Weekly Timer  
H5S  
Timer Provides Prompted Programming,  
Flexibility in Programs Within the Week  
AM/PM display  
24 program steps  
A different program possible each day  
Over midnight settings possible  
Two independent 15 A control circuits  
with manual override  
Automatic or manual operation following  
power failure  
Field-adjustable ON/OFF, cycle and  
pulse output  
Easy-to-use prompted programming  
Wide supply voltage range  
Battery backup for memory protection  
Protective cover and other accessories  
may be ordered separately  
Ordering Information  
TIMERS  
Timing function  
Contact type  
Terminal form  
Mounting  
ON/OFF and cycle operations up to one week  
Two SPST-NO time limit contacts with manual override switches  
Screw terminals  
Panel mounting  
H5S-B  
Surface or track mounting  
Part number  
Supply voltage  
H5S-FB  
100 to 240 VAC, 50/60 Hz  
TIME RANGES  
Time setting range  
Program capacity  
Cycle length  
00:00 a.m. to 11:59 p.m.  
24 steps: ON = 1 step, OFF = 1 step, CYCLE = 4 steps, PULSE = 1 step  
From 1 minute up to a full week  
1 minute  
Display time division  
Operation  
Weekly operation (multiple-day operation possible)  
Cycle operation  
Pulse-out operation (pulse width can be set in units of 1 second from 1 to 59 seconds and in units  
of 1 minute from 1 to 60 minutes)  
Day override operation (operation for one day can be also executed on any other day)  
Forced ON/OFF operation  
Manual or automatic operation selectable on recovery from power failure  
ACCESSORIES  
Description  
Part number  
Y92A-72C  
Hard plastic cover  
Track mounting adapter for H5S-FB  
Mounting track 50 cm (1.64 ft) length  
Y92F-90  
PFP-50N  
PFP-100N  
PFP-M  
1 m (3.28 ft) length  
End plate  
1
H5S  
H5S  
Specifications  
Part number  
H5S-B  
H5S-FB  
Supply  
voltage  
AC  
DC  
100 to 240 V, 50/60 Hz  
Operating voltage  
85 to 110% of rated voltage (85 to 264 VAC), 50/60 Hz  
AC  
DC  
10 VA  
Power  
consumption  
Timing functions  
Reset (boot) input  
ON and OFF programming  
No-voltage, 0.2 sec minimum  
Type  
Time limit  
Pulse  
SPST-NO x 2 circuits  
Control  
output  
1 sec to 59 seconds or 1 min to 60 min  
15 A, 250 VAC resistive load  
Max. load  
Min. load  
100 mA, 5 VDC  
Repeat accuracy  
Long-term error  
Setting error  
±0.01%, ±0.05 second max.  
±15 seconds per month at 25°C (77°F); ±4 seconds/week, ±1 minute/4 months  
Included in "Repeat Accuracy"  
Indicators  
10 mm LCD; day, hours (a.m., p.m.), minutes (0:00 to 11:59 a.m., 0:00 to 11:59 p.m.)  
Digital display of program steps during operation  
Timing chart display of program steps during operation  
Plastic  
Materials  
Mounting  
Connections  
Weight  
Panel  
Surface and track with adapter  
Terminal screws  
200 g (7 oz.)  
Approvals  
UL/CSA/SEV  
Operating ambient temperature  
Humidity  
-10° to 55°C (14° to 131°F)  
35 to 85% RH  
Vibration Mechanical durability  
Malfunction durability  
10 to 55 Hz, 0.75 mm (0.03 in) double amplitude  
10 to 55 Hz, 0.5 mm (0.02 in) double amplitude  
30 G  
Shock  
Mechanical durability  
Malfunction durability  
10 G  
Variation due to voltage change  
Variation due to temperature change  
Insulation resistance  
Included in "Repeat accuracy"  
Included in "Repeat accuracy"  
100 Mminimum between current-carrying terminals and non-current-carrying metal parts;  
operation circuit and contact control output circuit; non-continuous contacts  
Dielectric strength  
2,000 VAC, 50/60 Hz for 1 minute between current-carrying terminals and non-current-  
carrying metal parts, and operation circuit and contact control output circuit.  
1,000 VAC, 50/60 Hz for 1 minute between non-continuous contacts  
Service life  
Electrical  
50,000 operations minimum, 15 A, 250 VAC, resistive load  
50,000 operations minimum, 1 HP, 250 VAC, motor load  
50,000 operations minimum, 10 A, 250 VAC, inductive load (p.f.=0.7)  
50,000 operations minimum, 100 W, 100 VAC, lamp load  
10,000 operations minimum, 300 W, 100 VAC, lamp load  
2
H5S  
H5S  
Dimensions  
Unit: mm (inch)  
TIMERS  
H5S-B Panel-Mounting Type  
72  
(2.83)  
49  
(1.93)  
72  
(2.83)  
67.6  
(2.66)  
72  
67.6  
(2.66)  
58.5  
(2.30)  
H5S-FB Surface-Mounting Type  
49  
(1.93)  
72  
(2.83)  
37  
(1.46)  
67.6  
(2.66)  
17.7 (0.69)  
72  
(2.83)  
72  
(2.83)  
126.7  
(4.99)  
96  
(3.78)  
Track mounting adapter  
Y92F-90 (order separately)  
58.5  
(2.30)  
68  
(2.68)  
PROTECTIVE COVER  
