Electronic miniature circuit-breaker
CLIPLINE
Data sheet
103906_en_01
© PHOENIX CONTACT - 09/2009
The miniature circuit-breaker has a design width of 12.5 mm
1
Description
and can be snapped onto NS 35 DIN rails using a modular
approach. It is equipped with screw connections.
The EC-E... electronic miniature circuit-breaker selectively
protects all 24 V DC load circuits on power supply units. A
combination of active electronic current limitation for short
circuits and an overload shutdown function from 1.1 x IN
upwards ensures that the miniature circuit-breaker can
react to overloads faster than the power supply unit. In this
case, the residual current is constantly restricted to 1.3 -
1.8 times the nominal current.
This enables capacitive loads of up to 20,000 µF to be
switched on; loads are shut down only in the event of an
overload or short circuit.
Once an overload or short circuit has been detected in the
load circuit, the load output of the EC-E... is blocked. The
current flow in the faulty circuit is interrupted. The EC-E...
and, therefore, the current circuit can be activated again
using the electronic reset input or manually on the device
using the slide switch.
1.1
Properties
–
Selective load protection, electronic shutdown
characteristic curve
–
Active current limitation when switching on capacitive
loads of up to 20,000 µF and in the event of an
overload/short circuit
–
–
Nominal current can be selected in fixed current
strengths from 0.5 A ... 12 A
Safe overload shutdown from 1.1 x IN upwards, even
with long load lines or small cable cross-sections
–
–
Manual on/off switch (S1)
Clear signaling by means of LED, SF status output, or F
alarm output (signal contact), (can be combined)
–
–
–
RE electronic reset input (option)
Integrated fail-safe element, adapted to nominal current
Straightforward wiring using LINE+ power rail and 0 V,
as well as signal rails and signal bridges
Wiring and signaling tasks can be implemented easily using
power rails and plug-in bridges.
A multi-color LED and the integrated status output display
the operating and fault state.
NOTE: Make sure that you adapt the cable cross-section of the relevant load circuit to the nominal current of the
EC-E... being used.
Take special precautions in the system or machine to eliminate the possibility of system parts restarting (in
accordance with the Machinery Directive 2006/42/EC and EN 60204-1). In the event of a fault (short circuit/
overload), the EC-E... shuts down the load circuit electronically.
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/download.
This data sheet is valid for all products listed on the following page:
EC-E...
2
Ordering data
Electronic miniature circuit-breakers
Description
Type
Order No.
Pcs./Pkt.
Nominal
current
Electronic miniature circuit-breaker with signal contact: 1 N/O contact 0.5 A
Electronic miniature circuit-breaker with signal contact: 1 N/O contact 1 A
Electronic miniature circuit-breaker with signal contact: 1 N/O contact 2 A
Electronic miniature circuit-breaker with signal contact: 1 N/O contact 3 A
Electronic miniature circuit-breaker with signal contact: 1 N/O contact 4 A
Electronic miniature circuit-breaker with signal contact: 1 N/O contact 6 A
Electronic miniature circuit-breaker with signal contact: 1 N/O contact 8 A
