Weekly Timer
H5S
Timer Provides Prompted Programming,
Flexibility in Programs Within the Week
■ AM/PM display
■ 24 program steps
■ A different program possible each day
■ Over midnight settings possible
■ Two independent 15 A control circuits
with manual override
■ Automatic or manual operation following
power failure
■ Field-adjustable ON/OFF, cycle and
pulse output
■ Easy-to-use prompted programming
■ Wide supply voltage range
■ Battery backup for memory protection
■ Protective cover and other accessories
may be ordered separately
Ordering Information
■ TIMERS
Timing function
Contact type
Terminal form
Mounting
ON/OFF and cycle operations up to one week
Two SPST-NO time limit contacts with manual override switches
Screw terminals
Panel mounting
H5S-B
Surface or track mounting
Part number
Supply voltage
H5S-FB
100 to 240 VAC, 50/60 Hz
■ TIME RANGES
Time setting range
Program capacity
Cycle length
00:00 a.m. to 11:59 p.m.
24 steps: ON = 1 step, OFF = 1 step, CYCLE = 4 steps, PULSE = 1 step
From 1 minute up to a full week
1 minute
Display time division
Operation
Weekly operation (multiple-day operation possible)
Cycle operation
Pulse-out operation (pulse width can be set in units of 1 second from 1 to 59 seconds and in units
of 1 minute from 1 to 60 minutes)
Day override operation (operation for one day can be also executed on any other day)
Forced ON/OFF operation
Manual or automatic operation selectable on recovery from power failure
■ ACCESSORIES
Description
Part number
Y92A-72C
Hard plastic cover
Track mounting adapter for H5S-FB
Mounting track 50 cm (1.64 ft) length
Y92F-90
PFP-50N
PFP-100N
PFP-M
1 m (3.28 ft) length
End plate
1
H5S
H5S
Specifications
Part number
H5S-B
H5S-FB
Supply
voltage
AC
DC
100 to 240 V, 50/60 Hz
–
Operating voltage
85 to 110% of rated voltage (85 to 264 VAC), 50/60 Hz
AC
DC
10 VA
Power
consumption
–
Timing functions
Reset (boot) input
ON and OFF programming
No-voltage, 0.2 sec minimum
Type
Time limit
Pulse
SPST-NO x 2 circuits
Control
output
1 sec to 59 seconds or 1 min to 60 min
15 A, 250 VAC resistive load
Max. load
Min. load
100 mA, 5 VDC
Repeat accuracy
Long-term error
Setting error
±0.01%, ±0.05 second max.
±15 seconds per month at 25°C (77°F); ±4 seconds/week, ±1 minute/4 months
Included in "Repeat Accuracy"
Indicators
10 mm LCD; day, hours (a.m., p.m.), minutes (0:00 to 11:59 a.m., 0:00 to 11:59 p.m.)
Digital display of program steps during operation
Timing chart display of program steps during operation
Plastic
Materials
Mounting
Connections
Weight
Panel
Surface and track with adapter
Terminal screws
200 g (7 oz.)
Approvals
UL/CSA/SEV
Operating ambient temperature
Humidity
-10° to 55°C (14° to 131°F)
35 to 85% RH
Vibration Mechanical durability
Malfunction durability
10 to 55 Hz, 0.75 mm (0.03 in) double amplitude
10 to 55 Hz, 0.5 mm (0.02 in) double amplitude
30 G
Shock
Mechanical durability
Malfunction durability
10 G
Variation due to voltage change
Variation due to temperature change
Insulation resistance
Included in "Repeat accuracy"
Included in "Repeat accuracy"
100 MΩ minimum between current-carrying terminals and non-current-carrying metal parts;
operation circuit and contact control output circuit; non-continuous contacts
Dielectric strength
2,000 VAC, 50/60 Hz for 1 minute between current-carrying terminals and non-current-
carrying metal parts, and operation circuit and contact control output circuit.
