CUB5R000 [REDLION]

MODEL CUB®5 - MINIATURE ELECTRONIC 8-DIGIT DUAL COUNTER AND RATE INDICATOR;
CUB5R000
型号: CUB5R000
厂家: Red Lion Controls. Inc    Red Lion Controls. Inc
描述:

MODEL CUB®5 - MINIATURE ELECTRONIC 8-DIGIT DUAL COUNTER AND RATE INDICATOR

文件: 总16页 (文件大小:1315K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Bulletin No. CUB5-L  
Drawing No. LP0584  
Released 04/16  
Tel +1 (717) 767-6511  
Fax +1 (717) 764-0839  
www.redlion.net  
MODEL CUB®5 - MINIATURE ELECTRONIC 8-DIGIT DUAL  
COUNTER AND RATE INDICATOR  
LCD, REFLECTIVE OR GREEN/RED LED BACKLIGHTING  
0.46" (11.7 mm) HIGH DIGITS  
OPTIONAL SETPOINT OUTPUT CARD  
OPTIONAL SERIAL COMMUNICATIONS CARD (RS232 or RS485)  
OPTIONAL USB PROGRAMMING CARD  
OPERATES FROM 9 TO 28 VDC POWER SOURCE  
PROGRAMMABLE SCALING FOR COUNT AND RATE  
BI-DIRECTIONAL COUNTING, UP/DOWN CONTROL  
QUADRATURE SENSING (UP TO 4 TIMES RESOLUTION)  
BUILT-IN BATCH COUNTING CAPABILITY  
U
R
C L US LISTED  
IND. CONT. EQ.  
51EB  
DISPLAY COLOR CHANGE CAPABILITY AT SETPOINT OUTPUT  
NEMA 4X/IP65 SEALED FRONT BEZEL  
COUNTER  
GENERAL DESCRIPTION  
The CUB®5 provides the user the ultimate in flexibility, from its complete  
user programming to the optional setpoint control and communication capability.  
The meter can be programmed as a single or dual counter with rate indication  
capability. The display can be toggled either manually or automatically between  
the selected displays.  
The CUB5 receives incoming pulses and multiplies them by the Count Scale  
Factor to obtain the desired reading for the count display. Input A accepts the  
signal for the count and Input B is used for quadrature, dual counter, anti-  
coincidence counting, or up/down control counting.  
RATE  
The CUB5 display has 0.46" (11.7 mm) high digits. The LCD is available in  
two versions, reflective (CUB5R000) and backlight (CUB5B000). The backlight  
version is user selectable for green or red backlighting with variable display  
intensity.  
The counter is programmable for one of eight different count modes,  
including bi-directional and quadrature. When programmed as a dual counter,  
each counter has a separate scale factor and decimal points. In the counter/rate  
indicator mode, each have their own scaling and decimal point read-outs in  
different engineering units. The internal batch counter can be used to count  
setpoint output activations.  
The rate indicator utilizes the signal at Input A to calculate the rate value  
using a time interval method (1/tau). The unit counts on the negative edge of the  
input pulses. After the programmed minimum update time elapses and the next  
negative edge occurs, the unit calculates the input rate based on the number of  
edges that occurred during the elapsed time. The input rate is then multiplied by  
the rate scaling value to calculate the rate display.  
At slower rates, averaging can be accomplished by programming the rate  
minimum update time for the desired response. Extensive scaling capabilities  
allow practically any desired reading at very slow count rates.  
The meter has two separate inputs which provide different functions  
depending on which operating mode is selected. Input A accepts the signal for  
the Count and/or Rate displays, while Input B accepts the signal for the Count  
display or direction control. In the anti-coincidence mode, both inputs are  
monitored simultaneously so that no counts are lost. The resulting display can  
be chosen as the sum or difference of the two inputs. The Rate Indicator has  
programmable low (minimum) and high (maximum) update times to provide  
optimal display response at any input frequency. There is a programmable user  
input that can be programmed to perform a variety of functions.  
The capability of the CUB5 can be easily expanded with the addition of  
option cards. Setpoint capability is field installable with the addition of the  
single setpoint relay output card or the dual setpoint solid state output card.  
Serial communications capability for RS232 or RS485 is added with a serial  
option card.  
SAFETY SUMMARY  
All safety related regulations, local codes and instructions that appear in this  
literature or on equipment must be observed to ensure personal safety and to  
prevent damage to either the instrument or equipment connected to it. If  
equipment is used in a manner not specified by the manufacturer, the protection  
provided by the equipment may be impaired.  
Do not use this meter to directly command motors, valves, or other actuators  
not equipped with safeguards. To do so can be potentially harmful to persons or  
equipment in the event of a fault to the meter.  
The CUB5 can be powered from an optional Red Lion Micro-Line/Sensor  
Power Supply (MLPS), which attaches directly to the back of a CUB5. The  
MLPS is powered from 85 to 250 VAC and provides up to 400 mA to drive the  
unit and sensors.  
CAUTION: Risk of Danger.  
Read complete instructions prior to  
installationand operation of the unit.  
CAUTION: Risk of electric shock.  
Note: Recommended minimum clearance (behind the panel) for mounting clip installation is 2.15" (54.6) H x 3.00" (76.2) W.  
DIMENSIONS In inches (mm)  
.13 (3.3)  
ON ECE  
+.024  
1.30  
1
2
3
4
-.000  
+6  
1.29 (32.8)  
1.54 (39.1)  
(33  
)
9876543.2  
-0  
SEL  
RST  
+.025  
-.000  
+8  
2.95 (74.9)  
1.71  
(43.4)  
2.68  
(68  
.15 (3.8)  
)
-0  
1
orderinG inforMation  
TYPE  
MODEL NO.  
CUB5R  
DESCRIPTION  
PART NUMBER  
CUB5R000  
CUB5B000  
CUB5RLY0  
CUB5SNK0  
CUB5COM1  
CUB5COM2  
CUB5USB0  
MLPS1000  
MLPS2000  
CBLPROG0  
CBPRO007  
SFCRD200  
CBLUSB00  
Dual Counter & Rate Indicator with Reflective Display  
Dual Counter & Rate Indicator with Backlight Display  
Single Relay Option Card  
CUB5  
CUB5B  
CUB5RLY  
CUB5SNK  
Dual Sinking Open Collector Output card  
RS485 Serial Communications Card  
Optional Plug-in Cards  
CUB5COM  
CUB5USB  
MLPS  
RS232 Serial Communications Card  
USB Programming Card  
+12 VDC Micro-Line Power Supply, 85 to 250 VAC source, 400 mA max out  
+24 VDC Micro-Line Power Supply, 85 to 250 VAC source, 200 mA max out  
Programming Cable RS232 (RJ11-DB9)  
Communication Cable RS485 (RJ11-DB9)  
Crimson PC Configuration Software, Free Download Available1  
USB Programming Cable  
CBLPRO  
CBPRO  
SFCRD  
CBLUSB  
Accessories  
1 Crimson software is a free download from http://www.redlion.net. System requirements for the software are listed on the download page.  
General Meter SpecificationS  
1. DISPLAY: 8 digit LCD 0.46" (11.7 mm) high digits  
CUB5R000: Reflective LCD with full viewing angle  
CUB5B000: Transmissive LCD with selectable red or green LED backlight,  
viewing angle optimized. Display color change capability with output state  
when using an output module.  
7. MEMORY: Nonvolatile E2PROM memory retains all programming  
parameters and count values when power is removed.  
8. CONNECTIONS: Wire clamping screw terminals  
Wire Strip Length: 0.3" (7.5 mm)  
Wire Gage: 30-14 AWG copper wire  
2. POWER: Input voltage range is +9 to +28 VDC with short circuit and input  
polarity protection. Must use an RLC model MLPS or an NEC Class 2 or  
Limited Power Source (LPS) rated power supply.  
Torque: 3.5 inch-lbs (0.395 N-m) max.  
9. CONSTRUCTION: This unit rated for Type 4X/IP65 requirements for indoor/  
outdoor use. Installation Category I, Pollution Degree 2. High impact plastic  
case with clear viewing window. Panel gasket and mounting clip included.  
10. ENVIRONMENTAL CONDITIONS:  
Operating Temperature Range for CUB5R000: -35 to 75 °C  
Operating Temperature Range for CUB5B000 depends on display color  
and intensity level as per below:  
INPUT CURRENT  
@ 9 VDC WITHOUT  
CUB5RLY0  
INPUT CURRENT  
@ 9 VDC WITH  
CUB5RLY0  
MODEL  
NO.  
DISPLAY COLOR  
CUB5R000  
CUB5B000  
---  
10 mA  
85 mA  
95 mA  
30 mA  
115 mA  
125 mA  
Red (max intensity)  
CUB5B000 Green (max intensity)  
INTENSITY LEVEL  
TEMPERATURE  
Red Display  
1 & 2  
3
4
5
-35 to 75°C  
-35 to 70°C  
-35 to 60°C  
-35 to 50°C  
-35 to 75°C  
-35 to 65°C  
-35 to 50°C  
-35 to 35°C  
3. COUNTER DISPLAYS:  
Counter A: 8-digits, enabled in all count modes  
Display Range: -9999999 to 99999999  
Overflow Indication: Display flashes “Cnt OVEr”  
Green Display  
1 & 2  
Counter B: 7-digits, enabled in Dual Counter Mode or batch counting  
Display Designator: “b” to the left side of the display  
Display Range: 0 to 9999999 (positive count only)  
Overflow Indication: Display flashes “bCntOVEr”  
Maximum Count Rates: 50% duty cycle  
Without setpoint option card: 20 KHz (all count modes)  
With setpoint option card: 20 KHz for any count mode except Dual Counter  
(16 KHz), Quadrature x2 (14 KHz) and Quadrature x4 (13 KHz).  
4. RATE DISPLAY: 6-digits, may be enabled or disabled in any count mode  
Display Designator: “R” to the left side of the display  
Display Range: 0 to 999999  
3
4
5
Storage Temperature: -35 to 85 °C  
Operating and Storage Humidity: 0 to 85% max. relative humidity (non-  
condensing)  
Vibration to IEC 68-2-6: Operational 5-500 Hz, 5 g  
Shock to IEC 68-2-27: Operational 40 g  
Altitude: Up to 2000 meters  
11. CERTIFICATIONS AND COMPLIANCES:  
CE Approved  
EN 61326-1 Immunity to Industrial Locations  
Emission CISPR 11 Class A  
Safety requirements for electrical equipment for measurement, control, and  
laboratory use:  
EN 61010-1: General Requirements  
EN 61010-2-030: Particular Requirements for Testing and Measuring  
Circuits  
RoHS Compliant  
UL Recognized Component: File #E179259  
UL Listed: File #E137808  
Type 4X Indoor/Outdoor Enclosure rating (Face only)  
IP65 Enclosure rating (Face only)  
IP20 Enclosure rating (Rear of unit)  
Refer to EMC Installation Guidelines for additional information.  
12. WEIGHT: 3.2 oz (100 g)  
Over Range Display: “R OLOLOL”  
Maximum Frequency: 20 KHz  
Minimum Frequency: 0.01 Hz  
Accuracy: ±0.01%  
5. COUNT/RATE SIGNAL INPUTS (INP A and INP B):  
Input A: DIP switch selectable to accept pulses from a variety of sources.  
See Section 2.0 Setting the DIP Switches for Input A specifications.  
Input B: Logic signals only  
Trigger levels: VIL = 0.7 V max; VIH = 2.4 V min; VMAX = 28 VDC  
Current sinking: Internal 10Kpull-up resistor to +9 to 28 VDC  
Filter (LO Freq.): Damping capacitor provided for switch contact bounce.  
Limits input frequency to 50 Hz and input pulse widths to 10 msec min.  
6. USER INPUT (USR): Programmable input. Connect to input common (INP  
COMM) to activate function. Internal 10Kpull-up resistor to +9 to 28 VDC.  
Threshold Levels: VIL = 0.7 V max; VIH = 2.4 V min; VMAX = 28 VDC  
Response Time: 5 msec typ.; 50 msec debounce (activation and release)  
2
optional pluG-in cardS  
VDS ON: 0.7 V @ 100 mA  
VDS MAX: 30 VDC  
Offstate Leakage Current: 0.5 mA max.  
ADDING OPTION CARDS  
The CUB5 meters can be fitted with optional output cards and/or serial  
communications cards. The details for the plug-in cards can be reviewed in the  
specification section below. The plug-in cards, that are sold separately, can be  
installed initially or at a later date.  
RS485 SERIAL COMMUNICATIONS CARD  
Type: RS485 multi-point balanced interface (non-isolated)  
Baud Rate: 300 to 38.4k  
Data Format: 7/8 bits; odd, even, or no parity  
Bus Address: 0 to 99; max 32 meters per line  
Transmit Delay: Selectable, 2 msec min. or 50 msec min.  
WARNING: Disconnect all power to the unit before installing  
Plug-in card.  
SINGLE RELAY OUTPUT CARD (One setpoint only)  
Type: Single FORM-C relay  
Isolation To Sensor & User Input Commons: 1400 Vrms for 1 min.  
Working Voltage: 150 Vrms  
Contact Rating: 1 amp @ 30 VDC resistive; 0.3 amp @ 125 VAC resistive  
Life Expectancy: 100,000 minimum operations  
Response Time:  
RS232 SERIAL COMMUNICATIONS CARD  
Type: RS232 half duplex (non-isolated)  
Baud Rate: 300 to 38.4k  
Data Format: 7/8 bits; odd, even, or no parity  
Turn On Time: 4 msec. max.  
Turn Off Time: 4 msec. max.  
USB PROGRAMMING CARD  
Type: USB virtual comms port  
Connection: Type B  
Baud Rate: 300 to 38.4k  
Unit Address: 0 to 99  
DUAL SINKING OUTPUT CARD (One or two setpoints)  
Type: Non-isolated switched DC, N Channel open drain MOSFET  
Current Rating: 100 mA max.  
1.0 inStallinG the Meter  
panel latch engage in the slots on the case. The panel latch should be engaged in  
the farthest forward slot possible. To achieve a proper seal, tighten the latch  
screws evenly until the unit is snug in the panel (Torque to approx. 28 to 36 in-oz  
[0.202 to 0.26 N-m]). Do not over-tighten the screws.  
INSTALLATION  
The meter meets NEMAType 4X/IP65 requirements when properly installed.  
The unit is intended to be mounted into an enclosed panel. Prepare the panel  
cutout to the dimensions shown. Remove the panel latch  
from the unit. Slide the panel gasket over the rear of  
the unit to the back of the bezel. The unit should be  
installed fully assembled. Insert the unit into the  
panel cutout.  
INSTALLATION ENVIRONMENT  
The unit should be installed in a location that does not exceed the operating  
temperature and provides good air circulation. Placing the unit near devices that  
generate excessive heat should be avoided.  
While holding the unit in place, push the panel  
latch over the rear of the unit so that the tabs of the  
The bezel should only be cleaned with a soft cloth and neutral soap product.  
Do NOT use solvents. Continuous exposure to direct sunlight may accelerate the  
aging process of the bezel.  
Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the  
keypad of the unit.  
NUT FASTENER  
PANEL  
BEZEL  
MOUNTING SCREW  
+.025  
2.68  
-.000  
+.024  
-.000  
+.8  
(68  
)
1.30  
(33  
-.0  
MOUNTING CLIP  
+.6  
)
-.0  
PANEL  
GASKET  
2.0 SettinG the dip SwitcheS  
To access the switches, remove the rear cover of the meter as described  
SETTING THE INPUT DIP SWITCHES  
The meter has four DIP switches for Input A and Input B that must be set  
before applying power.  
below. A bank of 4 switches is located in the upper right hand corner. After  
setting the switches, install any optional plug-in cards before replacing the rear  
cover (see next section).  
SWITCH 1  
Warning: Exposed line voltage exists on the circuit boards. Remove  
all power to the meter and load circuits before accessing inside of  
the meter.  
LOGIC: Input A trigger levels VIL = 1.25 V max.;  
VIH = 2.75 V min.; VMAX = 28 VDC  
MAG: 200 mV peak input sensitivity; 100 mV  
ON  
hysteresis; maximum input voltage: ±40 V peak  
REMOVE/REPLACE THE REAR COVER  
(28 Vrms); Must also have SRC switch ON.  
To remove the rear cover, locate the cover locking tab below the 2nd and 3rd  
input terminals. To release the tab, insert a small, flat blade screwdriver between  
the tab and the plastic wall below the terminals. Inserting the screwdriver will  
provide enough pressure to release the tab locks. To replace the cover, align the  
cover with the input terminals and press down until the cover snaps into place.  
(Not recommended with counting applications.)  
1
2
3
4
SWITCH 2  
SNK.: Adds internal 7.8 Kpull-up resistor to +9 to  
28 VDC, IMAX = 3.8 mA.  
SRC.: Adds internal 3.9 Kpull-down resistor,  
7.2 mA max. @ 28 VDC max.  
Factory Setting  
SWITCHES 3 and 4  
HI Frequency: Removes damping capacitor and allows max. frequency.  
LO Frequency: Adds a damping capacitor for switch contact bounce. Limits  
input frequency to 50 Hz and input pulse widths to 10 msec.  
3
3.0 inStallinG pluG-in cardS  
The Plug-in cards are separately purchased option cards that perform specific  
functions. The cards plug into the main circuit board of the meter. After  
installing the cards, replace the rear cover before wiring the meter.  
CAUTION: The Plug-in cards and main circuit board contain static  
sensitive components. Before handling the cards, discharge  
static charges from your body by touching a grounded bare  
metal object. Ideally, handle the cards at a static controlled  
clean workstation. Also, only handle the cards by the edges.  
Dirt, oil or other contaminants that may contact the cards can  
adversely affect circuit operation.  
ON  
ECE  
REMOVE/REPLACE THE REAR COVER  
1
2
3
4
Comms or  
Programming  
Card  
To remove the rear cover, locate the cover locking tab below the 2nd and 3rd  
input terminals. To release the tab, insert a small, flat blade screwdriver between  
the tab and the plastic wall below the terminals. Inserting the screwdriver will  
provide enough pressure to release the tab locks. To replace the cover, align the  
cover with the input terminals and press down until the cover snaps into place.  