Electronic miniature circuit-breaker with signal contact: 1 N/O contact 10 A
Electronic miniature circuit-breaker with signal contact: 1 N/O contact 12 A
Electronic miniature circuit-breaker with signal contact: 1 N/C contact 0.5 A
Electronic miniature circuit-breaker with signal contact: 1 N/C contact 1 A
Electronic miniature circuit-breaker with signal contact: 1 N/C contact 2 A
Electronic miniature circuit-breaker with signal contact: 1 N/C contact 3 A
Electronic miniature circuit-breaker with signal contact: 1 N/C contact 4 A
Electronic miniature circuit-breaker with signal contact: 1 N/C contact 6 A
Electronic miniature circuit-breaker with signal contact: 1 N/C contact 8 A
Electronic miniature circuit-breaker with signal contact: 1 N/C contact 10 A
Electronic miniature circuit-breaker with signal contact: 1 N/C contact 12 A
Electronic miniature circuit-breaker with reset input and status output 0.5 A
Electronic miniature circuit-breaker with reset input and status output 1 A
Electronic miniature circuit-breaker with reset input and status output 2 A
Electronic miniature circuit-breaker with reset input and status output 3 A
Electronic miniature circuit-breaker with reset input and status output 4 A
Electronic miniature circuit-breaker with reset input and status output 6 A
Electronic miniature circuit-breaker with reset input and status output 8 A
Electronic miniature circuit-breaker with reset input and status output 10 A
Electronic miniature circuit-breaker with reset input and status output 12 A
EC-E1 0.5 A
EC-E1 1.0 A
EC-E1 2.0 A
EC-E1 3.0 A
EC-E1 4.0 A
EC-E1 6.0 A
EC-E1 8.0 A
EC-E1 10 A
EC-E1 12 A
EC-E4 0.5 A
EC-E4 1.0 A
EC-E4 2.0 A
EC-E4 3.0 A
EC-E4 4.0 A
EC-E4 6.0 A
EC-E4 8.0 A
0903022
0903023
0903024
0903025
0903026
0903028
0903029
0903030
0903031
0903040
0903032
0903033
0903034
0903035
0903036
0903037
0903038
0903039
0903041
0903042
0903043
0903044
0903045
0903046
0903047
0903048
0903049
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
EC-E4 10 A
EC-E4 12 A
EC-E 0.5 A 24 V DC
EC-E 1.0 A 24 V DC
EC-E 2.0 A 24 V DC
EC-E 3.0 A 24 V DC
EC-E 4.0 A 24 V DC
EC-E 6.0 A 24 V DC
EC-E 8.0 A 24 V DC
EC-E 10 A 24 V DC
EC-E 12 A 24 V DC
Version
Signal input
Signal output
F alarm output (signal contact)
SF status output
RE +24 V reset input
Individual-signal N/O contact
Individual-signal N/C contact
(normally closed)
SF +24 V status output = OK
(normally open)
EC-E1
EC-E4
EC-E
–
–
x
x
–
–
–
x
–
–
–
x
Accessories
Description
Continuous plug-in bridge for LINE+ and 0 V, insulated with gray
material, 500 mm long, can be cut to length
Type
Order No.
0901028
Pcs./Pkt.
10
Gray FBST 500 TMC-NGY
Current carrying capacity with one supply: I
(recommendation: central input)
= 50 A,
max
Current carrying capacity with two supplies: I
= 63 A
max
Continuous plug-in bridge for signal contacts and reset inputs,
insulated with gray material, 500 mm long, can be cut to length
Blue FBST 500-PLC-BU
Red FBST 500-PLC-RD
2966692
2966789
20
20
Current carrying capacity with one supply:
With signal contacts connected in series: I
Zack marker strip, flat, 10-section
Screwdriver
= 1 A
= 0.5 A
max
max
UC-TMF12
SZS 0.6X3.5
0819233
1205053
10
10
103906_en_01
PHOENIX CONTACT
2
EC-E...
3
Technical data
NOTE: Data apply where T = 25°C and U = 24 V DC.
