MQC02051 [POWER-ONE]
Temperature Sensors; 温度传感器型号: | MQC02051 |
厂家: | POWER-ONE |
描述: | Temperature Sensors |
文件: | 总4页 (文件大小:88K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Electrical
Accessory Products
Temperature Sensors
Temperature Sensors
Description
Power-One offers a wide range of battery charger systems
for power requirements of 50 Watt up to 8000 Watt.
need and optimum life expectancy of the battery. The type
of sensor needed is defined mainly by three parameters:
The nominal battery voltage (e.g. 24 V or 48 V), the tempe-
rature coefficient of the battery (e.g. –3.0 mV/K/cell) and the
nominal floating charge voltage per cell of the battery
at 20°C (e.g. 2.27 V/cell). The latter two are defined in the
specifications of the battery given by the respective battery
manufacturer.
For this purpose Power-One supplies temperature sensors
and adapted power supplies. The batteries (lead acid bat-
teries) are charged according to the battery temperature
and the ambient temerature. If the battery is fully charged it
is maintained at the float charge voltage which represents
the optimum point for maximum available energy in case of
Cell voltage [V]
2.45
06139
2.40
2.35
2.30
2.25
2.20
2.15
[°C]
50
2.10
-20
-10
0
10
20
30
40
UC = 2.27 V, –3 mV/K
UC = 2.23 V, –3 mV/K
UC = 2.27 V, –3.5 mV/K
UC = 2.23 V, –3.5 mV/K
Fig. 1
Float charge voltage versus temperature for defined tem-
perature coefficient.
03099
Vi+
Vo+
Power
supply
Load
Vi–
Vo–
R/UCR input
–
+
ϑ
Battery
Temperature sensor
Fig. 2
Functional description
Page
Table of Contents
Page
Temperature Sensors for
Description ....................................................................... 1
Temperature Sensors for T and U units ........................... 1
Mechanical Dimensions ................................................... 2
M, H, S, K, KP, PSx, LW, OK Units .................................. 3
Mechanical Dimensions ................................................... 3
Fail Safe Operation .......................................................... 4
Edition 5/06.2001
1/4
Electrical
Accessory Products
Temperature Sensors
Temperature Sensors for T and U units
For units without the Z selector switch a sensor according
to both criteria should be selected. In our example it would
be S24-2.27-35-02.
T and U units feature a cell voltage selector switch (feature
Z) to set the required floating charge voltage at 20°C di-
rectly at the unit. If this Z switch is used the 2.23 V/cell sen-
sor types should be selected in any case as a basis and the
selection criteria are only the temperature coefficient of the
battery and the nominal battery voltage. If for example a
24 V battery is used which has a cell voltage of 2.27 V/cell
and a temperature coefficient of –3.5 mV/K/cell, the sensor
type is S24-2.23-35-02. The setting on the Z switch of the T
or U unit should be 2.27.
For further details please consult the T or U datasheet.
Table 1: Type survey T sensors
Nominal battery
Sensor type
Part no.
Cell voltage
Temp. coefficient
Cable length
voltage [V]
[mV]
[mV/K/cell]
[m]
24
24
24
36
36
36
48
48
48
48
48
48
48
S24-2.23-30-02
S24-2.23-35-02
S24-2.23-45-02
S36-2.23-30-02
S36-2.23-35-02
S36-2.27-35-02
S48-2.23-30-02
S48-2.23-35-02
S48-2.23-40-02
S48-2.23-45-02
S48-2.27-30-02
S48-2.27-35-02
S48-2.27-45-02
MQC02052
MQC02053
MQC02051
MQC02081
MQC02082
MQC02083
MQC02008
MQC02009
MQC02013
MQC02012
MQC02010
MQC02007
MQC02006
2.23
2.23
2.23
2.23
2.23
2.27
2.23
2.23
2.23
2.23
2.27
2.27
2.27
–3.0
–3.5
–4.5
–3.0
–3.5
–3.5
–3.0
–3.5
–4.0
–4.5
–3.0
–3.5
–4.5
2
2
2
2
2
2
2
2
2
2
2
2
2
Other types for different cell voltages or temperature coefficients are available upon request.
05064
05148
—
–
Sensor Sensor Temperature
+
+
Sensor Sensor Temperature
wires
cable
sensor
wires
cable
sensor
U
28
white
2
i/Ucr
Vo+
Ucr
white
12
1
Vo+
brown
brown
+
+
—
–
22
green
9
Vo—
Vo–
Battery
Battery
green
Fig. 3:
Connection to the T unit.
Fig. 4:
Connection to the U unit.
Mechanical Dimensions
All dimensions in mm, tolerances ±0.3 mm unless otherwise specified.
European
Projection
09044
15
12
25 ± 0.2
l
≤60
adhesive tape
l: 2 m standard length
other cable lengths on request
Fig. 5
T and U temperature sensor with mounting fixture.
Edition 5/06.2001
2/4
Electrical
Accessory Products
Temperature Sensors
Temperature Sensors for
M, H, S, K, KP, PSx, W, OK Units
With M, H, S, K, KP, PSx, W and OK units the sensor signal
acts on the R pin to adjust the output voltage relative to the
battery temperature and the ambient temperature. As these
units in contrast to the T and U units do not feature a cell
voltage selector switch (Z switch) the sensor selection crite-
ria is in every case both the cell voltage and the tempera-
ture coefficient (beside the nominal battery voltage).
If the application uses for example a 48 V battery with a cell
voltage of 2.23 V/cell and a temperature coefficient of
–3.0mV/K/cell the sensor S-KSMH48-2.23-30-2 should be
selected.
Table 2: Type survey S-KSMH sensors
Nominal battery
Sensor type
Part no.
Cell voltage
Temp. coefficient
Cable length
voltage [V]
[mV]
[mV/K/cell]
[m]
12
24
24
48
48
S-KSMH12-2.27-30-2
S-KSMH24-2.27-35-2
S-KSMH24-2.27-30-2
S-KSMH48-2.27-35-2
S-KSMH48-2-27-30-2
MQC03005
MQC03002
MQC03004
MQC03001
MQC03003
2.27
2.27
2.27
2.27
2.27
-3.0
2
2
2
2
2
-3.5
-3.0
-3.5
-3.0
Other types for different cell voltages or temperature coefficients are available upon request.
05163
–
+
Sensor Sensor Temperature
wires
cable
sensor
R
white
Vo+
brown
green
+
–
Vo–
Battery
Fig. 6
Connection to a M, H, S, K, KP, LW or OK unit.
Mechanical Dimensions
All dimensions in mm, tolerances ±0.3 mm unless otherwise specified.
European
Projection
S90051
55 (2.17")
26 (1.02")
Fig. 7
S-KSMH temperature sensor.
Edition 5/06.2001
3/4
Electrical
Accessory Products
Temperature Sensors
Fail Safe Operation
To prevent overcharging of the battery but still maintain a
minimum charging in case of interruption of the sensor sig-
nal cable to the power supply, Power-One has designed
units with a special nominal output voltage setting. These
units differ from the respective standard units described in
the datasheet in the nominal output voltage and output
current settings. Without the sensor connected to the R pin
the output voltage will be higher than the nominal battery
voltage to avoid a discharging of the battery but still lower
than the theoretically needed float charge voltage. As soon
as the sensor is connected to the R pin the output voltage
will be set to the correct value.
Table 3:
Nominal battery voltage
Output voltage setting
[V]
12
24
36
48
60
(20°C) [V]
12.84
25.68
38.52
51.36
64.2
Tabel 4: Special units for battery charging
Ubatt [V]
12
Po 50 Watt
LM 1781-7R
LM 1782-7R
LM 1783-7R
LM 1784-7R
LM 1785-7R
Po 70 Watt
LH 1781-2R
LH 1782-2R
LH 1783-2R
LH 1784-2R
LH 1785-2R
Po 100 Watt
LS 4740-7R
LS 5740-7R
Po 150 Watt
Po 250 Watt
LKP 5740-6R
LKP 5740-6R
LK 4740-7R
LK 5740-7R
24
36
48
LS 5740-7R
LK 5740-7R
60
Higher power requirements can be covered by paralleling
of these units. Complete microprocessor controlled sys-
tems of un-interuptable power suplies (UPS) are realized
by our Applications Center. Please consult your local
Power-One representant.
Edition 5/06.2001
4/4
相关型号: