LC1D18SD [SCHNEIDER]

TeSys D IEC contactor, 18 A, 3 P, 10 HP at 480 VAC, nonreversing, 72 VDC coil;
LC1D18SD
型号: LC1D18SD
厂家: SCHNEIDER ELECTRIC    SCHNEIDER ELECTRIC
描述:

TeSys D IEC contactor, 18 A, 3 P, 10 HP at 480 VAC, nonreversing, 72 VDC coil

文件: 总4页 (文件大小:125K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Product data sheet  
LC1D12SD  
Characteristics  
TeSys D IEC contactor, 12 A, 3 P, 7.5 HP at 480  
VAC, nonreversing, 72 VDC coill  
Product availability : Non-Stock - Not normally stocked in distribution facility  
Price* : 149.00 USD  
Main  
Range  
TeSys  
Product name  
TeSys D  
Contactor  
LC1D  
Product or component type  
Device short name  
Contactor application  
Resistive load  
Motor control  
Utilisation category  
AC-1  
AC-3  
AC-4  
Poles description  
3P  
Power pole contact composition  
[Ue] rated operational voltage  
3 NO  
Power circuit: <= 690 V AC 25...400 Hz  
Power circuit <= 300 V DC  
[Ie] rated operational current  
Motor power kW  
25 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit  
12 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit  
3 kW 220...230 V AC 50/60 Hz AC-3)  
5.5 kW 380...400 V AC 50/60 Hz AC-3)  
5.5 kW 415...440 V AC 50/60 Hz AC-3)  
7.5 kW 500 V AC 50/60 Hz AC-3)  
7.5 kW 660...690 V AC 50/60 Hz AC-3)  
3.7 kW 400 V AC 50/60 Hz AC-4)  
Motor power HP (UL / CSA)  
0.5 hp 115 V AC 50/60 Hz 1 phase  
2 hp 230/240 V AC 50/60 Hz 1 phase  
3 hp 200/208 V AC 50/60 Hz 3 phase  
3 hp 230/240 V AC 50/60 Hz 3 phase  
7.5 hp 460/480 V AC 50/60 Hz 3 phase  
10 hp 575/600 V AC 50/60 Hz 3 phase  
Control circuit type  
DC standard  
72 V DC  
[Uc] control circuit voltage  
Auxiliary contact composition  
1 NO + 1 NC  
* Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.  
Jan 4, 2021  
1
[Uimp] rated impulse withstand voltage  
Overvoltage category  
6 kV conforming to IEC 60947  
III  
[Ith] conventional free air thermal  
current  
25 A 140 °F (60 °C) power circuit  
10 A (at 60 °C) for signalling circuit  
Irms rated making capacity  
250 A 440 V power circuit IEC 60947  
140 A AC for signalling circuit conforming to IEC 60947-5-1  
250 A DC for signalling circuit conforming to IEC 60947-5-1  
Rated breaking capacity  
250 A 440 V power circuit IEC 60947  
[Icw] rated short-time withstand current  
105 A 104 °F (40 °C) - 10 s power circuit  
210 A 104 °F (40 °C) - 1 s power circuit  
30 A 104 °F (40 °C) - 10 min power circuit  
61 A 104 °F (40 °C) - 1 min power circuit  
100 A - 1 s signalling circuit  
120 A - 500 ms for signalling circuit  
140 A - 100 ms for signalling circuit  
Associated fuse rating  
10 A gG for signalling circuit conforming to IEC 60947-5-1  
40 A gG <= 690 V type 1 power circuit  
25 A gG <= 690 V type 2 power circuit  
Average impedance  
2.5 mOhm - Ith 25 A 50 Hz power circuit  
[Ui] rated insulation voltage  
Power circuit: 690 V conforming to IEC 60947-4-1  
Power circuit: 600 V CSA certified  
Power circuit: 600 V UL certified  
Signalling circuit: 690 V conforming to IEC 60947-1  
Signalling circuit: 600 V CSA certified  
Signalling circuit: 600 V UL certified  
Electrical durability  
2 Mcycles 12 A AC-3 <= 440 V  
0.8 Mcycles 25 A AC-1 <= 440 V  
Power dissipation per pole  
0.36 W AC-3  
1.56 W AC-1  
Front cover  
With  
Mounting support  
Rail  
Plate  
Standards  
CSA C22.2 No 14  
EN 60947-4-1  
EN 60947-5-1  
IEC 60947-4-1  
IEC 60947-5-1  
UL 508  
Product certifications  
BV  
CCC  
CSA  
RINA  
GL  
GOST  
UL  
DNV  
LROS (Lloyds register of shipping)  
Connections - terminals  
Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end  
Power circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible without cable end  
Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible with cable end  
Power circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible with cable end  
Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)solid without cable end  
Power circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)solid without cable end  
Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end  
Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible without cable end  
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end  
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end  
Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)solid without cable end  
Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)solid without cable end  
Tightening torque  
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm  
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2  
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm  
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2  
Operating time  
53.55...72.45 ms closing  
16...24 ms opening  
Safety reliability level  
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1  
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1  
2
Mechanical durability  
30 Mcycles  
Maximum operating rate  
3600 cyc/h 60 °C  
Complementary  
Coil technology  
With integral suppression device  
Control circuit voltage limits  
0.1...0.25 Uc (-40…70 °C):drop-out DC  
0.7...1.25 Uc (-40…60 °C):operational DC  
1...1.25 Uc 140…158 °F (60…70 °C) operational DC  
Time constant  
28 ms  
Inrush power in W  
5.4 W (at 20 °C)  
5.4 W at 20 °C  
Hold-in power consumption in W  
Auxiliary contacts type  
type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1  
type mirror contact 1 NC conforming to IEC 60947-4-1  
Signalling circuit frequency  
Minimum switching current  
Minimum switching voltage  
Non-overlap time  
25...400 Hz  
5 mA for signalling circuit  
17 V for signalling circuit  
1.5 ms on de-energisation between NC and NO contact  
1.5 ms on energisation between NC and NO contact  
Insulation resistance  
Contact compatibility  
Compatibility code  
> 10 MOhm for signalling circuit  
M4  
LC1D  
Environment  
IP degree of protection  
IP20 front face conforming to IEC 60529  
Protective treatment  
TH IEC 60068-2-30  
3
Pollution degree  
Ambient air temperature for operation  
-40…140 °F (-40…60 °C)  
140…158 °F (60…70 °C) with derating  
Ambient air temperature for storage  
Operating altitude  
-76…176 °F (-60…80 °C)  
0...9842.52 ft (0...3000 m)  
850 °C conforming to IEC 60695-2-1  
V1 conforming to UL 94  
Fire resistance  
Flame retardance  
Mechanical robustness  
Vibrations contactor open: 2 Gn, 5...300 Hz  
Vibrations contactor closed: 4 Gn, 5...300 Hz  
Shocks contactor open: 10 Gn for 11 ms  
Shocks contactor closed: 15 Gn for 11 ms  
Height  
3.03 in (77 mm)  
Width  
1.77 in (45 mm)  
Depth  
3.74 in (95 mm)  
Net Weight  
1.07 lb(US) (0.485 kg)  
Ordering and shipping details  
Category  
22355 - CTR,TESYS D,OPEN,9-38A DC  
Discount Schedule  
GTIN  
I12  
03389110354546  
Nbr. of units in pkg.  
Package weight(Lbs)  
Returnability  
1
1.16 lb(US) (0.53 kg)  
No  
FR  
Country of origin  
Packing Units  
Unit Type of Package 1  
Package 1 Height  
Package 1 width  
PCE  
1.97 in (5 cm)  
3.62 in (9.2 cm)  
3
Package 1 Length  
4.41 in (11.2 cm)  
S02  
Unit Type of Package 2  
Number of Units in Package 2  
Package 2 Weight  
15  
18.16 lb(US) (8.238 kg)  
5.91 in (15 cm)  
11.81 in (30 cm)  
15.75 in (40 cm)  
P06  
Package 2 Height  
Package 2 width  
Package 2 Length  
Unit Type of Package 3  
Number of Units in Package 3  
Package 3 Weight  
240  
313.63 lb(US) (142.26 kg)  
30.31 in (77 cm)  
31.50 in (80 cm)  
23.62 in (60 cm)  
Package 3 Height  
Package 3 width  
Package 3 Length  
Offer Sustainability  
Sustainable offer status  
California proposition 65  
Green Premium product  
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony  
trioxide, which is known to the State of California to cause cancer. For more information go to  
www.P65Warnings.ca.gov  
REACh Regulation  
EU RoHS Directive  
REACh Declaration  
Compliant  
EU RoHS Declaration  
Mercury free  
Yes  
Yes  
RoHS exemption information  
China RoHS Regulation  
China RoHS declaration  
Product out of China RoHS scope. Substance declaration for your information.  
Environmental Disclosure  
Circularity Profile  
WEEE  
Product Environmental Profile  
End of Life Information  
The product must be disposed on European Union markets following specific waste collection and  
never end up in rubbish bins.  
PVC free  
Yes  
Contractual warranty  
Warranty  
18 months  
4