A
B
Operating data
Nominal voltage U
24 V DC (18 V DC ... 32 V DC)
B
Nominal current I
Depending on product version selected:
N
Fixed current strengths: 0.5 A, 1 A, 2 A, 3 A, 4 A, 6 A, 8 A, 10 A, 12 A
Closed-circuit current I
When ON: Typically 20 mA ... 30 mA, depending on signal output
0
Shutdown
Shutdown times
Typical behavior
Refer to the time/current characteristic curve (see page 8)
3 s where I
> 1.1 x I
load
N
100 ms ... 3 s where I
> 1.8 x I (or 1.5 x I /1.3 x I )
N N N
load
EC-E4: Pin 11/12
EC-E1: Pin 13/14
EC-E: SF 23, RE 22
Individual signaling (N/C contact)
Individual signaling (N/O contact)
RE reset input, SF status output
Status indicators
Operating state signaling
–
–
–
–
Multi-color LED
SF status output (option)
Floating signal contact (F alarm output) (option)
On/off setting for switch S1
Multi-color LED
Green = Device switched on (S1 = ON) or load circuit/Power MOSFET forced
to trip
Orange = Overload or short circuit leading to electronic shutdown
Red = Device shut down electronically, load circuit/Power MOSFET switched
off, undervoltage (U < 8 V) or after switch-on up to end of switch-on delay
B
time
OFF: Manually switched off (S1 = OFF) or device voltage is disconnected
Load circuit
Load output
Power MOSFET switching output (positive switching)
Overload shutdown (OL)
Typically 1.1 x I (1.05 ... 1.35 x I )
N N
Short-circuit current I
Active current limitation (see page 5)
K
Temperature shutdown
Undervoltage monitoring for load output after each switch-on procedure
Switch-on delay t
Internal temperature monitoring with electronic shutdown
With hysteresis, no reset required: Load "OFF" at U < 8 V
B
Typically 0.5 s after reset and after U applied
B
Start
Load circuit shutdown
Free running circuit
Parallel connection of multiple load outputs
Electronic shutdown after overload/short circuit
External free-wheeling diode recommended for inductive load
Not permitted
F alarm output, signal contact (for EC-E1 and EC-E4 only)
Electrical data
Floating signal contact
30 V DC/0.5 A maximum, 10 V/10 mA minimum
Normal state, LED lights up green
OFF state, LED off
U
–
–
is present, switch S1 is set to ON, and no overloads or short circuits occur
Device switched off (switch S1 set to OFF)
B
Operating voltage U is not present
B
103906_en_01
PHOENIX CONTACT
3
EC-E...
F alarm output, signal contact (for EC-E1 and EC-E4 only) (continued)
Fault state, LED lights up orange
Fault state, LED lights up red
Overload condition > 1.1 x I leading to electronic shutdown
N
–
–
–
–
Electronic shutdown after overload or short circuit
Device switched off with control signal (switch S1 set to ON)
EC-E1: Individual signal, N/O contact open, pins 13 and 14
EC-E4: Individual signal, N/C contact closed, pins 11 and 12
Fault description
F alarm output (signal contact) is in a fault state if
–
–
–
Operating voltage U is not present
B
ON/OFF switch S1 is set to OFF
The LED lights up red (electronic shutdown)
Status output (for EC-E only)
Electrical data
Positive-switching signal output,
switches U to pin 23,
B
nominal data: 24 V DC/0.2 A maximum (short-circuit-proof)
The status output is terminated internally to 0 V with a 10-kohm resistance.
OUT status
OFF state
EC-E... (OUT signal status), where U = +24 V
B
+24 V = S1 is ON, load output forced to trip
0 V = S1 is ON, load output blocked, and/or switch S1 is OFF.
LED lights up red
0 V level at status output in all cases where:
–
–
–
Switch S1 is set to ON, but the device is still subject to a switch-on delay
Switch S1 is set to OFF or control signal OFF, device is switched off
Operating voltage U is not present
B
Reset input (for EC-E only)
Electrical data
Maximum voltage: +32 V DC
High > 8 V DC ≤ 32 V DC
Low ≤ 3 V DC > 0 V DC
Current consumption: Typ. 2.6 mA (+24 V DC)
Minimum pulse duration: 10 ms
RE reset signal, pin 22
When the EC-E is electronically blocked, it can be switched on again remotely
on the falling edge of a +24 V DC pulse, using an external button. A common
reset signal can also be applied to several devices at the same time. Devices
that are switched on remain unaffected by this.
Connection terminal blocks
LINE+/LOAD+/0 V connection terminal blocks
Screw connections
M4
Connection capacity
1 conductor
2 conductors (two conductors with the same cross-section)
2 stranded conductors with a TWIN ferrule
Stripping length
Solid
0.5 mm ... 10 mm
0.5 mm ... 4 mm
Stranded
With ferrule
2
2
2
2
2
2
0.5 mm ... 10 mm
0.5 mm ... 10 mm
2
2
2
2
2
2
2
0.5 mm ... 4 mm
0.5 mm ... 2.5 mm
2
0.5 mm ... 6 mm
10 mm
Torque (EN 60934)
1.5 Nm ... 1.8 Nm
Signal connections for connection terminal blocks
Screw connections
Stranded connection capacity with ferrule
Stripping length
M3
2
2
0.25 mm ... 2.5 mm
8 mm
Torque (EN 60934)
0.5 Nm
103906_en_01
PHOENIX CONTACT
4
EC-E...
General data
Fail-safe element
No backup fuse required for EC-E... as a redundant fail-safe element is
integrated (fuse element)
Mounting the housing
DIN rail in acc. with EN 50022, NS 35 x 7.5
0°C ... +50°C (without condensation, see EN 60204-1)
-20°C ... +70°C
Ambient temperature (operation)
Ambient temperature (storage)
Humid heat
96 h, 95% relative humidity, 40°C
in acc. with IEC 60068-2-78, Test Cab. Climatic class 3K3 according to
EN 60721
Degree of protection (housing, terminals)
Installation dimensions (W x H x D)
Weight
IP20, DIN 40050
12.5 mm x 80 mm x 83 mm
Approx. 65 g
Tests/approvals
Conformance with EMC Directive 2004/108/EC
Noise emission: EN 61000-6-3
Noise immunity: EN 61000-6-2
Insulation coordination (IEC 60934)
Dielectric strength
0.5 kV/pollution degree 2, increased insulation in actuation area
32 V DC maximum (load circuit)
Insulation resistance ("off" state)
Vibration resistance
Approvals
None, electronic shutdown only
3g, tested in acc. with IEC 60068-2-6, test Fc
UL 2367, File E317172
Solid State Overcurrent Protectors
UL 1604, File E324415 (class I, division 2, groups A, B, C, D)
c
Voltage drop, current limitation, maximum load current
Nominal current I
Typical voltage drop U at
Active current limitation
(typical)
Max. load current at 100% OT,
= 40°C
Max. load current at 100% OT,
= 50°C
N
ON
I
T
T
A
N
A
0.5 A
1 A
2 A
3 A
4 A
6 A
8 A
10 A
12 A
70 mV
80 mV
130 mV
80 mV
100 mV
130 mV
120 mV
150 mV
180 mV
1.8 x I
1.8 x I
1.8 x I
1.8 x I
1.8 x I
1.8 x I
1.5 x I
1.5 x I
0.5 A
1 A
2 A
3 A
4 A
6 A
8 A
10 A
12 A
0.5 A
1 A
2 A
3 A
4 A
5 A
7 A
9 A
10.8 A
N
N
N
N
N
N
N
N
1.3 x I
N
In cases where a row-mounting configuration is being used without convection cooling, the effect of the heat during continuous operation
(100% OT) means that the nominal device current may only be run at a maximum of 80% of its strength.
103906_en_01
PHOENIX CONTACT
5
EC-E...
3.1
Connection diagrams
The signal contacts are shown in an off state or
fault state.
1
LINE+
1
1
LINE+
LINE+
EC-E1
EC-E4
EC-E
SF 23
12
14
13
RE 22
11
LOAD+
2
LOAD+
2
2
LOAD+
0 V
3
0 V
0 V
3
3
Without signal input, with F alarm output
(individual signal, N/O contact)
With RE reset input (+24 V DC0), with SF status
Without signal input, with F alarm output
(individual signal, N/C contact)
output (+24 V = load output ON)
Normal state: 13 - 14 closed
Fault state: 13 - 14 open
Normal state: SF +24 V = OK
Fault state: SF 0 V
Normal state: 11 - 12 open
Fault state: 11 - 12 closed
Figure 1
Signal inputs/outputs
3.2
Block diagram (using example of EC-E)
LINE (+)
24 V DC
S1
on/off
Operating state,
green/orange/red
RE Reset input
SF Status output
LOAD (+)
0 V
load output
Figure 2
Block diagram (using example of EC-E)
103906_en_01
PHOENIX CONTACT
6
EC-E...