Y92A-72C  
The hard plastic protective cover prevents  
accidental resetting. It also shields the front  
panel from dirt and water. The cover is  
intended for use in areas where unusual  
service conditions do not exist.  
75  
(2.95)  
75  
(2.95)  
12.5 (0.49)  
overall  
depth  
3
H5S  
H5S  
TRACK MOUNTING ADAPTER  
Y92F-90  
The H5S-FB timer can be mounted on DIN rail track using the  
Y92F-90 adapter. Two screws supplied with the timer fasten  
the adapter to the timer.  
96  
(3.78)  
9.5  
(0.37)  
MOUNTING TRACK AND ACCESSORIES  
PFP-100N/PFP-50N DIN Rail  
PFP-M End Plate  
Connections  
H5S-B PANEL MOUNTING TYPE  
AC  
common  
(Rear view)  
No-voltage  
contacts of a  
Power source  
for load 2  
pushbutton or  
relay for power  
restoration input  
(necessary for  
manual restoration  
from power failure)  
AC hot  
When separate  
power sources  
are used for load  
and H5S.  
When load and  
H5S share the  
same power  
source  
AC  
common  
AC hot  
Power source  
H5S-B PANEL MOUNTING TYPE  
H5S-FB SURFACE MOUNTING TYPE  
(Rear view)  
(Front view)  
*Power restoration input  
*Power restoration input  
Output 2  
Output 2  
7
8
9
10  
6 7 8 9  
AC  
1
2
3
4
2
Output 1  
3 4 5  
Output 1  
100 to 240 VAC  
Power Source  
100 to 240 VAC  
Power Source  
4
H5S  
H5S  
H5S-FB SURFACE MOUNTING TYPE  
AC  
common  
(Front view)  
Power source  
for load 2  
AC hot  
When separate  
power sources are  
used for load and H5S  
No-voltage contacts of a  
pushbutton switch or  
relay for power restoration  
input (necessary for manual  
restoration from power failure)  
When load and  
H5S share the  
same power  
source  
AC  
common  
Power source  
AC hot  
Operation  
NOMENCLATURE  
Key Operations  
Front Panel with Cover Open  
No.  
1
Function  
Shifts the cursor () specifying a day to the  
right.  
2
Sets or cancels a specified day.  
Sets a time or ON/OFF time width.  
3
4
Monitors the parameters set for an operation  
during an operation.  
5
Sets parameters.  
6
7
Sets a time adjustment mode.  
Specifies a cyclic operation, or sets a pulse width.  
Specifies a day substitution operation.  
8
9
Cancels the parameters set for each circuit, or a  
day substitution operation.  
10  
11  
P1: Circuit 1 programming mode  
P2: Circuit 2 programming mode  
RUN: RUN mode  
ON: Turns on the output regardless of the program.  
AUTO: Executes according to the program.  
12  
OFF: Turns off the output regardless of the program.  
Display  
TIMER: Executes an ordinary timer or cyclic  
operation.  
PULSE: Executes a pulse-output operation.  
13  
14  
Specifies automatic or manual operation following  
a power failure.  
5
H5S  
H5S  
OPERATING FUNCTIONS  
Timer Operation  
Controls the output according to the set time of ON and OFF (the time can be set in units of  
1 minute)  
Pulse-0utput operation  
Cycle operation  
Produces the output for a fixed duration at the set ON (pulse width: 1 to 59 seconds, or  
1 minute to 59 minutes). The pulse width can be set in units of 1 second or 1 minute.  
Repeatedly performs an ON/OFF operation during a specific period, which can be set in  
units of 1 minute  
Forcibly turns ON/OFF the output by a slide switch  
Forced ON/OFF operation  
Operation on power restoration  
AUTO: Operation is automatically started on power recovery  
MANUAL: Operation is started by applying an external no-voltage signal of 0.2 sec minimum  
after power recovery.  
Power  
AUTO  
Auto  
Manual  
operation  
Note that the signal must be a low to high transition (open to closed switching).  
MANUAL  
External  
input  
Day override operation  
Executes a day's operation on another day. The specified new operation is performed only  
for one week. This could be used for holidays.  
PROGRAMMING  
Before setting the parameters necessary  
for each operation, the operation of circuits  
(outputs 1 and 2) must be determined.  
Also, specify whether the operation is  
restarted automatically or manually after  
power failure recovery.  
In this example, circuit 1 performs an  
ordinary timer operation, while circuit  
2 performs a pulse output operation and  
automatic operation restarting  
mode is set.  
6
H5S  
H5S  
Time Adjustment  
The following figures show how to set the time to 10:30 a.m., Wednesday. Mode selector switch should be in RUN position.  
The time and day can also be adjusted or changed while the timer is operating. In the following example, the current set time,  
