0916611 [PHOENIX]
Thermal Magnetic Circuit Breaker;型号: | 0916611 |
厂家: | PHOENIX CONTACT |
描述: | Thermal Magnetic Circuit Breaker 电路保护 |
文件: | 总5页 (文件大小:144K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
UT 6-TMC M...
Thermomagnetic circuit breakers
CLIPLINE
Data sheet
103943_en_04
© PHOENIX CONTACT 2010-08-18
1
Description
The UT 6-TMC M circuit breaker is a single-position
overload circuit breaker with thermomagnetic tripping. It is a
space-saving circuit breaker with trip-free mechanism in the
event of overload and short circuits within the maximum
interrupting rating. The UT 6-TMC M is mounted on an
NS 35 DIN rail.
UT 6-TMC M thermomagnetic circuit breakers feature a
compact design, large labeling areas, and a double plug-in
bridge shaft.
The circuit breakers provide a high level of system
availability thanks to their reclosure function and clear status
display.
Eleven nominal current versions can be selected from 0.5 A
to 16 A. The large center labeling area enables clear
assignment of the relevant circuit breaker.
NOTE: The magnetic tripping ranges differ for alternating currents (AC) and direct currents (DC) (see page 3). The
magnetic operating currents for direct currents (DC) are approximately 1.6 times higher.
NOTE: When mounted in rows with simultaneous load, a mutual thermal effect occurs (see page 4).
Calibration is required for an ambient temperature of +23°C. A correction factor must be used to determine the
nominal current for a lower or higher ambient temperature (see page 5).
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/catalog.
This data sheet is valid for all products listed on the following page:
UT 6-TMC M...
2
Ordering data
Circuit breakers
Description
Nominal current Type
Order No.
0916603
0916604
0916605
0916606
0916607
0916608
0916609
0916610
0916611
0916612
0916613
Pcs./Pkt.
Thermomagnetic circuit breaker, 1-pos.
Thermomagnetic circuit breaker, 1-pos.
Thermomagnetic circuit breaker, 1-pos.
Thermomagnetic circuit breaker, 1-pos.
Thermomagnetic circuit breaker, 1-pos.
Thermomagnetic circuit breaker, 1-pos.
Thermomagnetic circuit breaker, 1-pos.
Thermomagnetic circuit breaker, 1-pos.
Thermomagnetic circuit breaker, 1-pos.
Thermomagnetic circuit breaker, 1-pos.
Thermomagnetic circuit breaker, 1-pos.
0.5 A
1 A
UT 6-TMC M 0,5A
6
6
6
6
6
6
6
6
6
6
6
UT 6-TMC M 1A
UT 6-TMC M 2A
UT 6-TMC M 4A
UT 6-TMC M 5A
UT 6-TMC M 6A
UT 6-TMC M 8A
UT 6-TMC M 10A
UT 6-TMC M 12A
UT 6-TMC M 15A
UT 6-TMC M 16A
2 A
4 A
5 A
6 A
8 A
10 A
12 A
15 A
16 A
Accessories
Description
Type
Order No.
3030336
3030242
3030255
3030349
3030271
3030365
3047345
1205066
Pcs./Pkt.
Plug-in bridge, for cross connection in the bridge shaft, red, 2-pos.
Plug-in bridge, for cross connection in the bridge shaft, red, 3-pos.
Plug-in bridge, for cross connection in the bridge shaft, red, 4-pos.
Plug-in bridge, for cross connection in the bridge shaft, red, 5-pos.
Plug-in bridge, for cross connection in the bridge shaft, red, 10-pos.
Plug-in bridge, for cross connection in the bridge shaft, red, 20-pos.
Warning label, for UT series, yellow
Screwdriver
UniCard sheet, for labeling
Zack marker strip, for labeling
FBS 2-6
FBS 3-6
FBS 4-6
FBS 5-6
FBS 10-6
FBS 20-6
WS UT 6
SZS 1,0X4,0
UC-TM 12
ZB 12
50
50
50
50
10
10
10
10
(See CLIPLINE catalog)
(See CLIPLINE catalog)
3
Electrical data
Nominal current, nominal voltage, and additional electrical data
Rated insulation voltage
Rated frequency
Nominal voltage
440 V AC
50/60 Hz (at 240 V AC)
240 V AC, 28 V DC
Nominal current AC/DC
Operating voltage range
Operating frequency range
Insulation resistance (main circuit)
Insulation resistance
Depending on module: 0.5 A, 1 A, 2 A, 4 A, 5 A, 6 A, 8 A, 10 A, 12 A, 15 A, 16 A
50 V AC ... 264 V AC, 5 V DC ... 30.8 V DC
48 Hz ... 62 Hz
> 100 MΩ
50 Hz: 2000 V
Pulse: 2800 V
II
Surge voltage category
Pollution degree
2
AC
DC
Switching cycles
Service life under load
6000 cycles at 1 x I
6000 cycles at 1 x I
n
n
Overload according to IEC 60943
Overload according to UL 1077
Short-circuit switching capacity (Inc)
Conditional short-circuit switching capacity (Inc)[Backup fuse]
40 cycles at 6 x I
50 cycles at 1.5 x I
200 A
40 cycles at 6 x I
n
n
50 cycles at 1.5 x I
400 A
n
n
2000 A
2000 A
103943_en_04
PHOENIX CONTACT
2
UT 6-TMC M...
Backup fuse
Nominal current
UT 6-TMC M
Maximum backup fuse
NOTE: If in the application the maximum short-circuit switching capacity (I ) could be exceeded in the event of an error, a backup fuse
cn
must be used in combination with the circuit breaker.
The following maximum backup fuse values are recommended according to 0.5 A
16 A
16 A
16 A
16 A
20 A
20 A
25 A
25 A
25 A
25 A
25 A
characteristic gG (VDE 0636, IEC 269)
1 A
2 A
4 A
5 A
6 A
8 A
10 A
12 A
15 A
16 A
Tripping characteristics
Type of actuation
Manual ON/OFF (S type)
Tripping method
Tripping type
Thermomagnetic (TM)
Trip-free mechanism
Specified non-tripping current (no tripping within an hour)
Specified tripping current (tripping within an hour)
Instantaneous non-tripping current
Instantaneous tripping current
1.05 x I
1.32 x I
n
n
6 x I (AC)
n
12 x I (AC)
n
NOTE: The magnetic tripping ranges differ for alternating currents (AC) and direct currents (DC). Please observe the tripping characteristics
shown in Figure 1.
The magnetic operating currents for direct currents (DC) are approximately 1.6 times higher.
3.1
Tripping characteristics
AC tripping characteristics
DC tripping characteristics
10000
1000
10000
1000
< 7.0A
> 7.0A
< 7.0A
> 7.0A
100
10
100
10
1
1
0.1
0.1
0.01
0.001
0.01
0.001
1
2
3 4 6 8 10
20
40 60 100
1
2
3 4 6 8 10
20
40 60 100
Multiples of IN
Multiples of IN
Figure 1
AC and DC tripping characteristics
103943_en_04
PHOENIX CONTACT
3
UT 6-TMC M...
3.2
Effect on thermal tripping of mounting in rows
Calculation example for overdimensioning
5 circuit breakers with In = 10 A are to be mounted in rows.
The ambient temperature is +23°C.
Nominal current when not mounted In = 10 A
in rows
NOTE: When mounted in rows with simultaneous
load, a mutual thermal effect occurs.
The mutual thermal effect is tantamount to an increase in the
ambient temperature (see page 5). This depends on the
following:
Typical correction factor
df = 1.25
Theoretical nominal current when
mounting in rows
In row = 10 A X 1.25
= 12.5 A
–
–
–
–
The nominal current
The ambient temperature
The number of devices
The distance between devices
3.3
Internal resistance of the UT 6-TMC M
Nominal current
0.5 A
Resistance
4.37 Ω
The nominal device current can be either overdimensioned
or limited. When the UT 6-TMC M is mounted in rows, the
correction factor is usually in the range of 1.25 or at
80% (reciprocal) in relation to the limiting nominal current.
These values apply in the event of continuous load and at an
ambient temperature of +23°C.
Since the thermal effect varies for each planned installation
when mounting in rows, the correction factors must be
defined individually and tested.
1.0 A
0.95 Ω
2.0 A
0.33 Ω
4.0 A
5.0 A
6.0 A
8.0 A
10.0 A
12.0 A
15.0 A
16.0 A
88.0 mΩ
55.8 mΩ
41.7 mΩ
22.2 mΩ
12.3 mΩ
10.9 mΩ
8.3 mΩ
7.7 mΩ
Measurement between the LINE and LOAD connections.
Tolerance: ±10%
4
Mechanical data
Fixing
Mounting method
On a DIN rail according to DIN EN 60715, NS 35N/7,5 or NS 35/15
The tripping characteristics are not dependent on the mounting position.
