GV2ME143 [SCHNEIDER]
Thermal Magnetic Circuit Breaker, 3 Pole(s), 10A, 690VAC, Din-rail Mount;![GV2ME143](http://pdffile.icpdf.com/pdf2/p00304/img/icpdf/GV2ME143_1835666_icpdf.jpg)
型号: | GV2ME143 |
厂家: | ![]() |
描述: | Thermal Magnetic Circuit Breaker, 3 Pole(s), 10A, 690VAC, Din-rail Mount 电路保护 |
文件: | 总3页 (文件大小:88K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
![](http://public.icpdf.com/style/img/ads.jpg)
Product data sheet
Characteristics
GV2ME143
TeSys GV2 - Circuit breaker - thermal-magnetic -
6...10 A - spring terminals
Main
Range
TeSys
Product name
TeSys GV2
GV2ME
Device short name
Product or component type
Device application
Trip unit technology
Circuit breaker
Motor
Thermal-magnetic
Complementary
Poles description
Network type
3P
AC
Utilisation category
AC-3 conforming to IEC 60947-4-1
Category A conforming to IEC 60947-2
Network frequency
Mounting mode
50/60 Hz conforming to IEC 60947-4-1
By clips
By screws
Mounting support
Mounting position
Rail
Horizontal
Vertical
Motor power kW
3 kW at 400/415 V AC 50/60 Hz
4 kW at 400/415 V AC 50/60 Hz
4 kW at 500 V AC 50/60 Hz
5.5 kW at 500 V AC 50/60 Hz
Breaking capacity
3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit
breaking capacity
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
Mar 13, 2017
1
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Control type
Push-button
[In] rated current
6...10 A
Trip unit rating
6...10 A
Magnetic tripping current
[Ue] rated operational voltage
[Ui] rated insulation voltage
138 A
690 V AC 50/60 Hz conforming to IEC 60947-2
690 V AC 50/60 Hz conforming to IEC 60947-2
10 A conforming to IEC 60947-4-1
[Ith] conventional free air thermal
current
[Uimp] rated impulse withstand voltage
Power dissipation per pole
Mechanical durability
Electrical durability
6 kV conforming to IEC 60947-2
2.5 W
100000 cycles
100000 cycles for AC-3 at 440 V
25 cyc/h
Operating rate
Rated duty
Continuous conforming to IEC 60947-4-1
Connections - terminals
Spring terminals 2 cable(s) 1...6 mm² - cable stiffness : solid
Spring terminals 2 cable(s) 1.5...4 mm² - cable stiffness : flexible - without cable end
Mechanical robustness
Vibrations 5 Gn, 5...150 Hz conforming to IEC 60068-2-6
Shocks 30 Gn for 11 ms conforming to IEC 60068-2-27
Suitability for isolation
Phase failure sensitivity
Height
Yes conforming to IEC 60947-1
Yes conforming to IEC 60947-4-1
101 mm
45 mm
Width
Depth
78.2 mm
0.28 kg
Product weight
Environment
Standards
VDE 0660
NF C 63-650
UL 508
CSA C22.2
IEC 60947-4-1
VDE 0113
IEC 60947-1
NF C 63-120
IEC 60947-2
NF C 79-130
EN 60204
Product certifications
DNV
TSE
LROS
UL
RINA
ATEX
EZU
BV
CEBEC
CSA
CCC
GL
EAC
SETI
Protective treatment
TH
IP degree of protection
IK degree of protection
Ambient air temperature for operation
Ambient air temperature for storage
Fire resistance
IP20 conforming to IEC 60529
IK04
-20...60 °C
-40...80 °C
960 °C conforming to IEC 60695-2-1
2000 m
Operating altitude
2
Offer Sustainability
Sustainable offer status
RoHS (date code: YYWW)
Green Premium product
Compliant - since 0631 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh
Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile
Product end of life instructions
Available
Product environmental
Need no specific recycling operations
Contractual warranty
Warranty period
18 months
3
©2020 ICPDF网 联系我们和版权申明