 s)  
Setting error  
5% FS 50 ms max.  
Reset time  
0.1 s max.  
Reset voltage  
Influence of voltage  
10% max. of rated voltage  
0.2% FS max. ( 0.2% FS 10 ms max. in ranges of 1.2 and 3 s)  
Influence of temperature 1% FS max. ( 1% FS 10 ms max. in ranges of 1.2 and 3s)  
Insulation resistance  
Dielectric strength  
100 MΩ min. (at 500 VDC)  
2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts)  
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)  
2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)  
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)  
Impulse withstand  
voltage  
3 kV (between power terminals) for 100 to 240 VAC, 48 to 125 VDC  
1 kV for 12 VDC, 24 VAC/DC  
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC, 48 to  
125 VDC  
1.5 kV for 12 VDC, 24 VAC/DC  
Noise immunity  
Static immunity  
Vibration resistance  
Shock resistance  
1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)  
400 V for 12 VDC  
Malfunction: 8 kV  
Destruction: 15 kV  
Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions  
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions  
Destruction: 980 m/s2 three times each in six directions  
Malfunction: 98 m/s2 three times each in six directions  
Ambient temperature  
Operating: 10°C to 55°C (with no icing)  
Storage:  
25°C to 65°C (with no icing)  
Ambient humidity  
Life expectancy  
Operating: 35% to 85%  
Mechanical: 20 million operations min. (under no load at 1,800 operations/h)  
Electrical:  
100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note)  
EMC  
(EMI)  
EN61812-1  
Emission Enclosure:  
Emission AC Mains:  
(EMS)  
EN55011 Group 1 class A  
EN55011 Group 1 class A  
EN61812-1  
Immunity ESD:  
IEC61000-4-2:  
6 kV contact discharge (level 3)  
8 kV air discharge (level 3)  
Immunity RF-interference from AM Radio Waves:  
IEC61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)  
Immunity RF-interference from Pulse-modulated Radio Waves: IEC61000-4-3: 10 V/m (900 5 MHz) (level 3)  
Immunity Conducted Disturbance: IEC61000-4-6:  
10 V (0.15 to 80 MHz) (level 3)  
2 kV power-line (level 3)  
Immunity Burst:  
IEC61000-4-4:  
2 kV I/O signal-line (level 4)  
1 kV line to line (level 3)  
Immunity Surge:  
IEC61000-4-5:  
2 kV line to ground (level 3)  
Case color  
Light Gray (Munsell 5Y7/1)  
IP40 (panel surface)  
Approx. 100 g  
Degree of protection  
Weight  
Note: Refer to the Life-test Curve.  
(c)Copyright OMRON Corporation 2007 All Rights Reserved.  
http://www.ia.omron.com/  
3
H3CR-F  
Life-test Curve  
10,000  
5,000  
1,000  
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1)  
30 VDC L/R = 7 ms  
500  
and a maximum current of 0.1 A can be switched if L/R is 7 ms. In  
both cases, a life of 100,000 operations can be expected.  
The minimum applicable load is 10 mA at 5 VDC (failure level: P).  
250 VAC/30 VDC  
(cosφ = 1)  
100  
250 VAC (cosφ = 0.4)  
Load current (A)  
Connections  
Block Diagrams  
Zero setting  
detection  
circuit  
ON indicator OFF indicator  
Indicator  
circuit  
ROM  
RAM  
Clock  
Output  
circuit  
Power supply  
circuit  
Time range/unit  
selectors  
One-chip microcomputer  
AC (DC) input  
I/O Functions  
Inputs  
---  
Outputs  
Control output  
Outputs are turned ON/OFF according to the time set by the ON- and OFF-time setting knob.  
Terminal Arrangement  
H3CR-F8  
H3CR-F8  
H3CR-F  
H3CR-FN  
NH3CR-F8-300  
H3CR-F8N-300  
H3CR-F-300  
H3CR-FN-300  
(+)(~)  
Power supply  
Power supply  
Note: Leave terminals 5, 6, and 7 open.  
Do not use them as relay terminals.  
(c)Copyright OMRON Corporation 2007 All Rights Reserved.  
http://www.ia.omron.com/  
4
H3CR-F  
Operation  
Timing Chart  
tON: ON set time  
tOFF: OFF set time  
Operating mode  
Flicker OFF start  
Timing chart  
0.1 s min.  
ON  
OFF  
Power  
t
OFF  
t
ON  
tOFF  
t
ON  
t
OFF  
tOFF  
Lit  
Not lit  
ON  
indicator  
Lit  
Not lit  
OFF  
indicator  
ON  
OFF  
Output  
NO  
ON  
OFF  
Output  
NC  
Flicker ON start  
0.1 s min.  
ON  
Power  
OFF  
tON  
tOFF  
tON  
tOFF  
tON  
tOFF  
Lit  
ON  
indicator  
Not lit  
Lit  
OFF  
indicator  
Not lit  
ON  
Output  
NO  
OFF  
ON  
Output  
NC  
OFF  
Note: 1. The reset time requires a minimum of 0.1 s.  
2. When power is supplied in flicker ON start mode, the OFF indicator lights momentarily. This, however, has no effect on the performance  
of the Timer.  
Nomenclature  
OFF indicator (green)  
OFF-time unit display window  
Lit when the output is OFF.  
OFF-time unit selector (select one from sec.  
10 s, min., and hrs, or from 10 s, 10 min, hrs,  
and 10 h)  
ON indicator (orange)  
Lit when the output is ON.  
Scale range display  
windows  
ON-time setting knob (with orange pointer)  
For ON-time setting  
OFF-time setting knob (with green pointer)  
For OFF-time setting  
Time range selector (select one  
from 1.2, 3, 12, and 30 at full  
scale)  
ON-time unit display window  
For both ON-time and OFF-time.  
ON-time unit selector (select one  
from sec, 10 s, min, and hrs, or from  
10 s, 10 min, hrs, and 10 h)  
(c)Copyright OMRON Corporation 2007 All Rights Reserved.  
http://www.ia.omron.com/  
5
H3CR-F  
Dimensions  
Note: All units are in millimeters unless otherwise indicated.  
H3CR-F  
66.6  
52.3  
17.4  
5.7  
H3CR-FN  
48  
0.7  
6
H3CR-F-300  
H3CR-FN-300  
44.8 × 44.8  
37 dia.  
14 dia.  
48  
R1.3  
11 pins  
17.4  
5.7  
66.6  
52.3  
H3CR-F8  
H3CR-F8N  
48  
0.7  
6
H3CR-F8-300  
H3CR-F8N-300  
37 dia.  
14 dia.  
44.8 × 44.8  
48  
R1.3  
8 pins  
Dimensions with Front Connecting Socket  
P2CF-08-@/P2CF-11-@  
Dimensions with Back Connecting Socket  
P3G-08/P3GA-11  
81.5  
80  
81.5  
75  
17.4  
17.4  
H3CR-F  
H3CR-FN  
H3CR-F8  
H3CR-F8N  
92.3*  
90.0  
103.2*  
100.9  
H3CR-F  
H3CR-FN  
H3CR-F8  
H3CR-F8N  
P3GA-11  
P3G-08  
Y92F-30  
Y92F-30  
(When  
(When  
2.3*  
2.3*  
Y92A-48G  
mounted)  
Y92A-48G  
mounted)  
P2CF-11  
P2CF-11-E  
P2CF-08  
P2CF-08-E  
*These dimensions vary with the kind of DIN track (reference value).  
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.  
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.  
In the interest of product improvement, specifications are subject to change without notice.  
(c)Copyright OMRON Corporation 2007 All Rights Reserved.  
http://www.ia.omron.com/  
6
HSoli3d-sCtateRSta-r-Gdelta Timers  
DIN 48 × 48-mm Star-delta Timer  
• A wide star-time range (up to 120 seconds) and star-delta  
transfer time range (up to 0.5 seconds).  
Model Number Structure  
Model Number Legend  
H3CR - G 8 @ L @  
1
2 3 4 5  
5. Supply Voltage  
100-120AC: 100 to 120 VAC  
200-240AC: 200 to 240 VAC  
1. Classification  
G: Star-delta timer  
2. Configuration  
8: 8-pin socket  
3. Outputs  
None: Star-delta operation contact  
E:  
Star-delta operation contact  
and instantaneous contact  
4. Dimensions  
L: Long-body model  
Ordering Information  
List of Models  
Outputs  
Supply voltage  
100 to 120 VAC  
200 to 240 VAC  
100 to 120 VAC  
200 to 240 VAC  
8-pin models  
Time-limit contact  
H3CR-G8L 100-120AC  
H3CR-G8L 200-240AC  
H3CR-G8EL 100-120AC  
H3CR-G8EL 200-240AC  
Time-limit contact and instantaneous contact  
Note: Specify both the model number and supply voltage when ordering.  
Example: H3CR-G8L 100-120AC  
Supply voltage  
(c)Copyright OMRON Corporation 2007 All Rights Reserved.  
http://www.ia.omron.com/  
7
H3CR-G  
Accessories (Order Separately)  
Name/specifications  
Models  
Flush Mounting Adapter  
Y92F-30  
Y92F-70  
Y92F-71  
PFP-50N  
PFP-100N  
PFP-100N2  
PFP-M  
Mounting Track  
50 cm (l) × 7.3 mm (t)  
1 m (l) × 7.3 mm (t)  
1 m (l) × 16 mm (t)  
End Plate  
Spacer  
PFP-S  
Protective Cover  
Y92A-48B  
P2CF-08  
P2CF-08-E  
P3G-08  
Track Mounting/  
Front Connecting Socket  
8-pin  
8-pin, finger safe type  
8-pin  
Back Connecting Socket  
8-pin, finger safe type  
Setting a specific time  
Limiting the setting range  
Light gray (5Y7/1)  
Black (N1.5)  
P3G-08 with Y92A-48G (See note 1)  
Time Setting Ring  
Y92S-27  
Y92S-28  
Panel Cover (See note 2)  
Y92P-48GL  
Y92P-48GB  
Y92P-48GM  
Y92H-1  
Medium gray (5Y5/1)  
For PL08 and PL11 Sockets  
For PF085A Socket  
Hold-down Clip (See note 3)  
Y92H-2  
Note: 1. Y92A-48G is a finger safe terminal cover which is attached to the P3G-08 Socket.  
2. The Time Setting Ring and Panel Cover are sold together.  
3. Hold-down Clips are sold in sets of two.  
Specifications  
General  
Item  
H3CR-G8L  
H3CR-G8EL  
Star-delta timer with instantaneous output  
Functions  
Pin type  
Star-delta timer  
8-pin  
Operating/Reset method  
Output type  
Time-limit operation/Self-reset  
Time-limit: SPST-NO (star operation circuit)  
SPST-NO (delta operation circuit)  
Time-limit:  
SPST-NO (star operation circuit)  
SPST-NO (delta operation circuit)  
Instantaneous: SPST-NO  
Mounting method  
DIN track mounting, surface mounting, and flush mounting  
Approved standards  
UL508, CSA C22.2 No.14, NK, Lloyds  
Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2.  
Output category according to EN60947-5-1.  
Time Ranges  
Time unit  
Star operation time ranges  
Full scale setting  
6
0.5 to 6 s  
12  
60  
120  
1 to 12 s  
5 to 60 s  
10 to 120 s  
Star-delta transfer time  
Programmable at 0.05 s, 0.1 s, 0.25 s or 0.5 s  
(c)Copyright OMRON Corporation 2007 All Rights Reserved.  
http://www.ia.omron.com/  
8
H3CR-G  
Ratings  
Rated supply voltage (See notes 1 and 2.) 100 to 120 VAC (50/60 Hz), 200 to 240 VAC (50/60 Hz)  
Operating voltage range  
Power reset  
85% to 110% of rated supply voltage  
Minimum power-opening time: 0.5 s  
Power consumption  
100 to 120 VAC: approx. 6 VA (2.6 W) at 120 VAC  
200 to 240 VAC: approx. 12 VA (3.0 W) at 240 VAC  
Control outputs  
Contact output: 5 A at 250 VAC/30 VDC, resistive load (cosφ = 1)  
Note: 1. Do not use an inverter output as the power supply. Refer to Safety Precautions for All Timers for details.  
2. Refer to Safety Precautions for All Timers when using the Timer together with a 2-wire AC proximity sensor.  
Characteristics  
Accuracy of operating  
time  
0.2% FS max.  