3.3
Information on UL approval
3.4
Dimensions
12.5
83
a UL1604
File E324415
Operating Temperature Code T5
–
This equipment is suitable for use in Class I, Division 2,
Groups A, B, C and D or non-hazardous locations only
1
WARNING:
–
Exposure to some chemicals may degrade the sealing
properties of materials used in the following device:
Relay
2
Sealant material:
–
Generic name: Modified diglycidyl ether of
bisphenol A
80
–
–
Supplier: Fine Polymers Corporation
Type: Epi Fine 4616L-160PK
Figure 4
Dimensions in mm
Casing material:
–
–
–
Generic name: Liquid crystal polymer
1
2
UC-TMF 12 marking label
Supplier: Sumitomo Chemical
Type: E4008, E4009, or E6008
Snap-on socket for DIN rail in acc. with EN 50022,
NS 35 x 7.5
RECOMMENDATION:
–
Periodically inspect the device named above for any
degradation of properties and replace if degradation is
found
3.5
Structure
WARNING – EXPLOSION HAZARD:
–
Do not disconnect equipment unless power has been
removed or the area is known to be non-hazardous
–
Substitution of any components may impair suitability
for Class I, Division 2
a UL2367
Non-hazardous use - UL File E317172
Class 2
Meets requirement for Class 2 current limitation
(EC-E...-0.5 A/1 A/2 A/3 A)
Figure 5
Structure (using example of EC-E1)
1
2
3
4
Line+ power rail
0-V power rail
Signal rail or signal bridge
Shock protection slides (molded below the housing and
can be easily removed)
Figure 3
UL approval package slip
103906_en_01
PHOENIX CONTACT
7
EC-E...
3.6
Time/current characteristic curve (TA = 25°C)
Stop point
1.8 x lN
typ. 1.1 x lN
10000
1000
100
10
5
1
0.1
0.01
IK
0
1
2
3
min. 10x lN max125 x N
Multiples of the nominal current
Figure 6
Time/current characteristic curve
–
–
In the 1.1 ... 1.8 x IN* range, the shutdown time is
typically 3 s.
The electronic current limitation function is typically
used from 1.8 x IN* upwards.
This means that, typically, 1.8 times the nominal
current* is flowing in the case of all overload conditions
that lead to a shutdown (regardless of the power supply
and load circuit resistance). The shutdown time ranges
from 100 ms to 3 s depending on the multiple of the
nominal current, or in the event of a short circuit (IK).
–
*
Without the current limitation function used at, typically,
1.8 x IN*, a considerably higher overcurrent would flow
in the event of an overload or a short circuit.
Current limitation typically 1.8 x IN where IN
=
0.5 A ... 6 A
Current limitation typically 1.5 x IN where IN = 8 A or 10 A
Current limitation typically 1.3 x IN where IN = 12 A
103906_en_01
PHOENIX CONTACT
8
EC-E...
3.7
Safe shutdown
Safe shutdown of the EC-E... with different supply line lengths and cable cross-sections
Specific electrical resistance for electrolytic copper: ρ0 = 0.0178 (Ω x mm²)/m
UB = 19.2 V DC (80% of 24 V DC)
The voltage drop on the EC-E... and the tolerance of the shutdown point
(typically 1.1 x IN = 1.05 ... 1.35 x IN) have already been taken into account.