Setpoint Card  
Locking Tab  
4.0 wirinG the Meter  
and portable two-way radios are used in close proximity or if the installation  
is near a commercial radio transmitter. Also, Signal or Control cables within  
an enclosure should be routed as far away as possible from contactors,  
control relays, transformers, and other noisy components.  
4. Long cable runs are more susceptible to EMI pickup than short cable runs.  
5. In extremely high EMI environments, the use of external EMI suppression  
devices such as Ferrite Suppression Cores for signal and control cables is  
effective. The following EMI suppression devices (or equivalent) are  
recommended:  
WIRING OVERVIEW  
Electrical connections are made via screw-clamp terminals located on the  
back of the meter. All conductors should conform to the meter’s voltage and  
current ratings. All cabling should conform to appropriate standards of good  
installation, local codes and regulations. It is recommended that the power  
supplied to the meter (DC or AC) be protected by a fuse or circuit breaker.  
Strip the wire, leaving approximately 0.3" (7.5 mm) bare lead exposed  
(stranded wires should be tinned with solder.) Insert the lead under the correct  
screw-clamp terminal and tighten until the wire is secure. (Pull wire to verify  
tightness.) Each terminal can accept up to one #14 AWG (2.55 mm) wire, two  
#18 AWG (1.02 mm), or four #20 AWG (0.61 mm).  
Fair-Rite part number 0443167251 (RLC part number FCOR0000)  
Line Filters for input power cables:  
Schaffner # FN2010-1/07 (Red Lion Controls # LFIL0000)  
6. To protect relay contacts that control inductive loads and to minimize radiated  
and conducted noise (EMI), some type of contact protection network is  
normally installed across the load, the contacts or both. The most effective  
location is across the load.  
a. Using a snubber, which is a resistor-capacitor (RC) network or metal oxide  
varistor (MOV) across an AC inductive load is very effective at reducing  
EMI and increasing relay contact life.  
b. If a DC inductive load (such as a DC relay coil) is controlled by a transistor  
switch, care must be taken not to exceed the breakdown voltage of the  
transistor when the load is switched. One of the most effective ways is to  
place a diode across the inductive load. Most RLC products with solid  
state outputs have internal zener diode protection. However external diode  
protection at the load is always a good design practice to limit EMI.  
Although the use of a snubber or varistor could be used.  
EMC INSTALLATION GUIDELINES  
Although Red Lion Controls Products are designed with a high degree of  
immunity to Electromagnetic Interference (EMI), proper installation and wiring  
methods must be followed to ensure compatibility in each application. The type  
of the electrical noise, source or coupling method into a unit may be different  
for various installations. Cable length, routing, and shield termination are very  
important and can mean the difference between a successful or troublesome  
installation. Listed are some EMI guidelines for a successful installation in an  
industrial environment.  
1. A unit should be mounted in a metal enclosure, which is properly connected  
to protective earth.  
2. Use shielded cables for all Signal and Control inputs. The shield connection  
should be made as short as possible. The connection point for the shield  
depends somewhat upon the application. Listed below are the recommended  
methods of connecting the shield, in order of their effectiveness.  
a. Connect the shield to earth ground (protective earth) at one end where the  
unit is mounted.  
b. Connect the shield to earth ground at both ends of the cable, usually when  
the noise source frequency is over 1 MHz.  
3. Never run Signal or Control cables in the same conduit or raceway with AC  
power lines, conductors, feeding motors, solenoids, SCR controls, and  
heaters, etc. The cables should be run through metal conduit that is properly  
grounded. This is especially useful in applications where cable runs are long  
RLC part numbers: Snubber: SNUB0000  
Varistor: ILS11500 or ILS23000  
7. Care should be taken when connecting input and output devices to the  
instrument. When a separate input and output common is provided, they  
should not be mixed. Therefore a sensor common should NOT be connected  
to an output common. This would cause EMI on the sensitive input common,  
which could affect the instrument’s operation.  
Visit RLC’s web site at http://www.redlion.net/emi for more information on  
EMI guidelines, Safety and CE issues as they relate to Red Lion Controls  
products.  
4.1 POWER WIRING  
DC Power  
4.2 USER INPUT WIRING  
Sinking Logic  
+9 to +28 VDC: +VDC  
INP COMM  
Connect external switching device between the  
}
User Input terminal and Input Common.  
Power Common: -VDC  
USR  
The user input of the meter is  
internally pulled up to +9 to +28 V  
with 10 K resistance. The input is  
active when it is pulled low (<1 .0 V).  
-
+
PWR COMMON  
+9-28 VDC  
PWR COMMON  
+9-28 VDC  
4
4.3 INPUT WIRING  
CAUTION: Power common (PWR COMMON) is NOT isolated from input common (INP COMM). In order to preserve the safety of the meter  
application, the power common must be suitably isolated from hazardous live earth referenced voltage; or input common must be at protective earth  
ground potential. If not, hazardous voltage may be present at the Signal or User Inputs and input common terminals. Appropriate considerations must  
then be given to the potential of the input common with respect to earth ground; and the common of the plug-in cards with respect to input common.  
Magnetic Pickup  
Two Wire Proximity, Current Source  
AC Inputs From Tach Generators, Etc.  
Input A  
Input A  
Input A  
ON  
1
ON  
1
ON  
*
3
*
4
*
3
*
4
*
AC  
MAGNETIC PICKUP  
2
2
1
2 3 4  
2.2 k Ω  
Resistor to Limit Current  
to 2.5 mA MAX.  
PWR COMMON  
+9-28 VDC  
PWR COMMON  
+9-28 VDC  
PWR COMMON  
+9-28 VDC  
Current Sinking Output  
Current Sourcing Output  
Interfacing With TTL  
Input A  
Input A  
Input A  
ON  
ON  
ON  
NPN  
O.C.  
+5 V  
*
3
*
4
*
3
*
4
*
PNP  
O.C.  
1
2
1
2
1
2 3 4  
COMMON  
PWR COMMON  
+9-28 VDC  
PWR COMMON  
+9-28 VDC  
PWR COMMON  
+9-28 VDC  
Switch or Isolated Transistor; Current Sink  
Switch or Isolated Transistor; Current Source Current Sink Output; Quad/Direction  
Input A  
Input A  
ON  
ON  
ON  
*
3
*
4
*
3
*
4
1
2
1
2 3 4  
1
2
PWR COMMON  
+9-28 VDC  
PWR COMMON  
+9-28 VDC  
PWR COMMON  
+9-28 VDC  
Switch position is application dependent.  
Shaded areas not recommended for counting applications.  
4.4 SETPOINT (OUTPUT) WIRING  
SINGLE SETPOINT RELAY PLUG-IN CARD  
ELECTRICAL CONNECTIONS  
COM  
N.O.  
N.C.  
N.O.  
COM  
N.C.  
DUAL SETPOINT N-FET OPEN DRAIN PLUG-IN CARD  
ELECTRICAL CONNECTIONS  
OSNK 1(2)  
COM  
(30 V MAX.)  
OSNK1  
OSNK2  
COM  
Note: Output Common is not isolated from DC Power Common. Load must  
be wired between OSNK terminal and V+ of the load supply.  
4.5 SERIAL COMMUNICATION WIRING 4.6 USB PROGRAMMING  
SERIAL COMMUNICATIONS PLUG-IN CARD  
USB PROGRAMING PLUG-IN CARD  
6
5
4
3
2
1
6
5
4
3
2
1
RS485  
RS232  
RJ11 CONNECTOR PIN OUTS  
5
5.0 reviewinG the front ButtonS and diSplay  
SEL  
RST  
KEY  
SEL  
DISPLAY MODE OPERATION  
ENTERING PROGRAM MODE  
PROGRAMMING MODE OPERATION  
Index display through enabled values  
Press and hold for 2 seconds to activate  
Store selected parameter and index to next parameter  
Advances through the program menu/  
Increments selected parameter value or selection  
RST  
Resets count display(s) and/or outputs  
OPERATING MODE DISPLAY DESIGNATORS  
R- To the left of the display is the rate value.  
- Counter A has no designator.  
b- To the left of the display is the Counter B value (dual count or batch).  
“1” and “2” - Indicates setpoint 1 and 2 output status.  
Pressing the SEL button toggles the meter through the selected displays. If display scroll is enabled, the display will toggle automatically every four seconds between  
the rate and count values.  
6.0 proGraMMinG the Meter  
DISPLAY  
MODE  
OVERVIEW  
SEL  
PROGRAMMING MENU  
NO  
Display and Front  
Panel Key  
Setpoint  
Output  
Parameters  
Serial  
Setup  
Parameters  
Rate Setup  
Parameters  
Input Setup  
Parameters  
Parameters  
Pro  
RST  
SEL  
SEL  
SEL  
SEL  
SEL  
2-rAtE  
3-dSPLAY  
1-INPUt  
4-SEtPt  
5-SEriAL  
PROGRAMMING MODE ENTRY (SEL KEY)  
PROGRAMMING MODE EXIT (SEL KEY)  
It is recommended all programming changes be made off line, or before  
installation. The meter normally operates in the Display Mode. No parameters  
can be programmed in this mode. The Programming Mode is entered by  
pressing and holding the SEL key. If it is not accessible then it is locked by  
either a security code, or a hardware lock.  