1,000 VAC, 50/60 Hz for 1 minute between non-continuous contacts
Service life
Electrical
50,000 operations minimum, 15 A, 250 VAC, resistive load
50,000 operations minimum, 1 HP, 250 VAC, motor load
50,000 operations minimum, 10 A, 250 VAC, inductive load (p.f.=0.7)
50,000 operations minimum, 100 W, 100 VAC, lamp load
10,000 operations minimum, 300 W, 100 VAC, lamp load
2
H5S
H5S
Dimensions
Unit: mm (inch)
■ TIMERS
H5S-B Panel-Mounting Type
72
(2.83)
49
(1.93)
72
(2.83)
67.6
(2.66)
72
67.6
(2.66)
58.5
(2.30)
H5S-FB Surface-Mounting Type
49
(1.93)
72
(2.83)
37
(1.46)
67.6
(2.66)
17.7 (0.69)
72
(2.83)
72
(2.83)
126.7
(4.99)
96
(3.78)
Track mounting adapter
Y92F-90 (order separately)
58.5
(2.30)
68
(2.68)
■ PROTECTIVE COVER
Y92A-72C
The hard plastic protective cover prevents
accidental resetting. It also shields the front
panel from dirt and water. The cover is
intended for use in areas where unusual
service conditions do not exist.
75
(2.95)
75
(2.95)
12.5 (0.49)
overall
depth
3
H5S
H5S
■ TRACK MOUNTING ADAPTER
Y92F-90
The H5S-FB timer can be mounted on DIN rail track using the
Y92F-90 adapter. Two screws supplied with the timer fasten
the adapter to the timer.
96
(3.78)
9.5
(0.37)
■ MOUNTING TRACK AND ACCESSORIES
PFP-100N/PFP-50N DIN Rail
PFP-M End Plate
Connections
■ H5S-B PANEL MOUNTING TYPE
AC
common
(Rear view)
No-voltage
contacts of a
Power source
for load 2
pushbutton or
relay for power
restoration input
(necessary for
manual restoration
from power failure)
AC hot
➚
When separate
power sources
are used for load
and H5S.
When load and
H5S share the
same power
source
AC
common
AC hot
Power source
■ H5S-B PANEL MOUNTING TYPE
■ H5S-FB SURFACE MOUNTING TYPE
(Rear view)
(Front view)
*Power restoration input
*Power restoration input
Output 2
Output 2
7
8
9
10
6 7 8 9
AC
1
2
3
4
2
Output 1
3 4 5
Output 1
100 to 240 VAC
Power Source
100 to 240 VAC
Power Source
4
H5S
H5S
■ H5S-FB SURFACE MOUNTING TYPE
AC
common
(Front view)
Power source
for load 2
AC hot
When separate
power sources are
used for load and H5S
No-voltage contacts of a
pushbutton switch or
relay for power restoration
input (necessary for manual
restoration from power failure)
When load and
H5S share the
same power
source
AC
common
Power source
AC hot
Operation
■ NOMENCLATURE
Key Operations
Front Panel with Cover Open
No.
1
Function
Shifts the cursor (▼) specifying a day to the
right.
2
Sets or cancels a specified day.
Sets a time or ON/OFF time width.
3
4
Monitors the parameters set for an operation
during an operation.
5
Sets parameters.
6
7
Sets a time adjustment mode.
Specifies a cyclic operation, or sets a pulse width.
Specifies a day substitution operation.
8
9
Cancels the parameters set for each circuit, or a
day substitution operation.
10
11
P1: Circuit 1 programming mode
P2: Circuit 2 programming mode
RUN: RUN mode
ON: Turns on the output regardless of the program.
AUTO: Executes according to the program.
12
OFF: Turns off the output regardless of the program.
Display
TIMER: Executes an ordinary timer or cyclic
operation.
PULSE: Executes a pulse-output operation.
13
14
Specifies automatic or manual operation following
a power failure.
5
H5S
H5S
■ OPERATING FUNCTIONS
Timer Operation
Controls the output according to the set time of ON and OFF (the time can be set in units of
1 minute)
Pulse-0utput operation
Cycle operation
Produces the output for a fixed duration at the set ON (pulse width: 1 to 59 seconds, or
1 minute to 59 minutes). The pulse width can be set in units of 1 second or 1 minute.
Repeatedly performs an ON/OFF operation during a specific period, which can be set in
units of 1 minute
Forcibly turns ON/OFF the output by a slide switch
Forced ON/OFF operation
Operation on power restoration
AUTO: Operation is automatically started on power recovery
MANUAL: Operation is started by applying an external no-voltage signal of 0.2 sec minimum
after power recovery.
Power
AUTO
Auto
Manual
operation
Note that the signal must be a low to high transition (open to closed switching).
MANUAL
External
input
Day override operation
Executes a day's operation on another day. The specified new operation is performed only
for one week. This could be used for holidays.
■ PROGRAMMING
Before setting the parameters necessary
for each operation, the operation of circuits
(outputs 1 and 2) must be determined.