EC-E... nominal current setting IN (in A) →
3 A
6 A
E.g., shutdown current Ishut = 1.25 A x IN (in A) → 3.75 A
7.5 A
2.51Ω
→ EC-E... typically shuts down after 3 s
Rmax in ohms = (UB/Ishut) - 0.050 Ω* → 5.07 Ω
EC-E... trips safely from 0 Ω up to max. circuit resistance Rmax
Cable cross-section A in mm² → 0.14 mm² 0.25 mm² 0.34 mm² 0.5 mm² 0.75 mm² 1 mm²
1.5 mm²
Length L in meters
(= single length)
Total cable resistance in ohms = (R0 x 2 x L)/A
0
0
0
0
0
0
0
0
5 m 1.27 Ω
10 m 2.54 Ω
15 m 3.81 Ω
20 m 5.09 Ω
25 m 6.36 Ω
30 m 7.63 Ω
35 m 8.90 Ω
40 m 10.17 Ω
45 m 11.44 Ω
50 m 12.71 Ω
0.71 Ω
1.42 Ω
2.14 Ω
2.85 Ω
3.56 Ω
4.27 Ω
4.98 Ω
5.70 Ω
6.41 Ω
7.12 Ω
0.52 Ω
1.05 Ω
1.57 Ω
2.09 Ω
2.62 Ω
3.14 Ω
3.66 Ω
4.19 Ω
4.71 Ω
5.24 Ω
7.85 Ω
0.36 Ω
0.71 Ω
1.07 Ω
1.42 Ω
1.78 Ω
2.14 Ω
2.49 Ω
2.85 Ω
3.20Ω
3.56 Ω
5.34 Ω
7.12 Ω
8.90 Ω
0.24 Ω
0.47 Ω
0.71 Ω
0.95 Ω
1.19 Ω
1.42 Ω
1.66 Ω
1.90 Ω
2.14 Ω
2.37 Ω
3.56 Ω
4.75 Ω
5.93 Ω
7.12 Ω
8.31 Ω
9.49 Ω
0.18 Ω
0.36 Ω
0.53 Ω
0.71 Ω
0.89 Ω
1.07 Ω
1.25 Ω
1.42 Ω
1.60 Ω
1.78 Ω
2.67 Ω
3.56 Ω
4.45 Ω
5.34 Ω
6.23 Ω
7.12 Ω
8.01 Ω
8.90 Ω
0.12 Ω
0.24 Ω
0.36 Ω
0.47 Ω
0.59 Ω
0.71 Ω
0.83 Ω
0.95 Ω
1.07 Ω
1.19 Ω
1.78 Ω
2.37 Ω
2.97 Ω
3.56 Ω
4.15 Ω
4.75 Ω
5.34 Ω
5.93 Ω
75 m 19.07 Ω 10.68 Ω
100 m 25.34 Ω 14.24 Ω 10.47 Ω
125 m 31.79 Ω 17.80 Ω 13.09 Ω
150 m 38.14 Ω 21.36 Ω 15.71 Ω 10.68 Ω
175 m 44.50 Ω 24.92 Ω 18.32 Ω 12.46 Ω
200 m 50.86 Ω 28.48 Ω 20.94 Ω 14.24 Ω
225 m 57.21 Ω 32.04 Ω 23.56 Ω 16.02 Ω 10.68 Ω
250 m 63.57 Ω 35.60 Ω 26.18 Ω 17.80 Ω 11.87 Ω
Example 1: Max. permissible length at 1.5 mm² and 3 A →
Example 2: Max. permissible length at 1.5 mm² and 6 A →
Approx. 200 m†
Approx. 100 m
Example 3: Mixed wiring:
R1 = 40 m in 1.5 mm² and R2 = 5 m in 0.25 mm²
(control cabinet--- sensor/actuator level)
R1 = 0.95 ohms, R2 = 0.71 ohms
Total (R1 + R2) = 1.66 ohms
*
Internal resistance of miniature circuit-breakers
†
Shutdown current I
= 3 A x 1.25 A = 3.75 A
shut
Max. current resistance R
= U /I
- 0.050 Ω (internal resistance of miniature circuit-breakers)
shut
max
B
R
= (19.2 V/3.75 A) - 0.050 Ω = 5.07 Ω
max
The value calculated, 5.07 Ω, falls between 200 m and 225 m in the table (4.75 Ω and 5.34 Ω).
This means that you can bridge 200 m comfortably.
103906_en_01
PHOENIX CONTACT
9
EC-E...