The Programming Mode is exited by pressing the SEL key with Pro NO  
displayed. This will commit any stored parameter changes to memory and  
return the meter to the Display Mode. (If power loss occurs before returning to  
the Display Mode, verify recent parameter changes.)  
PROGRAMMING TIPS  
MODULE ENTRY (SEL & RST KEYS)  
It is recommended to start with Module 1 for counting or Module 2 for rate.  
When programming is complete, it is recommended to record the parameter  
programming and lock out parameter programming with the user input or  
programming security code.  
The Programming Menu is organized into separate modules. These modules  
group together parameters that are related in function. The display will alternate  
between Proand the present module. The RST key is used to select the desired  
module. The displayed module is entered by pressing the SEL key.  
FACTORY SETTINGS  
MODULE MENU (SEL KEY)  
Factory settings may be completely restored in Module 3. This is useful when  
encountering programming problems.  
Each module has a separate module menu (which is shown at the start of each  
module discussion). The SEL key is pressed to advance to a particular parameter  
to be changed, without changing the programming of preceding parameters.  
After completing a module, the display will return to Pro NO. Programming may  
continue by accessing additional modules.  
ALTERNATING SELECTION DISPLAY  
In the explanation of the modules, the following dual display with arrows will  
appear. This is used to illustrate the display alternating between the parameter  
on top and the parameter’s factory setting on the bottom. In most cases,  
selections and values for the parameter will be listed on the right.  
SELECTION / VALUE ENTRY  
For each parameter, the display alternates between the present parameter and  
the selections/value for that parameter. The RST key is used to move through the  
selections/values for that parameter. Pressing the SEL key, stores and activates the  
displayed selection/value. This also advances the meter to the next parameter.  
For numeric values, press the RST key to access the value. The right hand  
most digit will begin to flash. Pressing the RST key again increments the digit  
by one or the user can hold the RST key and the digit will automatically scroll.  
The SEL key will advance to the next digit. Pressing and holding the SEL key  
will enter the value and move to the next parameter.  
Indicates Program Mode Alternating Display  
Parameter  
Cnt ud  
INP A-b  
Selection/Value  
Factory Settings are shown.  
6
6.1 Module 1 - input Setup paraMeterS (1-INPUt)  
PARAMETER MENU  
Dual Count  
or Batch  
Only  
1-INPUt  
Pro  
Dual Count or Batch  
SEL  
Only  
INP A-b  
CntA dP  
CntA ScF CntA rSt CntA dir CntA Ld  
Cntb bAt  
USEr INP  
Cntb dP  
Cntb ScF RSt P-UP  
USEr ASN  
Count  
Mode  
Counter A  
Decimal Point  
Counter A  
Scale Factor  
Counter A  
Reset Action  
Counter A  
Count  
Direction  
Counter A  
Count Load  
Value  
Counter B  
Batch Count  
Enable  
Counter B  
Decimal Point  
Counter B  
Scale Factor  
Counter Reset  
at Power-up  
User Input  
Function  
User Input  
Assignment  
Shaded area selections only apply when Counter B is enabled (Dual Counter  
mode or batch counter).  
COUNTER A COUNT LOAD VALUE  
COUNT MODE  
Cnt ud  
RAtE Cnt  
dUAL Cnt  
qUAd 1  
qUAd 2  
qUAd 4  
Add Add  
Add Sub  
00000500  
CmtA Ld  
INP A-b  
Cnt ud  
-9999999to 99999999  
Counter A resets to this value if Reset to Count Load action is selected.  
Select the count mode that corresponds with your application. The input  
actions are shown in the boxes below. For simple counting applications, it is  
recommended to use Count with Direction for the count mode. Simply leave the  
direction input unconnected.  
COUNTER B BATCH COUNT ENABLE  
NO  
Cmtb bAt  
NO  
SP2  
SP1 SP1-2  
DISPLAY  
Cnt ud  
MODE  
Count with Direction  
Rate/Counter  
INPUT A ACTION  
Counter A  
INPUT B ACTION  
Counter A Direction  
Counter A Add  
Counter B Add  
Quad A  
The Counter B batch count function internally counts the number of output  
activations of the selected setpoint(s). The count source for the batch counter  
can be SP1, SP2 or both. Batch counting is available in all count modes except  
Dual Counter, which uses an external input signal for Counter B. This  
parameter only appears if a Setpoint Output option card is installed.  
Rate only  
RAtE Cnt  
dUAL Cnt  
qUAd 1  
Dual Counter  
Counter A Add  
Count A  
Quadrature x1  
Quadrature x2  
Quadrature x4  
2 Input Add/Add  
2 Input Add/Subtract  
Count A  
Quad A  
COUNTER B DECIMAL POSITION  
qUAd 2  
Count A  
Quad A  
qUAd 4  
0
Cntb dP  
0
0.00  
0.0000  
Counter A Add  
Counter A Add  
Counter A Add  
Counter A Subtract  
Add Add  
Add Sub  
0.0  
0.000 0.00000  
This selects the decimal point position for Counter B. The selection will also  
affect Counter B scale factor calculations.  
Note: The Rate indicator signal is derived from Input A in all count modes.  
COUNTER A DECIMAL POSITION  
COUNTER B SCALE FACTOR  
0
CntA dP  
0
0.00  
0.000  
0.0000  
0.00000  
00.0001to 99.9999  
Cntb ScF  
0.0  
This selects the decimal point position for Counter A. The selection will also  
affect Counter A scale factor calculations.  
01.0000  
The number of input or batch counts is multiplied by the scale factor to  
obtain the desired process value. A scale factor of 1.0000 will result in the  
display of the actual number of input or batch counts. (Details on scaling  
calculations are explained at the end of this section.)*  
COUNTER A SCALE FACTOR  
01.0000  
CmtA ScF  
00.0001to 99.9999  
COUNTER RESET AT POWER-UP  
The number of input counts is multiplied by the scale factor to obtain the  
desired process value. A scale factor of 1.0000 will result in the display of the  
actual number of input counts. (Details on scaling calculations are explained at  
the end of this section.)*  
NO  
NO Count b  
NO  
RSt P-UP  
yES  
Count A both A-b  
COUNTER A RESET ACTION  
The selected counter(s) will reset at each meter power-up.  
to 2Ero  
CmtA rSt  
to 2Ero  
to CtLd  
* For value entry instructions, refer to selection/value entry in the Programming  
The Meter section.  
When Counter A is reset, it returns to Zero or Counter A Count Load value.  
This reset action applies to all Counter A resets, except a setpoint generated  
Counter Auto Reset programmed in Module 4.  
COUNTER A COUNT DIRECTION  
NOr  
CmtA dir  
NOr  
rEV  
Reverse (rEV) switches the normal Counter A count direction shown in the  
Count Mode parameter chart.  
7
USER INPUT FUNCTION  
SCALING FOR COUNT INDICATION  
The CUB5’s scale factor is factory set to 1, to provide one count on the  
display for each pulse that is input to the unit. In many applications, there will  
not be a one-to-one correspondence between input pulses and display units.  
Therefore, it is necessary for the CUB5 to scale or multiply the input pulses by  
a scale factor to achieve the desired display units (feet, meters, gallons, etc.)  
The Count Scale Factor Value can range from 00.0001 to 99.9999. It is  
important to note that the precision of a counter application cannot be improved  
by using a scale factor greater than one. To accomplish greater precision, more  
pulse information must be generated per measuring unit. The following formula  
is used to calculate the scale factor.  
NO  
USEr INP  
DISPLAY  
MODE  
DESCRIPTION  
No Function  
User Input disabled.  
NO  
See Programming Mode Access chart.  
(Module 3)  
Program Mode Lock-out  
Pro Loc  
Inhibit  
Inhibit counting for the selected counter(s).  
Level active reset of the selected counter(s).  
Inhibit  
rESEt  
Maintained Reset  
Desired Display Units  
Number of Pulses  
Scale Factor =  
x Decimal Point Position  
Freeze display of selected counter(s) while  
allowing counts to accumulate internally.  
Store  
StorE  
WHERE:  
Edge triggered reset of the selected  
counter(s) after storing the count.  
Desired Display Units: Count display units acquired after pulses that occurred.  
Number of Pulses: Number of pulses required to achieve the desired  
display units.  
Store and Reset  
Display Select *  
Stor-rSt  
d-SELECt  
d-LEVEL  
Advance once for each activation  
Increase intensity one level for each  
activation. (backlight version only)  
Display Intensity Level *  
Decimal Point Position:  
0
0.0  
0.00  
0.000  
0.0000  
0.00000  
=
=
=
=
=
=
1
10  
100  
1000  
10000  
100000  
Change backlight color with each activation  
(backlight version only)  
Backlight Color *  
Print Request  
d-COLOr  
Print  
Serial transmit of the active parameters  
selected in the Print Options (Module 5)  
Same as Print Request followed by a  
momentary reset of the selected counter(s).  