Also, specify whether the operation is
restarted automatically or manually after
power failure recovery.
In this example, circuit 1 performs an
ordinary timer operation, while circuit
2 performs a pulse output operation and
automatic operation restarting
mode is set.
6
H5S
H5S
Time Adjustment
The following figures show how to set the time to 10:30 a.m., Wednesday. Mode selector switch should be in RUN position.
The time and day can also be adjusted or changed while the timer is operating. In the following example, the current set time,
10:30 a.m., Wednesday, is changed to 4:00 a.m., Monday.
Ordinary Timer Operation
In this example, circuit 1 is set to operate at 8:30 a.m. and
stop at 5:15 p.m., from Monday through Friday. Set mode
switch to P1.
7
H5S
H5S
Multiple-Day Operation
The timer turns ON circuit 1 at 8:30 a.m.
on Monday, and turns it OFF at 0:00 p.m. on
Saturday. Set mode selector to P1.
Cycle Operation
Circuit 1 is set to turn ON for 2 minutes and OFF
for 1 minute repeatedly, from 8:30 a.m. to 5:15 p.m.
on Monday. Set mode selector to P1.
Pulse Output Operation
Circuit 2 is turned ON for 30 seconds at 8:25 a.m.,
Monday through Friday. Set mode selector to P2.
8
H5S
H5S
Checking the Set Time
The set times can be checked and, if necessary,
changed in the sequence they were set. In this
example, the times set for circuit 1 are checked. Set
mode selector switch to P1.
The set times can be checked in the sequence the
timer is to operate. In the following example, the times
set for today are checked. Set mode selector switch to
RUN.
It is also possible to check the timing operations in the sequence they are to be executed. The operations to be performed Thursday are
checked. Mode selector switch is in RUN.
9
H5S
H5S
Day Override
Wednesday and Thursday are holidays in the next week, the operations set for Sunday will be executed on these days. (The time switch
executes the new program for only one week from the day next to when the program is set. After the one week, the timer operates
according to the previous program.)
Canceling the Setting
All the operations of circuit 1 or 2 can be
cancelled. In the following example, all the
operations of circuit 1 are cancelled. Set mode
selector switch to P1.
In the next example an overriden operation
is cancelled. Set mode selector to RUN.
■ PRECAUTIONS
Ordinary Timer Operation
If both settings 1 and 2 are for an ON/OFF or pulse operation, the
output is continuously produced without being interrupted. For
example, if setting 1 is for cyclic operation, and 2 is set for an ON/OFF
operation, the cyclic operation is performed during period of a to b, and
the ON/OFF operation is performed from b to c.
10
H5S
H5S
Multiple-Day Operation
If more than one day is specified and when the output is turned
on, it is turned off on the day when the first OFF time is set.
If an ON and an OFF have been set at the same time of the same
day (such setting is possible), no operation is performed.
If the MODE switch is set to the P1 (or P2) position, no output is
produced. Therefore, after setting has been done, set the MODE
switch to the RUN position and confirm that the automatic operation
indicator lights.
The set data may be erased if the OUT switch is moved between
the TIMER and PULSE positions after the data has been set.
Mounting
■ PANEL MOUNTING H5S-B
49
(1.93)
Panel cutout
(2.68)
(2.68)
■ SURFACE MOUNTING H5S-FB
Note: Mounting hole diameter varies with the panel thickness
and material. The table below is for soft iron panel.
Mounting holes
Panel thickness
Hole diameter
0.8 to 1.2 mm
1.6 to 4.0 mm
(0.03 to 0.05 in) (0.06 to 0.16 in)
3.6 mm (0.12 in) (3.7 mm (0.146 in)
126.7
(4.99)
For diecast aluminum panels, the hole diameter should be
larger, 4 mm (0.157 in) diameter as shown.
(3.50)
(2.20)
62
(2.44)
11
H5S
H5S
■ TRACK MOUNTING H5S-FB
Use Y92F-90 Track Mounting Base
79.8
(3.14)
NOTE: ALL DIMENSIONS ARE IN MILLIMETERS. To convert millimeters into inches divide by 25.4.
OMRON ELECTRONICS, INC.
One East Commerce Drive
Schaumburg, IL 60173
OMRON CANADA, INC.
885 Milner Avenue
Scarborough, Ontario M1B 5V8
1-800-55-OMRON
416-286-6465
Cat. No. GC TI8
11/97
Specifications subject to change without notice.
Printed in the U.S.A.
12