4
Mounting the potenial distribution system
(12.5 mm x n) – 3 mm = length of rails +/- 0.5 mm
E.g. (12.5 mm x 5) – 3 = 59.5 mm +/- 0.5 mm
LINE+power rail continuous
plug-in bridge, gray
Continuous plug-in bridges
500 mm length, shorten
FB ST 500 TMC-NGY
Signal rail or signal bridge
continuous plug-in bridge
FBST 500-PLC-BU
FBST 500-PLC-RD
BU = blue
RD = red
Simply remove shock
protection slides from
underside of device
Attach shock protection
slides to sides of device
0-V power rail
continuous plug-in bridge, gray
FB ST 500 TMC-NGY
12.5 mm x n = width of device block
E.g. 12.5 mm x 5 = 62.5 mm
Press in bridges and
shock protection slides
so that they are flush
with the sides of the housing
Press in bridges
so that they are flush
with the housing and
place in a central
position above
the contacts
Figure 7
Mounting
NOTE: The EC-E... electronic miniature circuit-
breakers require a 0-V connection.
A potential distribution system is integrated into the EC-E...
Various continuous plug-in bridges can be used to create
the following wiring configurations:
–
–
–
–
LINE +(24 V DC)
0 V
Signal contacts
Reset inputs
103906_en_01
PHOENIX CONTACT 10
EC-E...
5
Application examples
The signal contacts are shown in an off state or
fault state.
5.1
EC-E1– group signaling (series connection)
+ Supply for the SI
+ Supply
LINE + Power Rail
Continuous Plug-in Bridges, Gray
1
1
LINE+
1
+24 V
LINE+
LINE+
14
14
13
14
13
13
Group Signaling Using
a Signal Lamp
Power Supply Unit
24 V DC
Signal Bridges Plugged in Offset
In Relation to Each Other
EC-E1
EC-E1
EC-E1
Continuous Plug-in Bridges, Blue or Red
2 LOAD+
3 0 V
2 LOAD+
3 0 V
2 LOAD+
3 0 V
0 V
0 V-Power Rail
Continuous Plug-in Bridges, Gray
- Supply
+
-
+
Load
-
+
-
Load
Load
Figure 8
EC-E1– group signaling (series connection)
5.2
EC-E4 – individual signaling with common supply
Individual Signaling for
Each channel using a
Signal Lamp
+ Supply for the SI
+ Supply
LINE+ Power Rail
Continuous Plug-in Bridges, Gray
1
LINE+
1
LINE+
1
LINE+
+24 V
12
12
12
11
11
11
Power Supply Unit
24 V DC
Signal Rail for Common
Suppy
EC-E4
EC-E4
EC-E4
Continuous Plug-In Bridges, Blue or Red
2 LOAD+
3 0 V
2 LOAD+
3 0 V
2 LOAD+
3 0 V
0 V
0 V-Power Rail
Continuous Plug-in Bridges, Gray
- Supply
+
+
Load
+
Load
-
-
-
Load
Figure 9
EC-E4 – individual signaling with common supply
103906_en_01
PHOENIX CONTACT 11
EC-E...
5.3
EC-E – individual signaling with common reset
Reset
button
Individual signaling for each
channel using a signal lamp
+ supply
LINE+ power rail
continuous plug-in bridge, gray
1
1
1
+24 V
LINE+
LINE+
LINE+
23
23
23
22
22
22
SF
SF
SF
RE
RE
RE
24 V DC
power supply unit
Signal rail for common
supply
EC-E
EC-E
EC-E
Continuous plug-in bridges, blue or red
2 LOAD+
3 0 V
2 LOAD+
3 0 V
2 LOAD+
3 0 V
0 V
0-V power rail
continuous plug-in bridge, gray
- supply
+
Load
+
Load
+
Load
-
-
-
Figure 10
EC-E – individual signaling with common reset
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00
PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +1 (0) 717-944-1300
www.phoenixcontact.com
103906_en_01
12
相关型号:
SI9130DB
5- and 3.3-V Step-Down Synchronous ConvertersWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1-E3
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135_11
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9136_11
Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130CG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130LG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130_11
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137DB
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137LG
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9122E
500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification DriversWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
©2020 ICPDF网 联系我们和版权申明