Print and Reset *  
Prnt-r5t  
Setpoint 1 Reset *  
Setpoint 2 Reset *  
Reset Setpoint 1 output  
Reset Setpoint 2 output  
rESEt-1  
rESEt-2  
rESEt-12  
EXAMPLE: The counter display is used to indicate the total number of feet  
used in a process. It is necessary to know the number of pulses for the desired  
units to be displayed. The decimal point is selected to show the resolution in  
hundredths.  
Setpoint 1 and 2 Reset * Reset Setpoint 1 and 2 outputs  
Note: * indicates Edge Triggered function. Other functions are Level Active  
(maintained)  
Desired Display Units  
Scale Factor =  
x Decimal Point Position  
Number of Pulses  
Given that 128 pulses are equal to 1 foot, display total feet with a one-  
hundredth resolution.  
USER INPUT ASSIGNMENT  
1.00  
Scale Factor =  
x 100  
USEr ASN  
Count A  
128  
Count A Count b both A-b  
Scale Factor = 0.007812 x 100  
Scale Factor = 0.7812  
The User Input Assignment is only active when Counter B is enabled and the  
User Input performs a Reset, Inhibit or Store function on one or both counters.  
6.2 Module 2 - rate Setup paraMeterS (2-rAtE)  
PARAMETER MENU  
2-rAtE  
Pro  
SEL  
RAtE Enb  
RAtE dP  
RAtE INP  
LO-Udt  
HI-Udt  
RAtE dSP  
Rate  
Enable  
Rate Decimal  
Point  
Rate Scaling  
Display Value  
Rate Scaling  
Input Value  
Rate Low  
Update Time  
Rate High  
Update Time  
Module 2 is the programming for the rate parameters. For maximum input  
frequency, Rate Enable should be set to NO when not in use. When set to NO, the  
remaining rate parameters are not accessible. The rate value is shown with an  
annunciator of “R” in the Display Mode.  
RATE SCALING DISPLAY VALUE  
001000  
RAtE dSP  
0 to 999999  
RATE ENABLE  
Enter the desired Rate Display Value for the Scaling Point.*  
YES  
RAtE Enb  
NO  
YES  
RATE SCALING INPUT VALUE  
01000.0  
RAtE INP  
0.1 to 99999.9  
RATE DECIMAL POINT  
O
RAtE dP  
0
0.00 0.0000  
0.000 0.00000  
Enter the corresponding Rate Input Value for the Scaling Point.*  
0.0  
This selects the decimal point position for the rate display and any setpoint  
value assigned to rate. This parameter does not affect rate scaling calculations.  
*For value entry instructions, refer to selection/value entry in the Programming  
The Meter section.  
8
INPUT FREQUENCY CALCULATION  
SCALING FOR RATE INDICATION  
The meter determines the input frequency by summing the number of falling  
edges received during a sample period of time. The sample period begins on the  
first falling edge. At this falling edge, the meter starts accumulating time  
towards Low Update and High Update values.Also, the meter starts accumulating  
the number of falling edges. When the time reaches the Low Update Time value,  
the meter looks for one more falling edge to end the sample period. If a falling  
edge occurs (before the High Update Time value is reached), the Rate display  
will update to the new value and the next sample period will start on the same  
edge. If the High Update Time value is reached (without receiving a falling edge  
after reaching Low Update Time), then the sample period will end but the Rate  
display will be forced to zero. The High Update Time value must be greater than  
the Low Update Time value. Both values must be greater than 0.0. The input  
frequency calculated during the sample period, is then shown as a Rate value  
determined by the scaling calculation.  
To scale the rate, enter a Scaling Display value with a corresponding Scaling  
Input value. These values are internally plotted to a display value of 0 and input  
value of 0.0 Hz. A linear relationship is formed between these points to yield a  
rate display value that corresponds to the incoming input signal rate. The meter  
is capable of showing a rate display value for any linear process.  
SCALING CALCULATION  
If a display value versus input signal (in pulses per second) is known, then  
those values can be entered into Scaling Display (RAtE dSP) and Scaling Input  
(RAtE INP). No further calculations are needed.  
If only the number of pulses per ‘single’ unit (i.e. # of pulses per foot) is  
known, then it can be entered as the Scaling Input value and the Scaling Display  
value will be entered as the following:  
RATE PER  
Second  
Minute  
DISPLAY (RAtE dSP)  
INPUT (RAtE INP)  
# of pulses per unit  
# of pulses per unit  
# of pulses per unit  
1
60  
Hour  
3600  
NOTES:  
1. If # of pulse per unit is less than 10, then multiply both Input and Display  
values by 10.  
2. If # of pulse per unit is less than 1, then multiply both Input and Display  
values by 100.  
3. If the Display value is raised or lowered, then Input value must be raised  
or lowered by the same proportion (i.e. Display value for per hour is  
entered by a third less (1200) then Input value is a third less of # of pulses  
per unit). The same is true if the Input value is raised or lowered, then  
Display value must be raised or lowered by the same proportion.  
4. Both values must be greater than 0.0.  
EXAMPLE:  
1. With 15.1 pulses per foot, show feet per minute in tenths. Scaling Display  
= 60.0 Scaling Input = 15.1.  
2. With 0.25 pulses per gallon, show whole gallons per hour. (To have greater  
accuracy, multiply both Input and Display values by 10.) Scaling Display  
= 36000 Scaling Input = 2.5.  
RATE LOW UPDATE TIME  
LO-Udt  
0.1 to 99.9 seconds  
01.0  
The Low Update Time is the minimum amount of time between display  
updates for the rate display. Values of 0.1 and 0.2 seconds will update the  
display correctly but may cause the display to appear unsteady.  
RATE HIGH UPDATE TIME  
02.0  
HI-Udt  
0.2 to 99.9 seconds  
The High Update Time is the maximum amount of time before the rate  
display is forced to zero. (For more explanation, refer to Rate Value  
Calculation.) The High Update Time must be higher than the Low Update Time  
and higher than the desired slowest readable speed (one divided by pulses per  
second). The factory setting of 2.0, will force the display to zero for speeds  
below 0.5 Hz or a pulse every 2 seconds.  
9
6.3 Module 3 - diSplay and front panel Key  
paraMeterS (3-dSPLAY)  
PARAMETER MENU  
3-dSPLAY  
Pro  
Backlight Unit Only  
SEL  
CodE UEr  
SEL Enb  
RSt Enb  
d-ScroLL  
Pro CodE  
FACt SEt  
d-COLOr  
d-LEVEL  
Software  
Version  
Display  
Front Panel  
Display Select  
Enable  
Front Panel  
Counter  
Reset Enable  
Display Scroll  
Enable  
Display  
Color  
Display  
Intensity  
Level  
Programming  
Security  
Load Factory  
Default  
Settings  
Code  
FRONT PANEL DISPLAY SELECT ENABLE (SEL)  
PROGRAMMING SECURITY CODE  
yES  
SEL Enb  
000  
Pro CodE  
0 to 999  
yES  
NO  
The yES selection allows the SEL button to toggle through the enabled  
The Security Code determines the programming mode and the accessibility  
of programming parameters. This code can be used indepentently or along with  
the Program Mode Lock-out (Pro Loc) selection in the User Input Function  
parameter (Module 1).  
displays.  
Two programming modes are available. Full Programming mode allows all  
unit parameters to be viewed and modified. Quick Programming mode permits  
only user selected values to be modified, but allows direct access to these values  
without having to enter Full Programming mode.  
Entering a Security Code from 1-99 enables Quick Programming mode, and  
displays a sublist to select what values appear in the Quick Programming menu.  
All applicable values set to YES in the sublist will be accessible in Quick  
Programming. The sublist includes Setpoint values (SP1 VAL, SP2 VAL), Output  
Time-out values (SP1 tOUt, SP2 tOUt), Counter A Count Load value (CntA Ld) and  
the Display Intensity Level (d-LEVEL) for backlight units.  
FRONT PANEL COUNTER RESET ENABLE (RST)  
yES  
NO  
NO  
Count A  
Count b  
both A-b  
dSPLAy  
YES  
RSt Enb  
The yESselection allows the RST button to reset the selected counter(s). The  
shaded selections are only active when Counter B is enabled (Dual Count mode  
or batch counter).  
Programming any Security Code other than 0, requires this code to be entered  
at the Pro CodE prompt in order to access Full Programming mode. Quick  
Programming mode, if enabled, is accessed before the Pro CodEprompt.  
DISPLAY SCROLL ENABLE  
NO  
d-ScroLL  
yES  
NO  
USER INPUT USER INPUT SECURITY  
MODE WHEN “SEL”  
KEY IS PRESSED  
FULL PROGRAMMING  
MODE ACCESS  
FUNCTION  
STATE  
CODE  
The yES selection allows the display to automatically scroll through the  
enabled displays. Each display is shown for 4 seconds.  
