RHN412BA76 [SCHNEIDER]
Power/Signal Relay, 4PDT, Momentary, 24VDC (Coil);![RHN412BA76](http://pdffile.icpdf.com/pdf2/p00308/img/icpdf/RHN412BA76_1853608_icpdf.jpg)
型号: | RHN412BA76 |
厂家: | ![]() |
描述: | Power/Signal Relay, 4PDT, Momentary, 24VDC (Coil) 光电二极管 继电器 |
文件: | 总2页 (文件大小:54K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
![](http://public.icpdf.com/style/img/ads.jpg)
Product data sheet
Characteristics
RHN412BA76
plug-in relay with suppressor - Zelio RHN -
instantaneous - 4 C/O - 24 V DC - 5A
Main
Range of product
Zelio Relay
Product or component
type
Plug-in relay
Device short name
RHN
Contacts type and com-
position
4 C/O
Contacts operation
Instantaneous
Standard
Control circuit voltage
24 V DC
[Ithe] conventional en-
closed thermal current
5 A at <= 40 °C
Status LED
Control type
Without
Manual control
With
Coil interference sup-
pression
Complementary
[Ui] rated insulation voltage
250 V
Operating position
Any position
Minimum switching capacity
150 mVA / 1 V
150 mVA at 10 mA
Contact bounce time
Voltage drop
<= 10 ms
<= 100 V for 3 A at 24 V
30 mOhm at 20 °C
Average resistance
Switching time
1.2...4 ms for de-energisation/energisation
1...4 ms for energisation/de-energisation
Average consumption in W
Control circuit voltage limits
Drop-out voltage threshold
Time constant
1.6 W at 20 °C
0.8...1.1 Uc conforming to IEC 60255
0.1...0.3 Uc
15 ms for closed contact(s)
12 ms for open contact(s)
Mechanical durability
Operating rate
20000000 cycles
<= 6 cyc/mn
Operating time
2...7 ms between de-energisation of coil and closing of NC contact at 20 °C
10...20 ms between energisation of coil and closing of NO contact at 20 °C
CAD overall width
33 mm
43 mm
54 mm
CAD overall height
CAD overall depth
Terminals description ISO n°1
(11-12-14)OC
(21-22-24)OC
(31-32-34)OC
(41-42-44)OC
(A1-A2)CO
Product weight
0.09 kg
May 11, 2016
1
Environment
Standards
BS 4794
IEC 60255
NF C 45-250
VDE 0435
Product certifications
ASE
BV
CSA
EDF
UR
USSR
Protective treatment
TC
Dielectric strength
2500 V
Ambient air temperature for operation
Ambient air temperature for storage
Vibration resistance
-5...40 °C conforming to IEC 60255
-40...70 °C
6 gn (f = 10...55 Hz) conforming to NF C 20-616
6 gn (f = 10...55 Hz) conforming to IEC 60068-2-6
Shock resistance
50 gn for 11 ms conforming to NF C 20-608
2
相关型号:
©2020 ICPDF网 联系我们和版权申明