10:30 a.m., Wednesday, is changed to 4:00 a.m., Monday.  
Ordinary Timer Operation  
In this example, circuit 1 is set to operate at 8:30 a.m. and  
stop at 5:15 p.m., from Monday through Friday. Set mode  
switch to P1.  
7
H5S  
H5S  
Multiple-Day Operation  
The timer turns ON circuit 1 at 8:30 a.m.  
on Monday, and turns it OFF at 0:00 p.m. on  
Saturday. Set mode selector to P1.  
Cycle Operation  
Circuit 1 is set to turn ON for 2 minutes and OFF  
for 1 minute repeatedly, from 8:30 a.m. to 5:15 p.m.  
on Monday. Set mode selector to P1.  
Pulse Output Operation  
Circuit 2 is turned ON for 30 seconds at 8:25 a.m.,  
Monday through Friday. Set mode selector to P2.  
8
H5S  
H5S  
Checking the Set Time  
The set times can be checked and, if necessary,  
changed in the sequence they were set. In this  
example, the times set for circuit 1 are checked. Set  
mode selector switch to P1.  
The set times can be checked in the sequence the  
timer is to operate. In the following example, the times  
set for today are checked. Set mode selector switch to  
RUN.  
It is also possible to check the timing operations in the sequence they are to be executed. The operations to be performed Thursday are  
checked. Mode selector switch is in RUN.  
9
H5S  
H5S  
Day Override  
Wednesday and Thursday are holidays in the next week, the operations set for Sunday will be executed on these days. (The time switch  
executes the new program for only one week from the day next to when the program is set. After the one week, the timer operates  
according to the previous program.)  
Canceling the Setting  
All the operations of circuit 1 or 2 can be  
cancelled. In the following example, all the  
operations of circuit 1 are cancelled. Set mode  
selector switch to P1.  
In the next example an overriden operation  
is cancelled. Set mode selector to RUN.  
PRECAUTIONS  
Ordinary Timer Operation  
If both settings 1 and 2 are for an ON/OFF or pulse operation, the  
output is continuously produced without being interrupted. For  
example, if setting 1 is for cyclic operation, and 2 is set for an ON/OFF  
operation, the cyclic operation is performed during period of a to b, and  
the ON/OFF operation is performed from b to c.  
10  
H5S  
H5S  
Multiple-Day Operation  
If more than one day is specified and when the output is turned  
on, it is turned off on the day when the first OFF time is set.  
If an ON and an OFF have been set at the same time of the same  
day (such setting is possible), no operation is performed.  
If the MODE switch is set to the P1 (or P2) position, no output is  
produced. Therefore, after setting has been done, set the MODE  
switch to the RUN position and confirm that the automatic operation  
indicator lights.  
The set data may be erased if the OUT switch is moved between  
the TIMER and PULSE positions after the data has been set.  
Mounting  
PANEL MOUNTING H5S-B  
49  
(1.93)  
Panel cutout  
(2.68)  
(2.68)  
SURFACE MOUNTING H5S-FB  
Note: Mounting hole diameter varies with the panel thickness  
and material. The table below is for soft iron panel.  
Mounting holes  
Panel thickness  
Hole diameter  
0.8 to 1.2 mm  
1.6 to 4.0 mm  
(0.03 to 0.05 in) (0.06 to 0.16 in)  
3.6 mm (0.12 in) (3.7 mm (0.146 in)  
126.7  
(4.99)  
For diecast aluminum panels, the hole diameter should be  
larger, 4 mm (0.157 in) diameter as shown.  
(3.50)  
(2.20)  
62  
(2.44)  
11  
H5S  
H5S  
TRACK MOUNTING H5S-FB  
Use Y92F-90 Track Mounting Base  
79.8  
(3.14)  
NOTE: ALL DIMENSIONS ARE IN MILLIMETERS. To convert millimeters into inches divide by 25.4.  
OMRON ELECTRONICS, INC.  
One East Commerce Drive  
Schaumburg, IL 60173  
OMRON CANADA, INC.  
885 Milner Avenue  
Scarborough, Ontario M1B 5V8  
1-800-55-OMRON  
416-286-6465  
Cat. No. GC TI8  
11/97  
Specifications subject to change without notice.  
Printed in the U.S.A.  
12  

相关型号:

Y92A-72N

Watertight Panel Covers
OMRON

Y92A-96B

This Compact Cam Positioner, Popular for Its Ease-of-use, Now Comes with Even Better Functions.
OMRON

Y92A-96N

Watertight Panel Covers
OMRON

Y92B-A100

Solid State Relays G3NA
OMRON

Y92B-A150N

Solid State Relays G3NA
OMRON

Y92B-A250

Solid State Relays G3NA
OMRON

Y92B-N100

Solid State Relays G3NA
OMRON

Y92B-N150

Solid State Relays G3NA
OMRON

Y92B-N50

Solid State Relays G3NA
OMRON

Y92B-P150

HEAT SINK 0.63DEGC/W FOR G3PB
OMRON

Y92B-P200

HEAT SINK 0.43DEGC/W FOR G3PB
OMRON

Y92B-P250

Solid State Relays G3NA
OMRON