相关型号:

LC1D258BL

TeSys D contactor - 4P(2 NO 2 NC) - AC-1 - 440 V 40 A - 24 V DC coil
SCHNEIDER

LC1D258ED

TeSys D contactor - 4P(2 NO 2 NC) - AC-1 - 440 V 40 A - 48 V DC coil
SCHNEIDER

LC1D25X7

TeSys D contactor - 3P(3 NO) - AC-3 - 440 V 25 A - 600 V AC coil
SCHNEIDER

LC1D326BD

TeSys D contactor - 3P(3 NO) - AC-3 - 440 V 32 A - 24 V DC coil
SCHNEIDER

LC1D326FD

TeSys D contactor - 3P(3 NO) - AC-3 - 440 V 32 A - 110 V DC coil
SCHNEIDER

LC1D326GD

TeSys D contactor - 3P(3 NO) - AC-3 - 440 V 32 A - 125 V DC coil
SCHNEIDER

LC1D326UD

TeSys D contactor - 3P(3 NO) - AC-3 - 440 V 32 A - 250 V DC coil
SCHNEIDER

LC1D386BL

TeSys D contactor - 3P(3 NO) - AC-3 - 440 V 38 A - 24 V DC low cons coil
SCHNEIDER

LC1D386CD

TeSys D contactor - 3P(3 NO) - AC-3 - 440 V 38 A - 36 V DC standard coil
SCHNEIDER

LC1D38B7

TeSys D contactor - 3P(3 NO) - AC-3 - 440 V 38 A - 24 V AC 50/60 Hz coil
SCHNEIDER

LC1D38P7

TeSys D contactor - 3P(3 NO) - AC-3 - 440 V 38 A - 230 V AC 50/60 Hz coil
SCHNEIDER

LC1D38U7

TeSys D contactor - 3P(3 NO) - AC-3 - 440 V 38 A - 240 V AC 50/60 Hz coil
SCHNEIDER