Setting error  
5% FS 50 ms max.  
25% FS + 5 ms max.  
Accuracy of Star-delta  
transfer time  
Reset voltage  
10% max. of rated voltage  
0.2% FS max.  
Influence of voltage  
Influence of temperature  
Insulation resistance  
Dielectric strength  
1% FS max.  
100 MΩ min. (at 500 VDC)  
2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts)  
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)  
2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)  
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)  
Impulse withstand  
voltage  
3 kV (between power terminals)  
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts)  
Noise immunity  
Static immunity  
1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)  
Malfunction: 8 kV  
Destruction: 15 kV  
Vibration resistance  
Shock resistance  
Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions  
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions  
Destruction: 980 m/s2 three times each in six directions  
Malfunction: 294 m/s2 three times each in six directions  
Ambient temperature  
Operating: 10°C to 55°C (with no icing)  
Storage:  
25°C to 65°C (with no icing)  
Ambient humidity  
Life expectancy  
Operating:  
35% to 85%  
Mechanical: 20 million operations min. (under no load at 1,800 operations/h)  
Electrical:  
100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note)  
EMC  
(EMI)  
EN61812-1  
Emission Enclosure:  
Emission AC Mains:  
(EMS)  
EN55011 Group 1 class A  
EN55011 Group 1 class A  
EN61812-1  
Immunity ESD:  
IEC61000-4-2:  
6 kV contact discharge (level 3)  
8 kV air discharge (level 3)  
Immunity RF-interference from AM Radio Waves:  
IEC61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)  
Immunity RF-interference from Pulse-modulated Radio Waves: IEC61000-4-3: 10 V/m (900 5 MHz) (level 3)  
Immunity Conducted Disturbance: IEC61000-4-6:  
10 V (0.15 to 80 MHz) (level 3)  
2 kV power-line (level 3)  
Immunity Burst:  
IEC61000-4-4:  
2 kV I/O signal-line (level 4)  
1 kV line to line (level 3)  
Immunity Surge:  
IEC61000-4-5:  
2 kV line to ground (level 3)  
Case color  
Light Gray (Munsell 5Y7/1)  
IP40 (panel surface)  
Degree of protection  
Weight  
H3CR-G8L: approx. 110 g; H3CR-G8EL: approx. 130 g  
Note: Refer to the Life-test Curve.  
(c)Copyright OMRON Corporation 2007 All Rights Reserved.  
http://www.ia.omron.com/  
9
H3CR-G  
Life-test Curve  
10,000  
5,000  
1,000  
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1)  
30 VDC L/R = 7 ms  
and a maximum current of 0.1 A can be switched if L/R is 7 ms. In  
both cases, a life of 100,000 operations can be expected.  
The minimum applicable load is 10 mA at 5 VDC (failure level: P).  
500  
250 VAC/30 VDC  
(cosφ = 1)  
100  
250 VAC (cosφ = 0.4)  
Load current (A)  
Connections  
Block Diagrams  
H3CR-G8L  
Star  
Star-delta  
transfer time  
selector  
operation  
time range  
selector  
Star operation  
time  
oscillation  
circuit  
Star  
Star-delta  
transfer time  
oscillation  
circuit  
Star-delta  
transfer time  
counting  
circuit  
Power  
supply  
circuit  
operation  
time counting  
circuit  
AC input  
Star operation  
Delta operation  
Output  
circuit  
Star  
operation  
indicator  
Indicator  
circuit  
Delta  
operation  
indicator  
H3CR-G8EL  
Star  
Star-delta  
transfer time  
selector  
operation  
time range  
selector  
Star operation  
time  
oscillation  
circuit  
Star  
Star-delta  
transfer time  
oscillation  
circuit  
Star-delta  
transfer time  
counting  
circuit  
Power  
supply  
circuit  
Star operation  
Delta operation  
operation  
time counting  
circuit  
AC input  
Output  
circuit  
Star  
operation  
indicator  
Indicator  
circuit  
Delta  
operation  
indicator  
Instantaneous  
output circuit  
(c)Copyright OMRON Corporation 2007 All Rights Reserved.  
http://www.ia.omron.com/  
10  
H3CR-G  
I/O Functions  
Inputs  
---  
Outputs  
Control output  
If the time reaches the value set with the time setting knob, the star operation output will be turned OFF  
and there will be delta operation output after the set star-delta transfer time has elapsed.  
Terminal Arrangement  
H3CR-G8L  
H3CR-G8EL  
Star  
operation  
contact  
Delta  
operation  
contact  
Star  
operation  
contact  
Delta  
operation  
contact  
Instantaneous contact  
Note: Leave terminals 1, 3, and 4 open.  
Note: Leave terminal 4 open. Do not use  
Do not use them as relay terminals.  
them as relay terminals.  
Operation  
Timing Chart  
t1: Star operation time setting  
t2: Star-delta transfer time  
Model  
Timing chart  
0.5 s min.  
H3CR-G8L/-G8EL  
ON  
OFF  
Power (2 7)  
ON  
OFF  
Instantaneous output  
(1 3) (-E models)  
t1  
ON  
OFF  
t2  
Star operation  
output (8 5)  
ON  
OFF  
Delta operation  
output (8 6)  
Lit  
Not lit  
Star operation indicator  
Delta operation indicator  
Lit  
Not lit  
Nomenclature  
Star operation  
indicator (green)  
Delta operation  
indicator (orange)  
Time unit display  
(sec is fixed)  
Scale range display  
windows  
Time setting knob (for setting  
star operation time)  
Star-delta transfer time selector  
(select one from 0.05 s, 0.1 s,  
0.25 s, and 0.5 s)  
Star operation time range selector  
(select one from 6, 12, 60, and 120  
at full scale)  
Star-delta transfer time display window  
(c)Copyright OMRON Corporation 2007 All Rights Reserved.  
http://www.ia.omron.com/  
11  
H3CR-G  
Dimensions  
Note: All units are in millimeters unless otherwise indicated.  
(78.0)  
63.7  
15  
6
48  
0.7  
44.8 × 44.8  
39 dia.  
48  
8 pins  
Dimensions with Set Ring  
16.5  
50  
42 dia.  
50  
Time setting ring  
Panel cover  
Dimensions with Front Connecting Socket  
P2CF-08-@  
Dimensions with Back Connecting Socket  
P3G-08  
92.9  
15  
86.4  
H3CR-G8@L  
99  
101.3*  
H3CR-  
G8@L  
P3G-08  
Y92F-30  
(When  
Y92A-48G  
mounted)  
2.3*  
P2CF-08  
P2CF-08-E  
*These dimensions vary with the kind of DIN track (reference value).  
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.  
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.  
In the interest of product improvement, specifications are subject to change without notice.  
(c)Copyright OMRON Corporation 2007 All Rights Reserved.  
http://www.ia.omron.com/  
12  
HSoli3d-sCtateRPow-eHr OFF-delay Timers  
DIN 48 × 48-mm Power OFF-delay Timer  
• Long power OFF-delay times;  
S-series: up to 12 seconds,  
M-series: up to 12 minutes.  
• Models with forced-reset input are available.  
• 11-pin and 8-pin models are available.  
Model Number Structure  
Model Number Legend  
Note: This model number legend includes combinations that are not available. Before ordering, please check the List of Models on page 1 for  
availability.  
H3CR - H @ @ L @ @  
1
2
3
4
5
6
6. Time Range  
1. Classification  
H: Power OFF-delay timer  
2. Configuration  
3. Input  
5. Supply Voltage  
100-120AC: 100 to 120 VAC  
200-240AC: 200 to 240 VAC  
S:  
0.05 to 12 s  
None: Without reset input  
M:  
0.05 to 12 min  
R:  
With reset input  
48DC:  
48 VDC  
4. Dimensions  
None: 11-pin socket  
100-125DC: 100 to 125 VDC  
8:  
8-pin socket  
L:  
Long-body model  
List of Models  
Input Output Supply voltage  
S-series  
M-series  
11-pin models  
8-pin models  
11-pin models  
8-pin models  
Without DPDT 100 to 120 VAC ---  
H3CR-H8L 100-120AC S ---  
H3CR-H8L 200-240AC S  
H3CR-H8L 24AC/DC S  
H3CR-H8L 48DC S  
H3CR-H8L 100-120AC M  
H3CR-H8L 200-240AC M  
H3CR-H8L 24AC/DC M  
H3CR-H8L 48DC M  
reset  
input  
200 to 240 VAC  
24 VAC/DC  
48 VDC  
100 to 125 VDC  
H3CR-H8L 100-125DC S  
H3CR-H8L 100-125DC M  
With  
reset  
input  
100 to 120 VAC H3CR-HRL 100-120AC S ---  
200 to 240 VAC H3CR-HRL 200-240AC S  
H3CR-HRL 100-120AC M ---  
H3CR-HRL 200-240AC M  
H3CR-HRL 24AC/DC M  
H3CR-HRL 48DC M  
24 VAC/DC  
48 VDC  
H3CR-HRL 24AC/DC S  
H3CR-HRL 48DC S  
100 to 125 VDC H3CR-HRL 100-125DC S  
SPDT 100 to 120 VAC ---  
H3CR-HRL 100-125DC M  
H3CR-H8RL 100-120AC S ---  
H3CR-H8RL 100-120AC M  
H3CR-H8RL 200-240AC M  
H3CR-H8RL 24AC/DC M  
H3CR-H8RL 48DC M  
200 to 240 VAC  
24 VAC/DC  
H3CR-H8RL 200-240AC S  
H3CR-H8RL 24AC/DC S  
H3CR-H8RL 48DC S  
48 VDC  
100 to 125 VDC  
H3CR-H8RL 100-125DC S  
H3CR-H8RL 100-125DC M  
Note: Specify the model number, supply voltage, and time range (S or M) when ordering.  
Example: H3CR-H8L 100-120AC S  
Time range  
Supply voltage  
(c)Copyright OMRON Corporation 2007 All Rights Reserved.  
http://www.ia.omron.com/  
13  
H3CR-H  
Accessories (Order Separately)  
Name/specifications  
Models  
Flush Mounting Adapter  
Y92F-30  
Y92F-70  
Y92F-71  
PFP-50N  
PFP-100N  
PFP-100N2  
PFP-M  
Mounting Track  
50 cm (l) × 7.3 mm (t)  
1 m (l) × 7.3 mm (t)  
1 m (l) × 16 mm (t)  
End Plate  
Spacer  
PFP-S  
Protective Cover  
Y92A-48B  
P2CF-08  
P2CF-08-E  
P2CF-11  
P2CF-11-E  
P3G-08  
Track Mounting/  
Front Connecting Socket  
8-pin  
8-pin, finger safe type  
11-pin  
11-pin, finger safe type  
8-pin  
Back Connecting Socket  
8-pin, finger safe type  
11-pin  
P3G-08 with Y92A-48G (See note 1)  
P3GA-11  
11-pin, finger safe type  
For PL08 and PL11 Sockets  
For PF085A Socket  
P3GA-11 with Y92A-48G (See note 1)  
Hold-down Clip (See note 2)  
Y92H-1  
Y92H-2  
Note: 1. Y92A-48G is a finger safe terminal cover which is attached to the P3G-08 or P3GA-11 Socket.  
2. Hold-down Clips are sold in sets of two.  
Specifications  
General  
Item  
H3CR-H8L  
H3CR-H8RL  
H3CR-HRL  
Operating/Reset method  
Instantaneous operation/Time-limit Instantaneous operation/Time-limit reset/Forced reset  
reset  
Pin type  
8-pin  
11-pin  
Input type  
---  
No-voltage  
Output type  
Relay output (DPDT)  
Relay output (SPDT)  
Relay output (DPDT)  
Mounting method  
Approved standards  
DIN track mounting, surface mounting, and flush mounting  
UL508, CSA C22.2 No.14, NK, Lloyds  
Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2.  
Output category according to EN60947-5-1.  
Time Ranges  
Time unit  
S-series  
s (sec)  
M-series  
min (min)  
Setting  
0.6  
1.2  
6
0.05 to 0.6  
0.12 to 1.2  
0.6 to 6  
12  
1.2 to 12  
0.1 s min.  
3 s min.  
Min. power ON time  
2 s min.  
Time-up operation repeat period  
Forced-reset repeat period  
3 s min.  
Note: 1. If the above minimum power ON time is not secured, the H3CR may not operate. Be sure to secure the above minimum power ON time.  
2. Do not use the Timer with a repeat period of less than 3 s. Doing so may result in abnormal heating or burning. Refer to Safety Precautions  
(H3CR-H) on page 8 for details.  
(c)Copyright OMRON Corporation 2007 All Rights Reserved.  
http://www.ia.omron.com/  
14  
H3CR-H  
Ratings  
Rated supply voltage (See notes 1 and 2.) 100 to 120 VAC (50/60 Hz), 200 to 240 VAC (50/60 Hz), 24 VAC/VDC (50/60 Hz), 48 VDC,  
100 to 125 VDC  
Operating voltage range  
85% to 110% of rated supply voltage  
ON-impedance: 1 kΩ max.  
ON residual voltage: 1 V max.  
No-voltage input (See note 3.)  
OFF impedance:  
500 kΩ min.  
Power consumption  
100 to 120 VAC: approx. 0.23 VA (0.22 W) at 120 VAC  
200 to 240 VAC: approx. 0.35 VA (0.3 W) at 240 VAC  
24 VAC/DC:  
approx. 0.17 VA (0.15 W) at 24 VAC  
approx. 0.1 W at 24 VDC  
48 VDC:  
approx. 0.18 W at 48 VDC  
100 to 125 VDC: approx. 0.5 W at 125 VDC  
Control outputs  
Contact output: 5 A at 250 VAC/30 VDC, resistive load (cosφ = 1)  
Note: 1. A power supply with a ripple of 20% max. (single-phase power supply with full-wave rectification) can be used with each DC Model.  
2. Do not use an inverter output as the power supply. Refer to Safety Precautions for All Timers for details.  
3. For contact input, use contacts which can adequately switch 1 mA at 5 V.  
Characteristics  
Accuracy of operating  
time  
0.2% FS max. ( 0.2% FS 10 ms max. in ranges of 0.6 and 1.2 s)  
Setting error  
5% FS 50 ms max.  
Operation start voltage  
Influence of voltage  
30% max. of rated voltage  
0.2% FS max. ( 0.2% FS 10 ms max. in ranges of 0.6 and 1.2 s)  
Influence of temperature 1% FS max. ( 1% FS 10 ms max. in ranges of 0.6 and 1.2 s)  
Insulation resistance  
Dielectric strength  
100 MΩ min. (at 500 VDC)  
2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts)  
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)  
2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)  
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)  
Impulse withstand  
voltage  
3 kV (between power terminals) for 100 to 120 VAC, 200 to 240 VAC, 100 to 125 VDC;  
1 kV for 24 VAC/DC, 48 VDC  
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 120 VAC, 200 to  
240 VAC, 100 to 125 VDC;  
1.5 kV for 24 VAC/DC, 48 VDC  
Noise immunity  
1.5 kV (between power terminals) and 600 V (between input terminals), square-wave noise by noise simulator  
(pulse width: 100 ns/1 μs, 1-ns rise); 1 kV (between power terminals) for 48 VDC  
Static immunity  
Malfunction: 8 kV, Destruction:15 kV  
Vibration resistance  
Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions  
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions  
Destruction: 980 m/s2 three times each in six directions  
Shock resistance  
Malfunction: 98 m/s2 three times each in six directions  
Ambient temperature  
Operating: 10°C to 55°C (with no icing),  
Storage:  
25°C to 65°C (with no icing)  
Ambient humidity  
Life expectancy  
Operating: 35% to 85%  
Mechanical: 10 million operations min. (under no load at 1,200 operations/h)  
Electrical:  
100,000 operations min. (5 A at 250 VAC, resistive load at 1,200 operations/h) (See note)  
EMC  
(EMI)  
EN61812-1  
Emission Enclosure:  
Emission AC Mains:  
(EMS)  
EN55011 Group 1 class A  
EN55011 Group 1 class A  
EN61812-1  
Immunity ESD:  
IEC61000-4-2:  
6 kV contact discharge (level 3)  
8 kV air discharge (level 3)  
Immunity RF-interference from AM Radio Waves:  
IEC61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)  
Immunity RF-interference from Pulse-modulated Radio Waves: IEC61000-4-3: 10 V/m (900 5 MHz) (level 3)  
Immunity Conducted Disturbance: IEC61000-4-6:  
10 V (0.15 to 80 MHz) (level 3)  
2 kV power-line (level 3)  
Immunity Burst:  
IEC61000-4-4:  
2 kV I/O signal-line (level 4)  
1 kV line to line (level 3)  
Immunity Surge:  
IEC61000-4-5:  
2 kV line to ground (level 3)  
Case color  
Light Gray (Munsell 5Y7/1)  
IP40 (panel surface)  
Approx. 120 g  
Degree of protection  
Weight  
Note: Refer to the Life-test Curve.  
(c)Copyright OMRON Corporation 2007 All Rights Reserved.  
http://www.ia.omron.com/  
15  
H3CR-H  
Life-test Curve  
10,000  
5,000  
1,000  
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1)  
30 VDC L/R = 7 ms  
500  
and a maximum current of 0.1 A can be switched if L/R is 7 ms. In  
both cases, a life of 100,000 operations can be expected.  
The minimum applicable load is 10 mA at 5 VDC for H3CR-H8L/-HRL  
and 100 mA at 5 VDC for H3CR-H8RL (failure level: P).  
250 VAC/30 VDC  
(cosφ = 1)  
100  
250 VAC (cosφ = 0.4)  
Load current (A)  
Connections  
Block Diagrams  
Without Reset Input (H3CR-H8L)  
Time range/  
unit selector  
Power supply  
circuit  
Oscillation  
circuit  
Counting  
circuit  
Output  
circuit  
AC (DC) input  
Power failure  
detection circuit  
Indicator  
circuit  
Output  
indicator  
With Reset Input (H3CR-H8RL/-HRL)  
Time range/  
unit selector  
Power supply  
AC (DC) input  
Oscillation  
circuit  
Counting  
circuit  
Output  
circuit  
circuit  
Indicator  
circuit  
Output  
indicator  
Power failure  
detection circuit  
Reset input  
Input circuit  
I/O Functions  
Inputs  
Reset  
Turns off the control output and resets the elapsed time.  
Outputs  
Control output  
Operates instantaneously when the power is turned on and time-limit resets when the set time is up  
after the power is turned off.  
(c)Copyright OMRON Corporation 2007 All Rights Reserved.  
http://www.ia.omron.com/  
16  
H3CR-H  
Terminal Arrangement  
Note: DC models, including 24 VAC/DC models, have polarity.  
8-pin Models  
Without Reset Input (H3CR-H8L)  
With Reset Input (H3CR-H8RL)  
Reset  
input  
Power supply  
Power supply  
Note: Leave terminal 3 open. Do not use  
them as relay terminals.  
11-pin Model  
With Reset Input (H3CR-HRL)  
Reset input  
Power supply  
Note: Leave terminal 6 open. Do not use  
them as relay terminals.  
(c)Copyright OMRON Corporation 2007 All Rights Reserved.  
http://www.ia.omron.com/  
17  
H3CR-H  
Operation  
Timing Chart  
t:  
Set time  
Rt: Minimum power ON time (S-series: 0.1 s min.; M-series: 2 s min.)  
If the power ON time is less than this value, the Timer may not operate (i.e., output may not turn ON).  
Model  
H3CR-H8L  
Timing chart  
Rt  
Rt  
t
t
ON  
Power  
(See note)  
OFF  
Output (1 3)  
Output (1 4)  
Output (8 6)  
Output (8 5)  
Lit  
Not lit  
Output  
indicator  
H3CR-H8RL  
Rt  
Rt  
ON  
t
t
Power  
(See note)  
OFF  
0.05 s min.  
0.05 s min.  
ON (Short-circuited)  
OFF (Open)  
Reset input  
Output (8 6)  
Output (8 5)  
Lit  
Not lit  
Output  
indicator  
Rt  
H3CR-HRL  
Rt  
ON  
OFF  
t
t
Power  
(See note)  
0.05 s min.  
0.05 s  
min.  
Reset input  
Output (1 3)  
Output (1 4)  
Output (11 9)  
Output (11 8)  
Lit  
Not lit  
Output  
indicator  
Note: If the power is turned ON until the set time is up, the timer will be retriggered.  
(c)Copyright OMRON Corporation 2007 All Rights Reserved.  
http://www.ia.omron.com/  
18  
H3CR-H  
Nomenclature  
Output indicator (red)  
Scale range display windows  
Time setting knob (for setting  
power OFF-delay time)  
Time range selector (select  
one from 0.6, 1.2, 6, and 12 at  
full scale)  
Time unit display  
S-series: sec  
M-series: min  
Dimensions  
Note: All units are in millimeters unless otherwise indicated.  
H3CR-H8L  
H3CR-H8RL  
15  
6
78.0  
63.7  
48  
0.7  
48  
39 dia.  
44.8 × 44.8  
8 pins  
H3CR-HRL  
15  
6
78.0  
63.7  
48  
0.7  
44.8 × 44.8  
48  
39 dia.  
11 pins  
Dimensions with Front Connecting Socket  
P2CF-08-@/P2CF-11-@  
Dimensions with Back Connecting Socket  
P3G-08/P3GA-11  
92.9  
91.4  
92.9  
86.4  
15  
15  
H3CR-H8@L  
H3CR-HRL  
101.3*  
99  
112.2*  
109.9  
2.3*  
H3CR-  
H8@L  
H3CR-HRL  
P3GA-11  
P3G-08  
Y92F-30  
Y92F-30  
(When  
Y92A-48G  
mounted)  
(When  
Y92A-48G  
mounted)  
2.3*  
P2CF-08  
P2CF-08-E  
P2CF-11  
P2CF-11-E  
*These dimensions vary with the kind of DIN track (reference value).  
(c)Copyright OMRON Corporation 2007 All Rights Reserved.  
http://www.ia.omron.com/  
19  
H3CR-H  
Safety Precautions (H3CR-H)  
Note: The undermentioned is common for all H3CR-H models.  
Power Supplies  
The H3CR-H has a large inrush current; provide sufficient power  
supply capacity. If the power supply capacity is too small, there may  
be delays in turning ON the output.  
Wiring  
The H3CR-H has a high impedance circuit. Therefore, the H3CR-H  
may not be reset if the H3CR-H is influenced by inductive voltage. In  
order to eliminate any influence of inductive voltage, the wires  
connected to the H3CR-H must be as short as possible and should  
not be installed alongside power lines. If the H3CR-H is influenced by  
inductive voltage that is 30% or more of the rated voltage, connect a  
CR filter with a capacitance of approximately 0.1 μF and a resistance  
of approximately 120 Ω or a bleeder resistor between the power  
supply terminals. If there is any residual voltage due to current  
leakage, connect a bleeder resistor between the power supply  
terminals.  
With the H3CR-H@RL, for the power supply of an input device, use  
an isolating transformer, of which the primary and secondary  
windings are mutually isolated and the secondary winding is not  
grounded.  
Correct  
H3CR-H@RL  
Input terminal  
10, 7*  
2, 2*  
4*, 7  
Power supply  
Operation  
1*, 5  
An interval of 3 s minimum is required to turn on the H3CR-H after  
the H3CR-H is turned off. If the H3CR-H is turned on and off  
repeatedly with an interval of shorter than 3 s, abnormal heating or  
burning may occur in internal elements.  
:H3CR-H8RL  
*
3 s min.  
Isolation transformer is required.  
Power  
Input device  
Incorrect  
H3CR-H@RL  
Output  
state 1  
10, 7*  
4*, 7  
1*, 5  
Input  
terminal  
Power  
supply  
2, 2*  
Output  
state 2  
After the forced reset function of the H3CR-H is activated, an interval  
of 3 s minimum is required to activate the forced reset function again.  
If the forced reset function is activated repeatedly with an interval of  
shorter than 3 s, the internal parts of the H3CR-H may deteriorate  
and the H3CR-H may malfunction.  
:H3CR-H8RL  
*
Input device  
Isolation  
transformer  
Power  
3 s min.  
3 s min.  
Input/Output (H3CR-H@RL)  
Reset  
input  
An appropriate input is applied to the input signal terminal of the  
Timer when the input terminal for the input signal is short-circuited.  