0
Full Programming  
Immediate Access  
After Quick Programming  
with correct code entry  
at Pro CodEprompt *  
Quick  
Programming  
1-99  
______  
not Pro Loc  
DISPLAY COLOR (BACKLIGHT UNIT ONLY)  
With correct code entry at  
Pro CodEprompt *  
100-999  
0
Pro CodEprompt  
rEd  
d-COLOr  
Programming  
Lock  
No Access  
No Access  
rEd  
6rn  
Quick  
Programming  
1-99  
Enter the desired display color, red or green. This parameter is active for  
backlight units only.  
Active  
Pro Loc  
With correct code entry at  
Pro CodEprompt *  
100-999  
0-999  
Pro CodEprompt  
Not Active  
Full Programming  
Immediate Access  
DISPLAY INTENSITY LEVEL (BACKLIGHT UNIT ONLY)  
* Entering Code 222 allows access regardless of security code.  
5
d-LEVEL  
1 to 5  
SOFTWARE VERSION DISPLAY  
Enter the desired Display Intensity Level (1-5). The display will actively dim  
or brighten as levels are changed. This parameter is active for backlight units only.  
CodE UEr  
NO  
NO  
yES  
Select YESto momentarily display the meter software version before advancing  
to the next parameter. The software version is also displayed at power-up.  
LOAD FACTORY DEFAULT SETTINGS  
FACt SEt  
NO  
yES  
MO  
The yESselection will return the meter to the factory default settings. The  
meter will display rESEtand then return to Pro, at which time all settings have  
been changed.  
10  
6.4 Module 4 - Setpoint output paraMeterS (4-SEtPt)  
4-SEtPt  
Pro  
PARAMETER MENU  
SP2 Only  
SEL  
SPt SEL  
SP2 Enb  
SPn ASN  
SPn ACt  
SPn tOUt  
SPn VAL  
SPn OUt  
SPn LIt  
Setpoint  
Select  
Setpoint 2  
Enable  
Setpoint  
Assignment  
Setpoint  
Setpoint  
Output  
Time-out  
Setpoint  
Value  
Setpoint  
Output Logic  
Setpoint  
Annunciator  
Output  
Action  
Backlight  
Unit Only  
SP1 Only  
SP2 Only  
SPn P-UP  
SPn tYPE  
SPn StbY  
SPn AUtO  
SP1 OFF2  
SP2 OFF1  
SPn rSt  
SPn ChC  
Setpoint Output  
Power-up  
State  
Setpoint  
Boundary  
Type  
Setpoint  
Standby  
Operation  
Counter  
Auto Reset  
SP1 Output  
Off at SP2  
Output  
SP2 Output  
Off at SP1  
Output  
Setpoint  
Output Reset  
with Manual  
Reset  
Change Display  
Color with  
Output State  
The Setpoint Output Parameters are only active when an optional Setpoint  
Output Module is installed in the meter. Some parameters in the menu will not  
appear depending on the Setpoint Assignment and Setpoint Output Action. The  
Setpoint Parameter Availability chart below illustrates this.  
SETPOINT OUTPUT ACTION  
SETPOINT SELECT  
NO  
SPt SEL  
LAtCH  
SPn ACt  
LAtCH  
t-OUt  
bOUNd  
NO  
SP1  
SP2  
Select the Setpoint Output to be programmed, starting with Setpoint 1. The  
"n" in the following parameters reflects the chosen Setpoint number. After  
Setpoint 1 is completely programmed, the display returns to SPt SEL. Repeat  
steps for Setpoint 2 if both Setpoints are used in the application.  
The parameter selects the action of the Setpoint Output as described in the  
chart. Boundary output action is not applicable for Counter B assignment.  
SPT ACTION DESCRIPTION  
OUTPUT ACTIVATES OUTPUT DEACTIVATES  
Select NOto exit the Setpoint programming module. The number of Setpoints  
available is dependent on the Setpoint option module installed.  
When Count =  
Setpoint  
At Manual Reset  
(if SPn rSt=YES)  
Latched Output Mode  
LAtCH  
t-OUt  
When Count =  
Setpoint  
After Setpoint  
Output Time-Out  
Timed Output Mode  
SETPOINT 2 ENABLE (SP2 Only)  
Boundary Mode  
(High Acting Type)  
When Count  
< Setpoint  
When Count ≥  
Setpoint  
bOUNd  
Boundary Mode  
(Low Acting Type)  
When Count  
> Setpoint  
When Count ≤  
NO  
SP2 Enb  
Setpoint  
NO  
YES  
Select YESto enable Setpoint 2 and access the setup parameters. If NOis  
selected, the unit returns to SPt SELand Setpoint 2 is disabled.  
SETPOINT ASSIGNMENT  
Count A  
SPn ASN  
Count A  
Count b  
rAtE  
Select the display to which the Setpoint is assigned.  
SETPOINT PARAMETER AVAILABILITY  
COUNTER ASSIGNMENT (A or B) *  
RATE ASSIGNMENT  
PARAMETER  
DESCRIPTION  
TIMED OUT BOUNDARY  
LATCH  
LAtCH  
TIMED OUT BOUNDARY  
LATCH  
LAtCH  
t-OUt  
Yes  
Yes  
Yes  
Yes  
No  
bOUNd  
t-OUt  
Yes  
Yes  
Yes  
Yes  
No  
bOUNd  
Setpoint Output Time-out Value  
Setpoint Value  
No  
No  
Yes  
Yes  
Yes  
Yes  
No  
No  
No  
SPn tOUt  
SPn VAL  
SPn OUt  
SPn LIt  
SPn P-UP  
SPn tYPE  
SPn StbY  
SPn AUtO  
SP1 OFF2  
SP2 OFF1  
SPn rSt  
SPn ChC  
Yes  
Yes  
Yes  
No  
Yes  
Yes  
Yes  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
Setpoint Output Logic  
Setpoint Annunciator  
Setpoint Output Power-up State  
Setpoint Boundary Type  
No  
Yes  
Yes  
No  
Yes  
Yes  
No  
Yes  
Yes  
No  
Standby Operation (Low acting only)  
Counter Auto Reset  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
SP1 Output Off at SP2 (SP1 only)  
SP2 Output Off at SP1 (SP2 only)  
Output Reset with Manual Reset  
Change Display Color w/ Output State  
No  
No  
No  
No  
No  
No  
No  
No  
No  
Yes  
Yes  
No  
Yes  
Yes  
Yes  
Yes  
* BOUNDARY Setpoint Action not applicable for Counter B Assignment  
11  
SETPOINT OUTPUT TIME-OUT  
COUNTER AUTO RESET  
SPn tOUt  
This parameter is only active if the Setpoint Action is set to time out (t-OUt).  
Enter the value in seconds that the Setpoint output will be active, once the  
Setpoint Value is reached.  
NO  
SPn AUtO  
NO  
@2Ero-Str  
2Ero-End  
CtLd-Str  
CtLd-End  
0.01 to 599.99 seconds  
001.00  
This parameter automatically resets the counter to which the setpoint is  
assigned (SPn ASN) each time the setpoint value is reached. The automatic reset  
can occur at output start, or at output end if the Setpoint Output Action is  
programmed for timed output mode. The Reset-to-Count Load selections  
(“CtLd-”) only apply to Counter A assignment. This reset may be different from  
the Counter A Reset Action selected in Module 1.  
SETPOINT VALUE  
SELECTION ACTION  
Count A:  
Count B:  
Rate:  
-9999999to 99999999  
0to 9999999  
0to 999999  
SPn VAL  
00000100  
No Auto Reset.  
NO  
Reset to Zero at the start of output activation.  
2Ero-Str  
CtLd-Str  
2Ero-End  
Reset to Count Load value at the start of output activation.  
Reset to Zero at the end of output activation (timed out only).  
Enter the desired Setpoint value. To enter a negative setpoint value,  
increment digit 8 to display a “-” sign (Counter A only).  
Reset to Count Load value at the end of output activation  
(timed out only).  
CtLd-End  
SETPOINT OUTPUT LOGIC  
NOr  
SETPOINT 1 OUTPUT OFF AT SETPOINT 2 (SP1 Only)  
SPn OUt  
NOr  
rEV  
SP1 OFF2  
NO  
Out2-Str Out2-End  
Normal (NOr) turns the output “on” when activated and “off” when  
deactivated. Reverse (rEV) turns the output “off” when activated and “on” when  
deactivated.  
NO  
This parameter will deactivate Setpoint 1 output at the Start or End of  
Setpoint 2 output (O1 off at O2). The “-End” setting only applies if Setpoint 2  
Output Action is programmed for timed output.  
SETPOINT ANNUNCIATOR  
NOr  
SPn LIt  
SETPOINT 2 OUTPUT OFF AT SETPOINT 1 (SP2 Only)  
NOr  
rEV  
SP2 OFF1  
NO  
Out1-Str  
Out1-End  
Normal (NOr) displays the setpoint annunciator when the corresponding  
output is “on”. Reverse (rEV) displays the setpoint annunciator when the output  
is “off”.  
NO  
This parameter will deactivate Setpoint 2 output at the Start or End of  
Setpoint 1 output (O2 off at O1). The “-End” setting only applies if Setpoint 1  
Output Action is programmed for timed output.  
SETPOINT OUTPUT POWER-UP STATE  
OFF  
ON  
SAVE  
SETPOINT OUTPUT RESET WITH MANUAL RESET  
OFF  
SPn P-UP  
YES  
SPn rSt  
YES  
NO  
SAVEwill restore the output to the same state it was at before the meter was  
powered down. ONwill activate the output at power up. OFFwill deactivate the  
output at power up.  
Selecting YES causes the Setpoint output to deactivate (reset) when the  
Setpoint Assigned Counter is reset. The counter reset can occur by the RST  
button, User Input, Counter Reset at Power-up or a serial Reset Counter  
command.  
SETPOINT BOUNDARY TYPE  
This output reset will not occur when the Assigned Counter is reset by a  
Setpoint generated Counter Auto Reset.  
SPn tYPE  
HI-ACt  
LO-ACt  
HI-ACt  
High Acting Boundary Type activates the output when the assigned display  
value (SPn ASN) equals or exceeds the Setpoint value. Low Acting activates the  
output when the assigned display value is less than or equal to the Setpoint.  
CHANGE DISPLAY COLOR WITH OUTPUT STATE  
NO  
SPn ChC  
NO  
YES  
SETPOINT STANDBY OPERATION  
This parameter enables the backlight CUB5 to switch the backlight color when  
the output state changes. This parameter is only active for the backlight version.  
SPn StbY  
NO  
YES  
NO  
This parameter only applies to Low Acting Boundary Type setpoints. Select  
YESto disable a Low Acting Setpoint at power-up, until the assigned display  
value crosses into the output “off” area. Once in the output “off” area, the  
Setpoint will then function per the description for Low Acting Boundary Type.  
12  
6.5 Module 5 - Serial coMMunicationS paraMeterS (5-SEriAL)  
5-SEriAL  
Pro  
PARAMETER MENU  
SEL  
bAUd  
dAtA  
PAritY  
Addr  
Abbr  
Prnt OPt  
COPY  
Baud Rate  
Data Bit  
Parity Bit  
Meter  
Address  
Print  
Options  
Copy Program  
Settings  
Abbreviated  
Printing  
The Serial Setup Parameters are only active when one of the optional serial  
communication/programming cards is installed in the meter.  
PRINT OPTIONS  
Refer to the CUB5USB bulletin for details on the CUB5 USB programming  
and programming requirements. This section replaces the bulletin shipped with  
the RS232 and RS485 serial communications plug-in cards. Discard the  
separate bulletin when using those serial plug-in cards with the CUB5B and  
CUB5R.  
NO  
YES  
Prnt OPt  
NO  
This parameter selects the meter values transmitted in response to a Print  
Request. A print request is also referred to as a block print because more than  
one parameter can be sent to a printer or computer as a block.  
Selecting YES displays a sublist for choosing the meter parameters to appear  
in the print block. All active parameters entered as YESin the sublist will be  
transmitted during a block print. Parameters entered as NOwill not be sent.  
The “Print All” (Prnt ALL) option selects all meter values for transmitting  
(YES), without having to individually select each parameter in the sublist.  
Note: Inactive parameters will not be sent regardless of the print option  
setting. For example, Counter B or Scale Factor B will only be sent if Counter  
B is enabled (Dual Counter mode or batch count). Likewise, the Setpoint  
value(s) will not be sent unless an optional setpoint card is installed in the meter.  
BAUD RATE  
300  
600  
1200  
2400  
4800  
9600  
19200  
38400  
9600  
bAUd  
Set the baud rate to match that of other serial communications equipment.  
Normally, the baud rate is set to the highest value that all of the serial  
communications equipment is capable of transmitting and receiving.  
FACTORY  
SETTING  
DISPLAY  
DESCRIPTION  
MNEMONIC  
DATA BIT  
Counter A  
Counter B  
CTA  
CTB  
RTE  
SFA  
SFB  
SP1  
SP2  
CLD  
Count A  
Count b  
RAtE  
YES  
NO  
NO  
NO  
NO  
NO  
NO  
NO  
7-bit  
dAtA  
7-bit 8-bit  
Rate Value  
Scale Factor A  
Scale Factor B  
Setpoint 1  
CntA ScF  
Cntb ScF  
sSP1  
Select either 7- or 8-bit data word length. Set the word length to match the  
other serial communications equipment on the serial link.  
Setpoint 2  
SP2  
Counter A Count Load  
CntA Ld  
PARITY BIT  
Odd  
PAritY  
NO  
Odd  
EVEN  
COPY PROGRAM SETTINGS  
This parameter only appears when the Data Bit parameter is set to a 7-bit  
data word length. Set the parity bit to match that of the other serial equipment  
on the serial link. The meter ignores parity when receiving data and sets the  
parity bit for outgoing data. If parity is set to NO, an additional stop bit is used  
to force the frame size to 10 bits.  
NO  
COPY  
NO  
YES  
This parameter is used to copy all the program settings from one CUB5  
meter directly to another CUB5 meter, through the serial communications cards  
(RS232 or RS485). The USB programming card cannot be used for the copy  
procedure. No PC connection or additional software is required. Copying  
program settings eliminates the need for repetitive programming when multiple  
meters use identical settings.  
METER ADDRESS  
0 to 99  
00  
Addr  
Copy Requirements:  
To copy program settings from one meter to another requires the following:  
1. Both meters must have the same software version (Version 3.1 or later). The  
version is displayed during the meter power-up sequence, or in Module 3 at  
the Software Version Display parameter. (See Module 3 for details)  
2. The meter receiving the program settings (receiver) must have the Baud Rate  
set to 9600 baud. Since this is the factory default setting, a new meter will  
arrive ready for copying. The meter sending the program settings (master)  
should be set to the desired Baud Rate for the application (if different than  
9600). This Baud Rate setting will then be copied to the receiver.  
Enter the serial node address. With a single unit, an address is not needed  
and a value of zero can be used (RS232 applications). Otherwise, with multiple  
bussed units, a unique address number must be assigned to each meter. The  
node address applies specifically to RS485 applications.  
ABBREVIATED PRINTING  
NO  
YES  
Abbr  
Copy Connections:  
To connect the meters for copying, install a serial communications card of  
the same type into each meter (RS232 or RS485). Connect the meters using the  
proper cable listed in the chart.  
NO  
This parameter determines the formatting of data transmitted from the meter  
in response to a Transmit Value command or a Block Print Request. Select NO  
for a full print transmission, consisting of the meter address, mnemonics, and  
parameter data. Select YESfor abbreviated print transmissions, consisting of the  
parameter data only. This setting is applied to all the parameters selected in the  
PRINT OPTIONS. (Note: If the meter address is 0, the address will not be sent  
during a full transmission.)  
TYPE  
DESCRIPTION  
PART NUMBER  
CBLRLC02  
CBLRLCS2  
RS232 Copy Cable RS232 10’ (RJ12-RJ12)  
RS485 Copy Cable RS485 10’ (RJ12-RJ12)  
13  
Copy Procedure:  
1. Connect the master and receiver using the appropriate copy cable.  
2. Apply power to the meters. The receiving meter must be operating in the  
normal display mode (not programming mode).  
MASTER  
3. On the master meter, enter programming mode and proceed to the Copy  
Program Settings parameter in Module 5. Select YESto begin copying.  
4. During the copy process (~ 2 sec.), the master meter displays an upload  
message (UP-LOAd) while the receiver displays a download message (dn-LOAd).  
This indicates successful communication between the master and receiver. If  
the receiver message is not displayed, be sure the proper cable is connected.  
5. When copying is complete, the receiver displays the power-up sequence and  
returns to normal operating mode, programmed with all the same settings as  
the master meter. The master remains at the COPYprompt, ready to connect  
another receiver for copying.  
UP-LOAd  
SEL  
RST  
RECEIVER  
dn-LOAd  
SEL  
RST  
Sending Serial Commands and Data  
When sending commands to the meter, a string containing at least one  
command character must be constructed. A command string consists of a  
command character, a value identifier, and numerical data (if writing data to the  
meter) followed by a command terminator character, * or $.  
Command String Examples:  
1. Node address = 17, Write 350 to the Setpoint 1 value  
String: N17VF350*  
2. Node address = 5, Read Counter A, response time of 50 msec min  
String: N5TA*  
3. Node address = 0, Reset Setpoint 1 output  
Command Chart  
String: RF*  
Command Description  
Notes  
4. Node address = 31, Request a Block Print Output, response time of 2 msec min  
String: N31P$  
Address a specific meter. Must be followed  
by one or two digit node address. Not  
required when node address = 0.  
Node (meter)  
N
Address Specifier  
Transmitting Data to the Meter  
Transmit Value  
(read)  
Read a register from the meter. Must be  
followed by a register ID character.  
Numeric data sent to the meter must be limited to transmit details listed in the  
Register Identification Chart. Leading zeros are ignored. Negative numbers  
must have a minus sign. The meter ignores any decimal point and conforms the  
number to the scaled resolution. (For example: The meter’s scaled decimal point  
position is set for 0.0 and 25 is written to a register. The value of the register is  
now 2.5. In this case, write a value of 250 to equal 25.0).  
T
Write to register of the meter. Must be  
V
Value Change (write) followed by a register ID character and  
numeric data.  
Reset a count value or setpoint output. Must  
be followed by a register ID character  
R
P
Reset  
Block Print Request Initiates a block print output. Registers in the  
(read)  
Note: Since the meter does not issue a reply to value change commands, follow  
with a transmit value command for readback verification.  
print block are selected in Print Options.  
Register Identification Chart  
Receiving Data From The Meter  
Applicable  
Commands  
ID  
Value Description  
MNEMONIC  
Transmit Details (T and V)  
Data is transmitted from the meter in response to either a transmit command  
(T), a block print request command (P) or a User Input print request. The  
response from the meter is either a full field transmission or an abbreviated  
transmission, depending on the selection chosen in Module 5.  
A
Counter A  
CTA  
T, V, R  
8 digit positive/7 digit  
negative (with minus sign)  
B
C
D
E
F
Counter B  
Rate  
CTB  
RTE  
SFA  
SFB  
SP1  
T, V, R  
T
7 digit, positive only  
6 digit, positive only  
6 digit, positive only  
6 digit, positive only  
Full Field Transmission  
Byte  
1, 2  
3
Description  
Scale Factor A  
Scale Factor B  
T, V  
2 byte Node Address field [00-99]  
<SP> (Space)  
T, V,  
T, V, R  
Setpoint 1  
per setpoint Assignment,  
same as Counter or Rate  
4-6  
7-18  
3 byte Register Mnemonic field  
(Reset Output 1)  
12 byte data field; 10 bytes for number, one byte for sign,  
one byte for decimal point  
G
H
Setpoint 2  
(Reset Output 2)  
SP2  
CLD  
T, V, R  
T, V  
per setpoint Assignment,  
same as Counter or Rate  
19  
20  
21  
22  
23  
<CR> (carriage return)  
<LF> (line feed)  
Counter A Count  
Load Value  
8 digit positive/7 digit  
negative (with minus sign)  
<SP>* (Space)  
Command String Construction  
<CR>* (carriage return)  
<LF>* (line feed)  
The command string must be constructed in a specific sequence. The meter  
does not respond with an error message to illegal commands. The following  
procedure details construction of a command string:  
* These characters only appear in the last line of a block print.  
1. The first 2 or 3 characters consist of the Node Address Specifier (N) followed  
by a 1 or 2 character node address number. The node address number of the  
meter is programmable. If the node address is 0, this command and the node  
address itself may be omitted. This is the only command that may be used in  
conjunction with other commands.  
2. After the optional address specifier, the next character is the command character.  
3. The next character is the register ID. This identifies the register that the  
command affects. The P command does not require a register ID character. It  
prints all the active selections chosen in the Print Options menu parameter.  
4. If constructing a value change command (writing data), the numeric data is  
sent next.  
The first two characters transmitted are the meter address. If the address  
assigned is 0, two spaces are substituted. A space follows the meter address  
field. The next three characters are the register mnemonic, as shown in the  
Register Identification Chart.  
The numeric data is transmitted next. The numeric field (bytes 7 to 18) is 12  
characters long. When a requested counter or rate value exceeds the meter’s  
display limits, an * (used as an overflow character) replaces a space in byte 7.  
Byte 8 is always a space.  
The remaining ten positions of this field consist of a minus sign (for negative  
values), a floating decimal point (if applicable), and eight positions for the  
requested value. The data within bytes 9 to 18 is right-aligned with leading  
spaces for any unfilled positions.  
The end of the response string is terminated with a <CR> and <LF>. After  
the last line of a block print, an extra <SP>, <CR> and <LF> are added to  
provide separation between the print blocks.  
5. All command strings must be terminated with the string termination characters  
* or $. The meter does not begin processing the command string until this  
character is received. See Command Response Time section for differences in  
meter response time when using the * and $ terminating characters.  
14  
Abbreviated Transmission  
Communication Format  
Byte  
Description  
Data is transferred from the meter through a serial communication channel.  
In serial communications, the voltage is switched between a high and low level  
at a predetermined rate (baud rate) using ASCII encoding. The receiving device  
reads the voltage levels at the same intervals and then translates the switched  
levels back to a character. The voltage level conventions depend on the interface  
standard. The table lists the voltage levels for each standard.  
1-12  
12 byte data field, 10 bytes for number, one byte for  
sign, one byte for decimal point  
13  
14  
15  
16  
17  
<CR> (carriage return)  
<LF> (line feed)  
<SP>* (Space)  
LOGIC  
INTERFACE STATE  
mark (idle)  
RS232*  
RS485*  
<CR>* (carriage return)  
<LF>* (line feed)  
1
0
TXD,RXD; -3 to -15 V  
TXD,RXD; +3 to +15 V  
a-b < -200 mV  
a-b > +200 mV  
space (active)  
* These characters only appear in the last line of a block print.  
* Voltage levels at the Receiver  
The abbreviated response suppresses the node address and register ID,  
leaving only the numeric part of the response.  
Data is transmitted one byte at a time with a variable idle period between  
characters (0 to ). Each ASCII character is “framed” with a beginning start bit,  
an optional parity bit and one or more ending stop bits. The data format and  
baud rate must match that of other equipment in order for communication to  
take place. The figures list the data formats employed by the meter.  
Meter Response Examples:  
1. Node address = 17, full field response, Counter A = 875  
17 CTA  
2. Node address = 0, full field response, Setpoint 1 = -250.5  
SP1 -250.5<CR><LF>  
875 <CR><LF>  
3. Node address = 0, abbreviated response, Setpoint 1 = 250, last line of block  
print  
250<CR><LF><SP><CR><LF>  
Command Response Time  
The meter can only receive data or transmit data at any one time (half-duplex  
operation). During RS232 transmissions, the meter ignores commands while  
transmitting data, but instead uses RXD as a busy signal. When sending  
commands and data to the meter, a delay must be imposed before sending  
another command. This allows enough time for the meter to process the  
command and prepare for the next command.  
At the start of the time interval t1, the computer program prints or writes the  
string to the com port, thus initiating a transmission. During t1, the command  
characters are under transmission and at the end of this period, the command  
terminating character (* or $) is received by the meter. The time duration of t1  
is dependent on the number of characters and baud rate of the channel.  
Character Frame Figure  
Start Bit and Data Bits  
Data transmission always begins with the start bit. The start bit signals the  
receiving device to prepare for reception of data. One bit period later, the least  
significant bit of the ASCII encoded character is transmitted, followed by the  
remaining data bits. The receiving device then reads each bit position as they are  
transmitted.  
t1 = (10 times the # of characters) / baud rate  
Parity Bit  
At the start of time interval t2, the meter starts the interpretation of the  
command and when complete, performs the command function. This time  
interval t2 varies. If no response from the meter is expected, the meter is ready  
to accept another command.  
If the meter is to reply with data, the time interval t2 is controlled by the use  
of the command terminating character. The ‘*’ terminating character results in a  
response time of 50 msec. minimum. This allows sufficient time for the release  
of the sending driver on the RS485 bus. Terminating the command line with ‘$’  
results in a response time (t2) of 2 msec. minimum. The faster response time of  
this terminating character requires that sending drivers release within 2 msec.  
after the terminating character is received.  
After the data bits, the parity bit is sent. The transmitter sets the parity bit to  
a zero or a one, so that the total number of ones contained in the transmission  
(including the parity bit) is either even or odd. This bit is used by the receiver to  
detect errors that may occur to an odd number of bits in the transmission.  
However, a single parity bit cannot detect errors that may occur to an even  
number of bits. Given this limitation, the parity bit is often ignored by the  
receiving device. The CUB5 meter ignores the parity bit of incoming data and  
sets the parity bit to odd, even or none (mark parity) for outgoing data.  
Stop Bit  
The last character transmitted is the stop bit. The stop bit provides a single bit  
period pause to allow the receiver to prepare to re-synchronize to the start of a  
new transmission (start bit of next byte). The receiver then continuously looks  
for the occurrence of the start bit. If 7 data bits and no parity is selected, then 2  
stop bits are sent from the meter.  
At the beginning of time interval t3, the meter responds with the first  
character of the reply. As with t1, the time duration of t3 is dependent on the  
number of characters and baud rate of the channel. At the end of t3, the meter is  
ready to receive the next command.  
t3 = (10 times the # of characters) / baud rate  
The maximum serial throughput of the meter is limited to the sum of the  
times t1, t2 and t3.  
NO REPLY FROM METER  
Command  
String  
Transmission  
Meter  
Response  
Time  
t1  
t2  
Ready  
Ready  
RESPONSE FROM METER  
t1  
t2  
t3  
Ready  
Ready  
Reply  
Transmission  
Time  
First  
Character  
of Reply  
Command  
Terminator  
Received  
Timing Diagram Figure  
15  
cuB5 proGraMMinG QuicK overview  
16  

相关型号:

SI9130DB

5- and 3.3-V Step-Down Synchronous Converters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1-E3

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135_11

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9136_11

Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130CG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130LG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130_11

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137DB

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137LG

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9122E

500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification Drivers

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY