2700356 [PHOENIX]

Power/Signal Relay,;
2700356
型号: 2700356
厂家: PHOENIX CONTACT    PHOENIX CONTACT
描述:

Power/Signal Relay,

继电器
文件: 总6页 (文件大小:89K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
https://www.phoenixcontact.com/pi/products/2700356  
Coupling relay - PSR-PS20-1NO-1NC-24DC-SC - 2700356  
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's  
documentation. Our General Terms of Use for Downloads are valid  
(http://phoenixcontact.com/download)  
Coupling relay for SIL 3 high and low-demand applications, couples digital output signals to the I/O, 1  
enabling current path, 1 confirmation current path, 1 digital signal output, safe state off applications, test pulse  
filter, fixed screw terminal block  
Your advantages  
Up to SIL 3 according to IEC 61508  
Forcibly guided contacts according to EN 50205  
Easy proof test according to IEC 61508 thanks to integrated signal contact  
Approved for Class I, Zone 2 applications  
Low housing width of just 6.8 mm  
Long service life thanks to filtering of controller test pulses  
1 enabling current path, 1 digital signal output, 1 diagnostic current path  
Couples digital output signals from failsafe controllers to I/O devices (valves, etc.) for electrical isolation and power adaptation  
Key Commercial Data  
Packing unit  
1 pc  
GTIN  
GTIN  
4046356912891  
Technical data  
Note  
EMC: class A product, see manufacturer's declaration in the download  
area  
Utilization restriction  
Dimensions  
Width  
Height  
Depth  
6.8 mm  
93.1 mm  
102.5 mm  
Ambient conditions  
03/13/2019 Page 1 / 6  
https://www.phoenixcontact.com/pi/products/2700356  
Coupling relay - PSR-PS20-1NO-1NC-24DC-SC - 2700356  
Technical data  
Ambient conditions  
Ambient temperature (operation)  
-40 °C ... 70 °C (observe derating)  
-40 °C ... 85 °C  
Ambient temperature (storage/transport)  
Max. permissible relative humidity (operation)  
Max. permissible humidity (storage/transport)  
Maximum altitude  
75 % (on average, 85% infrequently, non-condensing)  
75 % (on average, 85% infrequently, non-condensing)  
≤ 2000 m (Above sea level)  
Power supply  
Rated control circuit supply voltage US  
24 V DC -15 % / +10 % (A1/A2)  
20.4 V DC ... 26.4 V DC  
Rated control supply current IS  
Power consumption at US  
Inrush current  
typ. 45 mA  
typ. 1.08 W  
typ. 400 mA (Δt < 10 µs at Us)  
max. 2 ms (at A1-A2; test pulse width)  
≥ 100 ms (at A1-A2; test pulse rate)  
24 V DC -15 % / +10 % (21/A2)  
6 mA (at 21-A2 for UD; depending on load + 100 mA at M1 and 22)  
typ. 2.5 A (Δt < 20 µs at UD)  
Filter time  
Diagnostic supply voltage UD  
Input current at UD  
Inrush current at UD  
Serial protection against polarity reversal Suppressor diode 33 V (A1/  
A2), 38 V (21/A2)  
Protective circuit  
Relay outputs: enabling current path  
Output name  
Enabling current path  
2 N/O contacts in series, without delay, floating  
1 (safety-related N/O contacts: 13/14)  
1 enabling current path  
AgSnO2  
Output description  
Number of outputs  
Contact type  
Contact material  
Switching voltage  
min. 12 V AC/DC  
max. 250 V AC/DC (Observe the load curve)  
6 A (High demand)  
Limiting continuous current  
Inrush current  
4 A (Low demand)  
min. 3 mA  
max. 6 A  
36 A2 (observe derating)  
min. 60 mW  
Sq. Total current  
Switching capacity  
Switching frequency  
max. 1 Hz  
10x 106 cycles  
Mechanical service life  
Switching capacity according to IEC 60947-5-1  
4 A (24 V (DC13))  
5 A (250 V (AC15))  
6 A gL/gG  
Output fuse  
4 A gL/gG (for low-demand applications)  
Relay outputs: return current/signaling current path  
03/13/2019 Page 2 / 6  
https://www.phoenixcontact.com/pi/products/2700356  
Coupling relay - PSR-PS20-1NO-1NC-24DC-SC - 2700356  
Technical data  
Relay outputs: return current/signaling current path  
Output name  
Confirmation current path  
2 N/C contacts in series, without delay, not floating (reference ground:  
A2)  
Output description  
Number of outputs  
Contact type  
1 (safety-related N/C contacts: 21/22)  
1 confirmation current path  
AgCuNi, + Au  
Contact material  
Switching voltage  
min. 20.4 V DC  
max. 26.4 V DC  
100 mA  
Limiting continuous current  
Inrush current  
min. 1 mA  
max. 100 mA  
Switching capacity  
Switching frequency  
Mechanical service life  
Output fuse  
min. 20 mW  
max. 1 Hz  
10x 106 cycles  
150 mA Fast-blow  
Alarm outputs  
Output description  
Number of outputs  
Voltage  
PNP  
1 (non-safety-related)  
approx. 22 V DC (UD - 2 V)  
max. 100 mA  
Current  
500 mA (Δt = 1 ms at Us)  
no  
Maximum inrush current  
Short-circuit protection  
Output fuse  
150 mA fast blow  
Times  
< 100 ms (with Us when controlled via A1)  
< 35 ms (when controlled via A1)  
500 ms  
Typical pickup time at US  
Typical release time at US  
Recovery time  
General  
Electromechanical relay with forcibly guided contacts in accordance with  
IEC/EN 61810-3 (EN 50205)  
Relay type  
Nominal operating mode  
Net weight  
100% operating factor  
83.5 g  
Mounting position  
vertical, horizontal, with front of module upward  
Mounting type  
DIN rail mounting  
See derating curve  
IP20  
Assembly instructions  
Degree of protection  
Min. degree of protection of inst. location  
Housing material  
IP54  
PBT  
Housing color  
yellow  
Operating voltage display  
1 x yellow LED  
03/13/2019 Page 3 / 6  
https://www.phoenixcontact.com/pi/products/2700356  
Coupling relay - PSR-PS20-1NO-1NC-24DC-SC - 2700356  
Technical data  
General  
Status display  
Indication  
2 x green LEDs  
1 x red LED  
Connection data  
Connection method  
Screw connection  
pluggable  
no  
Conductor cross section solid min.  
Conductor cross section solid max.  
Conductor cross section flexible min.  
Conductor cross section flexible max.  
Conductor cross section AWG min.  
Conductor cross section AWG max.  
Stripping length  
0.2 mm²  
2.5 mm²  
0.2 mm²  
2.5 mm²  
26  
12  
12 mm  
M3  
Screw thread  
Torque  
0.5 Nm ... 0.6 Nm  
Safety-related characteristic data  
Stop category  
0
Designation  
IEC 61508 - High demand  
Safety Integrity Level (SIL)  
Designation  
3
IEC 61508 - Low demand  
Safety Integrity Level (SIL)  
Designation  
3
EN 50156  
3
Safety Integrity Level (SIL)  
Standards and Regulations  
Designation  
Air clearances and creepage distances between the power circuits  
Standards/regulations  
Rated insulation voltage  
DIN EN 50178, EN 60079-15  
250 V AC  
Safe isolation, 6 kV reinforced insulation from control circuit, start circuit,  
confirmation current path, signal output to the enabling current path; 4  
kV/basic insulation between all current paths and housing  
Rated surge voltage/insulation  
Degree of pollution  
Overvoltage category  
Shock  
2
III  
15g  
Vibration (operation)  
Conformance  
10 Hz ...150 Hz, 2g  
CE-compliant  
UL, USA/Canada  
cULus  
Class I, Zone 2, AEx nA nC IIC T4 / Ex nA nC IIC Gc T4 X  
Class I, Div. 2, Groups A, B, C, D, T4  
C, EMC2  
GL  
Environmental simulation test  
ISA-S71.04 (G3)  
Environmental Product Compliance  
03/13/2019 Page 4 / 6  
https://www.phoenixcontact.com/pi/products/2700356  
Coupling relay - PSR-PS20-1NO-1NC-24DC-SC - 2700356  
Technical data  
Environmental Product Compliance  
China RoHS  
Environmentally Friendly Use Period = 50  
For details about hazardous substances go to tab “Downloads”,  
Category “Manufacturer's declaration”  
Drawings  
Block diagram  
Circuit diagram  
24 V DC  
SIS / FS-PLC  
Logic  
A1  
21  
13  
I/O  
24V  
GND  
PSR-PS20  
0V DO DO DI  
ERR  
DGN  
0 V  
PWR  
K1/2  
K1  
K2  
L
24V DC  
A2  
M1  
22  
14  
(
A1  
13  
)22  
K1  
K2  
PSR-PS20  
A2  
(
(
) M1  
14  
)21  
M
K1  
24 V DC  
K2  
N
Approvals  
Approvals  
Approvals  
GL / UL Listed / cUL Listed / Functional Safety / EAC / cULus Listed  
Ex Approvals  
Approval details  
GL  
http://exchange.dnv.com/tari/  
11253-14 HH  
UL Listed  
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm  
FILE E 140324  
03/13/2019 Page 5 / 6  
https://www.phoenixcontact.com/pi/products/2700356  
Coupling relay - PSR-PS20-1NO-1NC-24DC-SC - 2700356  
Approvals  
cUL Listed  
Functional Safety  
EAC  
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm  
FILE E 140324  
44-780-13755203  
RU C-  
DE.A*30.B.01082  
cULus Listed  
Phoenix Contact 2019 © - all rights reserved  
http://www.phoenixcontact.com  
PHOENIX CONTACT GmbH & Co. KG  
Flachsmarktstr. 8  
32825 Blomberg  
Germany  
Tel. +49 5235 300  
Fax +49 5235 3 41200  
http://www.phoenixcontact.com  
03/13/2019 Page 6 / 6  

相关型号:

2700357

Safety Relay, Momentary, 0.045A (Coil), 24VDC (Coil), 1080mW (Coil), 250VDC (Contact), DC Input, DIN-Rail Mount,
PHOENIX

2700498

PSR-MC30-2NO-1DO-24DC-SC
PHOENIX

2700499

PSR-MC30-2NO-1DO-24DC-SP
PHOENIX

270050100

Board Connector, 5 Contact(s), 1 Row(s), Male, Straight, Solder/Wire Wrap Terminal,
MOLEX

2700548

PSR-MC34-3NO-1DO-24DC-SP
PHOENIX

2700582

Power/Signal Relay,
PHOENIX

2700622

Visu RT and AX OPC server integrated as standard in all devices
PHOENIX

2700623

Visu RT and AX OPC server integrated as standard in all devices
PHOENIX

2700SM28CAN-T13

Trans Voltage Suppressor Diode
PROTEC

2700SM78CA

POWER BUS VOLTAGE SUPPRESSOR
PROTEC

2700SM78CAN-T13

Trans Voltage Suppressor Diode
PROTEC

2700SM78CA_12

POWER BUS VOLTAGE SUPPRESSOR
PROTEC