Plug-in bridge, for cross connection in the bridge shaft
FBS x-6 plug-in bridge (see "Accessories" on page 2)
Connection polarity
Suitability
Weight
Independent polarity (for DC) for the LINE and LOAD connections
"Factory wiring"
51 g
Housing material
Fuse type
PA 66
Medium blow fuse
Inflammability class according to UL 94
Maximum number of cycles
V0
6000 at 1 x I
n
Connection terminal block
Screw connection
M4
Connection capacity
1 conductor
2 conductors (two conductors with same cross-section, ferrule without
plastic sleeve)
Solid
0.2 mm² ... 10 mm²
Stranded
0.2 mm² ... 10 mm²
0.2 mm² ... 2.5 mm²
With ferrule
0.25 mm² ... 6 mm²
0.25 mm² ... 1.5 mm²
2 stranded conductors with a TWIN ferrule
Stripping length
0.5 mm² ... 4 mm²
12 mm
Tightening torque (EN 60934)
1.5 Nm ... 1.8 Nm
103943_en_04
PHOENIX CONTACT
4
UT 6-TMC M...
5.3
Resistance to vibrations and shocks
5
Environmental influences
Shock resistance according to EN 60068-2-27,
Test Ea [3 shocks in each direction (= 18 shocks)]
Peak G
50g
5.1
Temperature range, influence on the ambient
temperature
Pulse length Pulse form
11 ms Half-sine
NOTE: Calibration is required for an ambient
temperature of +23°C.
Vibration resistance according to EN 60068-2-6,
Test Fc - frequency range: 5 Hz ... 500 Hz
Temperature range
Reference temperature +23°C
-30°C … +60°C
< 60 Hz
(constant amplitude)
> 60 Hz
(constant acceleration)
The following typical correction factors must be observed to
calculate the nominal current:
0.15 mm
2g
Correction factors
°C
5.4
Approvals
Certifica-
tion body
VDE
Standard License
number
IEC 60934 400028127 Circuit Breaker for
Approved as
I
[A] -30 -20
-10
0
10
23
30
40
50
60
n
0.5 0.77 0.81 0.84 0.87 0.90 1.00 1.03 1.08 1.15 1.21
1
2
4
5
6
8
0.77 0.81 0.84 0.87 0.90 1.00 1.03 1.06 1.13 1.19
0.77 0.81 0.84 0.87 0.90 1.00 1.03 1.08 1.15 1.21
0.77 0.81 0.84 0.87 0.90 1.00 1.03 1.08 1.15 1.21
0.77 0.81 0.84 0.87 0.90 1.00 1.03 1.08 1.15 1.25
0.70 0.73 0.78 0.84 0.90 1.00 1.03 1.08 1.15 1.21
0.70 0.73 0.78 0.84 0.90 1.00 1.03 1.06 1.13 1.21
Equipment
Supplementary
Protector
Supplementary
Protector
UL
UL 1077
E140459
UL
CSA 22.2 E140459
No.235
CSA 22.2 250505
No.235
CSA
Supplementary
Protector
10 0.78 0.81 0.84 0.87 0.90 1.00 1.05 1.15 1.21 1.30
12 0.77 0.80 0.85 0.90 0.95 1.00 1.03 1.08 1.15 1.21
15 0.73 0.73 0.78 0.84 0.90 1.00 1.03 1.08 1.11 1.21
16 0.70 0.73 0.78 0.84 0.90 1.00 1.03 1.08 1.15 1.21
6
Dimensions
0.75 0.78 0.82 0.86 0.90 1.00 1.03 1.08 1.15 1.22
ø
Example calculation:
A circuit breaker with In = 4 A is to be used at an ambient
temperature of +60°C.
Nominal current at +23°C In (+23°C) = 4 A
Ambient temperature
Correction factor
T
amb = +60°C
df = 1.21
Theoretical nominal current at +60°C
In (+60°C) = 4 A x 1.21 = 4.84 A
At +60°C, a nominal current of 5 A should be selected.
5.2
IP protection class
IP protection class
Actuation area
Connection area
IP40
IP20
Figure 2
Dimensions (in mm)
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49 - 52 35 - 30 0
PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300
www.phoenixcontact.com
103943_en_04
5
相关型号:
SI9130DB
5- and 3.3-V Step-Down Synchronous ConvertersWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1-E3
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135_11
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9136_11
Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130CG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130LG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130_11
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137DB
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137LG
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9122E
500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification DriversWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
©2020 ICPDF网 联系我们和版权申明