LC1D183E7 [SCHNEIDER]
TeSys D contactor - 3P(3 NO) - AC-3 - 440 V 18 A - 48 V AC coil;型号: | LC1D183E7 |
厂家: | SCHNEIDER ELECTRIC |
描述: | TeSys D contactor - 3P(3 NO) - AC-3 - 440 V 18 A - 48 V AC coil |
文件: | 总4页 (文件大小:119K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Product data sheet
LC1D183E7
Characteristics
TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V
18 A - 48 V AC coil
Product availability : Non-Stock - Not normally stocked in distribution facility
Price* : 136.00 USD
Main
Range
TeSys
Product name
TeSys D
Contactor
LC1D
Product or component type
Device short name
Contactor application
Motor control
Resistive load
Utilisation category
AC-4
AC-1
AC-3
Poles description
3P
Power pole contact composition
[Ue] rated operational voltage
3 NO
Power circuit: <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current
Motor power kW
18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
4 kW 220...230 V AC 50/60 Hz AC-3)
7.5 kW 380...400 V AC 50/60 Hz AC-3)
9 kW 415...440 V AC 50/60 Hz AC-3)
10 kW 500 V AC 50/60 Hz AC-3)
10 kW 660...690 V AC 50/60 Hz AC-3)
4 kW 400 V AC 50/60 Hz AC-4)
Motor power HP (UL / CSA)
1 hp 115 V AC 50/60 Hz 1 phase
3 hp 230/240 V AC 50/60 Hz 1 phase
5 hp 200/208 V AC 50/60 Hz 3 phase
5 hp 230/240 V AC 50/60 Hz 3 phase
10 hp 460/480 V AC 50/60 Hz 3 phase
15 hp 575/600 V AC 50/60 Hz 3 phase
Control circuit type
AC 50/60 Hz
[Uc] control circuit voltage
Auxiliary contact composition
48 V AC 50/60 Hz
1 NO + 1 NC
* Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.
Jan 4, 2021
1
[Uimp] rated impulse withstand voltage
Overvoltage category
6 kV conforming to IEC 60947
III
[Ith] conventional free air thermal
current
25 A 140 °F (60 °C) power circuit
10 A (at 60 °C) for signalling circuit
Irms rated making capacity
140 A AC signalling circuit IEC 60947-5-1
250 A DC signalling circuit IEC 60947-5-1
300 A 440 V power circuit IEC 60947
Rated breaking capacity
300 A 440 V power circuit IEC 60947
[Icw] rated short-time withstand current
145 A 104 °F (40 °C) - 10 s power circuit
240 A 104 °F (40 °C) - 1 s power circuit
40 A 104 °F (40 °C) - 10 min power circuit
84 A 104 °F (40 °C) - 1 min power circuit
100 A - 1 s signalling circuit
120 A - 500 ms signalling circuit
140 A - 100 ms signalling circuit
Associated fuse rating
10 A gG signalling circuit IEC 60947-5-1
50 A gG <= 690 V type 1 power circuit
35 A gG <= 690 V type 2 power circuit
Average impedance
2.5 mOhm - Ith 25 A 50 Hz power circuit
[Ui] rated insulation voltage
Power circuit: 690 V conforming to IEC 60947-4-1
Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Electrical durability
1.65 Mcycles 18 A AC-3 <= 440 V
1 Mcycles 32 A AC-1 <= 440 V
Power dissipation per pole
2.5 W AC-1
0.8 W AC-3
Front cover
With
Mounting support
Plate
Rail
Standards
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
Product certifications
DNV
UL
LROS (Lloyds register of shipping)
GOST
CCC
BV
CSA
RINA
GL
Connections - terminals
Control circuit: spring terminals 1 cable(s) 2.5 mm²flexible without cable end
Control circuit: spring terminals 2 cable(s) 2.5 mm²flexible without cable end
Power circuit: spring terminals 1 cable(s) 4 mm²flexible without cable end
Power circuit: spring terminals 2 cable(s) 4 mm²flexible without cable end
Operating time
12...22 ms closing
4...19 ms opening
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
15 Mcycles
Maximum operating rate
3600 cyc/h 60 °C
Complementary
Coil technology
Without built-in suppressor module
Control circuit voltage limits
0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
Inrush power in VA
2
70 VA 60 Hz cos phi 0.75 (at 20 °C)
70 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA
7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
7 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation
2…3 W at 50/60 Hz
Auxiliary contacts type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency
Minimum switching current
Minimum switching voltage
Non-overlap time
25...400 Hz
5 mA signalling circuit
17 V signalling circuit
1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Insulation resistance
Contact compatibility
Compatibility code
> 10 MOhm signalling circuit
M2
LC1D
Environment
IP degree of protection
IP20 front face IEC 60529
Protective treatment
TH IEC 60068-2-30
3
Pollution degree
Ambient air temperature for operation
-40…140 °F (-40…60 °C)
140…158 °F (60…70 °C) with derating
Ambient air temperature for storage
Operating altitude
-76…176 °F (-60…80 °C)
0...9842.52 ft (0...3000 m)
1562 °F (850 °C) IEC 60695-2-1
V1 UL 94
Fire resistance
Flame retardance
Mechanical robustness
Vibrations contactor open2 Gn, 5...300 Hz
Vibrations contactor closed4 Gn, 5...300 Hz
Shocks contactor open: 10 Gn for 11 ms
Shocks contactor closed15 Gn for 11 ms
Height
3.90 in (99 mm)
1.77 in (45 mm)
3.39 in (86 mm)
0.73 lb(US) (0.33 kg)
Width
Depth
Net Weight
Ordering and shipping details
Category
22354 - CTR,TESYS D,OPEN,9-38A AC
Discount Schedule
GTIN
I12
03389110803679
Nbr. of units in pkg.
Package weight(Lbs)
Returnability
1
0.74 lb(US) (0.34 kg)
No
ID
Country of origin
Packing Units
Package 1 Height
Package 1 width
Package 1 Length
0.550 dm
1.100 dm
1.050 dm
Offer Sustainability
Sustainable offer status
California proposition 65
Green Premium product
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony
trioxide, which is known to the State of California to cause cancer. For more information go to
www.P65Warnings.ca.gov
REACh Regulation
REACh Declaration
3
REACh free of SVHC
EU RoHS Directive
Yes
Compliant
EU RoHS Declaration
Toxic heavy metal free
Mercury free
Yes
Yes
Yes
RoHS exemption information
China RoHS Regulation
China RoHS declaration
Pro-active China RoHS declaration (out of China RoHS legal scope)
Environmental Disclosure
Circularity Profile
WEEE
Product Environmental Profile
End of Life Information
The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins.
PVC free
Yes
Contractual warranty
Warranty
18 months