TMT12-111N-1.2-TZZ02 [SCHURTER]
TMT12-111N-1.2-TZZ02;型号: | TMT12-111N-1.2-TZZ02 |
厂家: | SCHURTER INC. |
描述: | TMT12-111N-1.2-TZZ02 |
文件: | 总7页 (文件大小:152K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
1
CIRCUIT BREAKERS FOR EQUIPMENT
The TM12 circuit breaker for equipment (CBE) is a single pole, ther-
mal-magnetically operated device providing small size, low cost and
reliable trip-free operation on overloads and short circuits within the
maximum breaking capacity. It is intended primarily for the protection
of circuit control functions in sensitive instruments etc. It is not
generally suitable for line protection unless the prospective short cir-
cuit current is less than 200 A at 240 V a.c. (400 A at 28 V d.c.).
TM12 Series
• Thermal magnetic release
• Positively trip-free
• Reset or manual
actuation
Threaded neck and flange mounting types are available each with
optional push on/push off mechanism, shunt terminal and auxiliary
contact. There is also a choice of screw clamp terminals on certain
types.
The well proven mechanism is designed to open the contacts in the
event of overloads. A bimetal strip is heated by the overcurrent and
deflects, thereby releasing the latch mechanism. If the overcurrent is
sufficiently high, the magnetic release will operate and open the
circuit instantaneously. Two characteristics are available. The more
commonly used T characteristic has operating limits between 8-12
times the rated current. The optional F characteristic operates at a
lower current levels of 4-8 times the rated current.
In case of overloads, the contacts will open even if the reset button is
manually held in the closed position. This is known as a trip-free
feature. The contacts open and close with a snap action and the
tripped state is clearly shown by the increased projection of the reset
button. After the opening operation, the reset button has to be fully
depressed, then released, to effect a closing of the contact.
It is impossible to «tease» the contacts by gentle pressure on the
reset button.
Available options
• Fast and slow magnetic tripping characteristics
• Flange type
• Threaded neck type
• Type of actuation: reset or manual ON/OFF (push/push)
• Terminals: quick connect or screw clamp terminals
• Independent auxiliary contact (change-over contact)
• Shunt terminal
• Setting indication on reset button indicates the position
of the contacts
Special features
• Competitive pricing
• Quick connect terminals
• Choice of mounting styles
• Positively trip-free
• Insensitive to shock or vibration
• UL, CSA, VDE and other approvals
Schurter, Inc. Phone 707-778-6311 • Fax 707- 778-6401 • E-mail info@schurterinc.com • Website http://www.schurterinc.com 193
•
1
CIRCUIT BREAKERS FOR EQUIPMENT TM12
Effect of ambient
temperature
Tripping characteristics
TMF + TMT
The unit is calibrated for an ambient tem-
perature of +23°C. To determine the rated
current for a lower or higher ambient
temperature, use a correction factor from
the table below:
[ min ] [ sec ]
10'000
1'000
100
Rated current
60
< 7,0 A
30
20
≥ 7,0 A
+23 °C
10
5
Ambient temp..
1
Ambient
temperature [°C]
Correction factor
10
-5
0
0,87
0,90
0,95
1,00
1,05
1,12
1,20
1,30
1
TMF
TMT
+10
+23
+30
+40
+50
+60
0,1
0,01
0,001
0,0001
1,051,32
2
4
5
8
10
20
50
Example
Multiple of rated current
[ x I
n
Rated current at +23°C
Ambient temperature
Correction factor
5,0 A
+50°C
1,2
Chosen rated current at
+50°C ambient temperature
5,0 A x 1,2 = 6,0 A
Technical data
Main circuit
Rated voltage Ue
See approvals, page 195
See approvals, page 195
AC 240 V; DC 28 V
AC/DC 0,05 – 16 A
Rated current I
n
Conditional short circuit current I
EN 60 934
PC1, AC 240 V
nc
1000 A
Short circuit capacity I
cn
AC 240 V
AC/DC 28 V
200 A
400 A
Auxiliary circuit
Rated voltage Ue
See approvals, page 195
AC 120 V, 240 V; DC 28 V
Rated current I
n
See approvals, page 195
Between live and accessible parts
Other parts
1,0; 2,0; 3,0 A
Class of protection
II
I
194 Schurter, Inc. Phone 707-778-6311 • Fax 707-778-6401 • E-mail info@schurterinc.com • Website http://www.schurterinc.com
•
1
CIRCUIT BREAKERS FOR EQUIPMENT TM12
Technical data (continued)
Degree of protection
Accessible range
Termination range
IP40
IP00
Dielectric strength
Insulation resistance
Endurance
Accessible range
DC 500 V
AC 4000 V
>100 MΩ
Number of cycles at 6 x I (AC)
n
Number of cycles at I
n
R-type
S-type
40
5000
Permissible ambient temperature
Vibration resistance
-5°C to +60°C
10 g
IEC 68-2-6, Test Fc,
1 mm amplitude 5-60 Hz, 60-500 Hz
Shock resistance
Type of actuation
IEC 68-2-6, Test Ea
100 g
• Reset type
• Manual ON/OFF (push/push)
R
S
Type of tripping
Weight
• Thermal-magnetic
• Positively trip-free
TM
approx. 33 g
Approvals
Main circuit
Auxiliary circuit
Rated
Rated
Rated
Rated
Rated
Rated
current range voltage AC
voltage DC
current
voltage AC
voltage DC
UL
1077
0,05 – 16 A
240 V
28 V
3 A
2 A
1 A
1 A
1 A
1 A
1 A
1 A
28 V
28 V
120 V
240 V
240 V
240 V
240 V
240 V
240 V
CSA
C 22,2
0,05 – 16 A
0,05 – 16 A
0,05 – 16 A
0,05 – 16 A
0,05 – 16 A
0,05 – 16 A
240 V
240 V
240 V
240 V
240 V
240 V
28 V
28 V
VDE
EN 60934
SEMKO
NEMKO
DEMKO
SEV
EN 60934
28 V
28 V
Schurter, Inc. Phone 707-778-6311 • Fax 707- 778-6401 • E-mail info@schurterinc.com • Website http://www.schurterinc.com 195
•
1
CIRCUIT BREAKERS FOR EQUIPMENT TM12
Order code
Basic type
TM Single pole thermal magnetic overload protection switch,
positively trip-free
Magnetic release range**
F
T
Fast
Slow
Mounting style
1
Flange type
2
Threaded neck type M10 x 1, with hexagonal- and knurled nut
Actuation type
1
Reset type
2
Manual ON/OFF (push/push)
Terminal type
1
6,3 x 0,8 mm quick connect terminals DIN 46244-A
2
Screw clamp terminals*
* Not available with S-auxiliary contact or N-shunt terminal
Construction variants *
S
N
R
Auxiliary contact
Shunt terminal only for rated currents <7 A
Setting indication on reset button
* (S; N; R; SN; SR; NR; SNR)
Rated current
0,05 0,1 0,15 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0
1,1
2,5
7,5
1,2 1,3
2,8 3,0
8,0 8,5
1,4 1,5 1,6 1,7 1,8 1,9 2,0 2,1 2,3
3,3 3,5 4,0 4,5 5,0 5,5 6,0 6,5 7,0
9,0 9,5 10
11
12
13
14
15
16
Other rated currents by request
** The magnetic tripping range is valid for AC. For DC the stated magnetic currents are
approx. 1,6 x higher.
Accessories
TZZ 02 Protective cover for threaded neck mounted front side IP54
T
M
F
1
2 –
2
1
1
S
N
R
–
0,15
–
T
Z
Z
0
2
Order example
196 Schurter, Inc. Phone 707-778-6311 • Fax 707-778-6401 • E-mail info@schurterinc.com • Website http://www.schurterinc.com
•
1
CIRCUIT BREAKERS FOR EQUIPMENT TM12
Threaded neck type
TMx12-211N
TMx12-211
Maximum torque 1,5 Nm
Maximum torque 1,5 Nm
M 10x1
Ø 5.7
M 10x1
Ø 5.7
8
8
Label
Label
1
3
7 8
2
1
3 7 8
2
36
42±0.2
6.3
36
42±0.2
6.3
11.5
11.5
42
42
TMx12-212
Cut-out
+0.1
8.1
–0.0
1
1
Maximum torque 1,5 Nm
M 10x1
Ø 5.7
8
16
16
without
with
Anti-rotation protection
Label
1
3
7 8
2
42±0.2
M 4
11.5
42
Schurter, Inc. Phone 707-778-6311 • Fax 707- 778-6401 • E-mail info@schurterinc.com • Website http://www.schurterinc.com 197
•
1
CIRCUIT BREAKERS FOR EQUIPMENT TM12
Flange type
TMx12-111
TMx12-111SN
6
4 5
50
50
Ø 11.5
Ø 5.7
Ø 11.5
Ø 5.7
Label
Label
A 6.3
1
3
7 8
2
1
3
7 8
2
36
42±0.2
6.3
11.5
2.5
36
6.3
8.6
11.5
20.2
58
42±0.2
Ø 4.5
58
Ø 4.5
TMx12-112
Installation from rear
Cut-out
5
.
4
1
1
50
Ø 11.5
Ø 5.7
5
.
4
13
13
Label
Installation from front
12
5
.
4
1
3
7 8
2
42±0.2
11.5
M 4
58
Ø 4.5
5
.
4
13
13
198 Schurter, Inc. Phone 707-778-6311 • Fax 707-778-6401 • E-mail info@schurterinc.com • Website http://www.schurterinc.com
•
1
CIRCUIT BREAKERS FOR EQUIPMENT TM12
Schematic diagrams – accessories – colors
Schematic diagrams
TM12-...
1
TM12-...N
1
TM12-...S
1
TM12-...SN
1
54
54
I>
2
I>
2
2
3
6
2
3
6
Accessories
Colors
Black
Setting display R white
Protective transparent cover
Degree of protection IP54
TZZ02
Nickel plated
Black
White label
Ø 16
Nickel plated
Black galvanized
2
1
7 8
2
Schurter, Inc. Phone 707-778-6311 • Fax 707- 778-6401 • E-mail info@schurterinc.com • Website http://www.schurterinc.com 199
•
相关型号:
©2020 ICPDF网 联系我们和版权申明