Do not attempt to connect any input terminal to any terminal other  
than the input terminal or to apply voltage across other than the  
specified input terminals or the internal circuits of the Timer may be  
damaged.  
Output  
If it is required that the output be turned on repeatedly with an  
interval of shorter than 3 s, consider use of the H3CR-A in mode D  
(signal OFF-delay).  
The H3CR-H@RL uses transformerless power supply. When  
connecting a relay or transistor as an external signal input device,  
pay attention to the following points to prevent short-circuiting due to  
a sneak current to the transformerless power supply.  
Others  
If the H3CR-H is dropped or experiences some other kind of shock,  
because a latching relay is used for output, contacts may be reversed  
or go into a neutral state. If the H3CR-H is dropped, reconfirm correct  
operation.  
If input is made simultaneously from one input contact or a transistor  
to the H3CR-H and a Timer whose common input terminals are used  
as power terminals, such as the H3CR-A, a short-circuit current will  
be generated. Either input through isolated contacts, or isolate the  
power supply for one of the Timers.  
H3CR-H@RL  
10, 7*  
4*,  
7
2, 2*  
1*, 5  
Short-circuit current  
G. S. R.  
5
10  
2
7
6
H3CR-A  
*: H3CR-H8RL  
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.  
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.  
In the interest of product improvement, specifications are subject to change without notice.  
(c)Copyright OMRON Corporation 2007 All Rights Reserved.  
http://www.ia.omron.com/  
20  
Safety Precautions for All Timers  
Refer to the Safety Precautions for individual Timers for precautions specific to each Timer.  
Normal operation may not be possible in locations subject to  
!WARNING  
sulfidizing gas, such as in sewer systems or waste incinerators.  
OMRON does not market any Timers or other control devices for  
operation in atmospheres containing sulfidizing gas. Seal the Timer  
so that sulfidizing gas will not enter it. If sealing is not possible,  
OMRON does provide special Timers with improved resistance to  
sulfidizing gas. Ask your OMRON representative for details.  
The following Timers contain lithium batteries that are  
not explosion proof.  
1. Timers with Built-in Batteries: H5L  
The Timer contains a lithium battery, which may occasionally  
ignite or rupture. Do not disassemble, deform under pressure,  
heat to 100°C or higher, or incinerate the Timer.  
Power Supply  
Be sure that the voltage applied is within the specified range,  
2. Timers with Replaceable Batteries: Y92S-20 (for H5CN-M)  
The battery may occasionally rupture, ignite, or leak fluid. Do  
not short the positive and negative terminals. Do not charge,  
disassemble, deform under pressure, or throw the battery into a  
fire. If a non-specified battery is used, the battery may leak fluid  
or rupture, occasionally resulting in equipment failure or minor  
injury. Use only the specified battery.  
otherwise the internal elements of the Timer may be damaged.  
Install a switch or circuit breaker that allows the operator to  
immediately turn OFF the power, and label it to clearly indicate its  
function.  
Maintain voltage fluctuations  
in the power supply within  
the specified range.  
Allowable  
Voltage Range  
!CAUTION  
The following Timers contain lithium batteries that are  
explosion proof.  
Use a commercial power supply for the power supply voltage input  
to models with AC inputs.  
Inverters with an output frequency of 50/60 Hz are available, but  
the rise in the internal temperature of the Timer may result in  
ignition or burning. Do not use an inverter output for the power  
supply of the Timer.  
The Timers listed below cannot be directly turned ON and OFF by  
using an AC 2-wire proximity sensor to turn the Timer's power  
supply ON and OFF.  
Timers with Built-in Batteries:H5BR, H5AN-4DM, H5S, H5F, and  
H4KV  
The Timer contains a lithium battery, which may occasionally  
ignite or rupture. Do not disassemble, deform under pressure,  
heat to 100°C or higher, or incinerate the Timer.  
Use the following countermeasure when using an AC 2-wire  
proximity sensor with the Timer. (The power supply circuit in the  
Timer uses half-wave rectification. Only a half AC wave is supplied  
to the proximity sensor, which may cause operation to be unstable.)  
Precautions for Safe Use  
Operating Environment  
Applicable Models  
H3Y, H3YN, H3RN, H3CA-8, RD2P, and H3CR(-A, -A8, -AP, -F, and  
-G)  
Use the Timer within the ratings specified for ambient operating  
temperature and ambient operating humidity for each model.  
Store the Timer with the specified temperature range for each  
model. If the Timer has been stored at a temperature of less than  
10°C, allow the Timer to stand at room temperature for at least 3  
hours before using it.  
Countermeasure  
Wire through a relay and use the relay contacts to turn the power  
supply ON and OFF.  
Confirm the stability of operation after making the connections.  
Use the Timer within the performance specified for water and oil  
exposure for each model.  
Install protective measures (such as earth leakage breakers, wiring  
breakers, or fuses) on the power supply side according to any  
applicable laws or regulations.  
Do not use the Timer in locations subject to shock and vibration.  
Long-term usage in such locations may damage the Timer due to  
stress.  
Magnetic contactors generate a shock of 1,000 to 2,000 m/s2 when  
switching a load. When mounting to DIN Track, separate magnetic  
contactors from the Timer so that the Timer is not subjected to  
vibration and shock. Use anti-vibration rubber.  
Do not use the Timer in locations subject to excessive dust,  
corrosive gases, or direct sunlight.  
Do not use organic solvents (such as paint thinner or benzine),  
strong alkalis, or strong acids because they will damage the  
external finish of the Timer.  
Separate the input devices, input wiring, and Timer as far as  
possible from sources of noise and power lines carrying noise.  
When using the Timer in environments subject to large amounts of  
static electricity (e.g., pipes carrying molding materials, powders, or  
fluid materials), separate the Timer as far as possible from the  
sources of static electricity.  
Do not remove the external case from the Timer.  
Do not use the Timer in locations where condensation may occur  
due to high humidity or sudden temperature changes.  
Condensation inside the Timer may result in malfunction or  
damage to Timer elements.  
The life of internal parts may be reduced if Timers are mounted in  
close proximity to each other.  
Resin and rubber parts (e.g., rubber packing) may deteriorate,  
shrink, or harden depending on the operating environment (e.g.,  
subjected to corrosive gases, ultraviolet light, or high  
temperatures). We recommend periodic inspection and  
replacement.  
(c)Copyright OMRON Corporation 2007 All Rights Reserved.  
http://www.ia.omron.com/  
C-1  
Correctly Handling Input Signals  
Other Precautions  
Confirm that you have the correct model before using it.  
Malfunction due to noise may occur if input wiring is placed in the  
same duct or conduit as power lines or high-voltage lines. Separate  
input wiring from power lines and wire them in a separate system.  
Also, use shielded cables, use metal conduits, and keep wiring  
distances as short as possible.  
Be sure that all terminals are wired correctly.  
Always test the output status with a tester before using a Timer with  
a built-in keep relay (e.g., the H3CR-H and H3DE-H). Shock  
resulting from dropping the Timer during transport or handling may  
cause the output contacts to reverse or to be in a neutral status.  
Leaving the Timer with outputs ON at a high temperature for a long  
time may hasten the degradation of internal parts (such as  
electrolytic capacitors). Use the Timer in combination with relays  
and avoid leaving the Timer with the output turned ON for an  
extended period of time (e.g., for more than a month).  
Timers with Relays  
Do not connect a load that exceeds contact ratings, such as the  
switching capacity (contact voltage or contact current). Insulation  
faults, contact welding, contact faults, and other failures to achieve  
specified performance may occur and the relay may be damaged or  
may burn.  
Reference Example (Use the Timer as shown below.)  
Continued use with deteriorated performance may ultimately result  
in insulation breakdown between circuits or relay burning. The life  
of the built-in relay is greatly affected by switching conditions.  
Before using the Timer, test operation under actual application  
conditions and confirm that the switching frequency presents no  
problems in performance.  
X2/b  
T/a  
X1/a  
X1/a  
X
Auxiliary relay  
(e.g., MY Relays)  
T
X1  
X2  
Electrical life depends on the type of load, switching frequency, and  
ambient environment. Observe the following precautions when  
using the Timer. When switching a DC load, contact transfer may  
cause the contacts to stick or may cause contact failure. Confirm  
applicability and consider using a surge absorbing element. When  
switching at high frequencies, heat generated by arcing may cause  
contacts to melt or may cause metal corrosion. Consider  
connecting an arc absorbing element, reducing the switching  
frequency, or lowering the humidity.  
Be sure that only a qualified worker (e.g., an electrical engineer)  
performs electrical work for the Timer.  
The surge current depends on the type of load, which also affects  
contact switching frequency and the number of operations. Check  
the rated current and the surge current, and design the circuits with  
sufficient margin.  
Resistive load Solenoid load  
Motor load  
Incandescent  
lamp load  
Rated current  
10 to 20 times 5 to 10 times  
10 to 20 times  
the rated  
current  
the rated  
current  
the rated  
current  
Sodium light  
loads  
Capacitor  
loads  
Transformer  
loads  
Mercury light  
loads  
1 to 3 times the 20 to 40 times 5 to 15 times  
rated load  
1 to 3 times the  
the rated load the rated load rated load  
Arcing when switching and relay heating may result in ignition or  
explosion. Do not use the Timer in atmospheres subject to  
inflammable or explosive gases.  
Contact faults may occur. Do not use the Timer in atmospheres  
subject to sulfidizing gas, chloride gas, or silicon gas.  
The switching capacity for DC voltage loads is lower than that for  
AC voltage loads.  
Timers with Non-contact Outputs  
Short faults or open faults may occur due to destruction of the  
output element. Do not use the Timer for a load that exceeds the  
rated output current.  
Short faults or open faults may occur due to destruction of the  
output element from reverse electromotive force. When using the  
Timer for a DC inductive load, always connect a diode as a  
countermeasure against reverse electromotive force.  
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.  
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.  
In the interest of product improvement, specifications are subject to change without notice.  
(c)Copyright OMRON Corporation 2007 All Rights Reserved.  
http://www.ia.omron.com/  
C-2  
Read and Understand This Catalog  
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or  
comments.  
Warranty and Limitations of Liability  
WARRANTY  
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if  
specified) from date of sale by OMRON.  
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR  
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS  
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER  
WARRANTIES, EXPRESS OR IMPLIED.  
LIMITATIONS OF LIABILITY  
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS, OR COMMERCIAL  
LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR  
STRICT LIABILITY.  
In no event shall responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.  
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS  
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT  
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.  
Application Considerations  
SUITABILITY FOR USE  
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's  
application or use of the product.  
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the  
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,  
machine, system, or other application or use.  
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible  
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:  
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.  
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety  
equipment, and installations subject to separate industry or government regulations.  
• Systems, machines, and equipment that could present a risk to life or property.  
Please know and observe all prohibitions of use applicable to the products.  
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE  
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERLY RATED AND  
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.  
Disclaimers  
CHANGE IN SPECIFICATIONS  
Product specifications and accessories may be changed at any time based on improvements and other reasons.  
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.  
However, some specifications of the product may be changed without any notice. When in doubt, special model numbers may be assigned to fix  
or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual  
specifications of purchased product.  
DIMENSIONS AND WEIGHTS  
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.  
ERRORS AND OMISSIONS  
The information in this catalog has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,  
typographical, or proofreading errors, or omissions.  
PERFORMANCE DATA  
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent  
the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON  
Warranty and Limitations of Liability.  
PROGRAMMABLE PRODUCTS  
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.  
COPYRIGHT AND COPY PERMISSION  
This catalog shall not be copied for sales or promotions without permission.  
This catalog is protected by copyright and is intended solely for use in conjunction with the product. Please notify us before copying or reproducing this  
catalog in any manner, for any other purpose. If copying or transmitting this catalog to another, please copy or transmit it in its entirety.  
2007.3  
In the interest of product improvement, specifications are subject to change without notice.  
OMRON Corporation  
Industrial Automation Company  
http://www.ia.omron.com/  
(c)Copyright OMRON Corporation 2007 All Rights Reserved.  

相关型号:

SI9130DB

5- and 3.3-V Step-Down Synchronous Converters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1-E3

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135_11

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9136_11

Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130CG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130LG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130_11

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137DB

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137LG

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9122E

500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification Drivers

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY