Characteristics
TeSys D control relay - 5 NO - 690 V - 110 V DC
standard coil
Main
Range
TeSys
Product name
TeSys CAD
Control relay
CAD
Product or component type
Device short name
Contactor application
Control circuit
Complementary
Utilisation category
AC-15
DC-13
AC-14
Pole contact composition
[Ue] rated operational voltage
Control circuit type
5 NO
<= 690 V AC 25...400 Hz
DC standard
[Uc] control circuit voltage
Coil technology
110 V DC
With integral suppression device
6 kV conforming to IEC 60947
10 A (at 60 °C)
[Uimp] rated impulse withstand voltage
[Ith] conventional free air thermal
current
Irms rated making capacity
140 A AC conforming to IEC 60947-5-1
250 A DC conforming to IEC 60947-5-1
[Icw] rated short-time withstand current
100 A - 1 s
120 A - 500 ms
140 A - 100 ms
Associated fuse rating
[Ui] rated insulation voltage
Mounting support
10 A gG conforming to IEC 60947-5-1
690 V conforming to IEC 60947-5-1
Rail
Plate
Connections - terminals
Tightening torque
Lugs-ring terminals (external diameter: 9.5 mm)
1.7 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5
1.7 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5
Aug 16, 2019
1
Control circuit voltage limits
Operating time
Operational: 0.7...1.25 Uc (at <60 °C)
Drop-out: 0.1...0.25 Uc (at <60 °C)
53...72 ms coil energisation and NO closing
16...24 ms coil de-energisation and NO opening
Mechanical durability
Maximum operating rate
Time constant
30 Mcycles
180 cyc/mn
28 ms
Inrush power in W
5.4 W (at 20 °C)
5.4 W at 20 °C
17 V
Hold-in power consumption in W
Minimum switching voltage
Minimum switching current
Non-overlap time
5 mA
1.5 ms on energisation between NC and NO contact
1.5 ms on de-energisation between NC and NO contact
Insulation resistance
> 10 MOhm
Mechanical robustness
Shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27
Shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27
Vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
Height
77 mm
45 mm
93 mm
0.32 kg
Width
Depth
Net weight
Environment
Standards
EN 45545: R22 HL3
EN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
Product certifications
CCC
EAC
CSA
IEC
UL
IP degree of protection
Protective treatment
IP20 front face conforming to IEC 60529
TH conforming to IEC 60068
-40…70 °C
Ambient air temperature for operation
Ambient air temperature for storage
Operating altitude
-60…80 °C
3000 m without
Fire resistance
850 °C conforming to IEC 60695-2-1
V0 conforming to UL 94
Flame retardance
Offer Sustainability
Sustainable offer status
REACh Regulation
Green Premium product
REACh Declaration
EU RoHS Directive
Not applicable, out of EU RoHS legal scope
EU RoHS Declaration
Mercury free
Yes
Yes
RoHS exemption information
China RoHS Regulation
Download RoHS China Declaration
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure
Circularity Profile
WEEE
Product Environmental Profile
End of Life Information
The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins
2
Contractual warranty
Warranty
18 months
3
相关型号:
©2020 ICPDF网 联系我们和版权申明