GLC50-28 [SLPOWER]
Power Supply Module;型号: | GLC50-28 |
厂家: | SL Power Electronics |
描述: | Power Supply Module 输出元件 |
文件: | 总2页 (文件大小:44K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
GLC50 Commercial/GLM50 Medical
50Watt Output Global Performance Switchers
FEATURES:
• Cost-effective power source
• Universal input 90-264Vac
• 2-year warranty
• Compact (4.25" x 2.50" x 1.15"; meets 1U applications)
• Overload and overvoltage protection
• Built-in EMI filter
• Commercial UL, CSA and IEC approvals
• Medical UL2601, CSA22.2 No. 601, IEC601-1, ENB60601
•
marked to LVD
SPECIFICATIONS:
Environmental
AC Input
Designed for 0 to 50°C operation at full rated output power; derate
output current and total output power by 2.5% per °C above 50°C.
See Environmental and Packaging Specifications on next page.
90-264 Vac, 47-63 Hz single phase.
Input Current
Maximum input current at 120 Vac, 60 Hz with full rated output load:
1.5 A
Output Noise
0.5% rms, 1% pk-pk, 20 MHz bandwidth, differential mode.
Measured with noise probe directly across output terminals of the
power supply.
Hold-Up Time
15 ms minimum from loss of ac input at full load, nominal line (115
Vac).
Transient Response
500 µs typical response time for return to within 0.5% of final value
for a 50% load step change. ∆i/∆t<0.2 A/µs. Maximum voltage
deviation is 3.5%. Startup/shutdown overshoot less than 3%.
Output Power
50 W continuous, 60 W peak. Peak ratings are for 60 s maximum
duration, 10% duty cycle. During peak load condition, output
regulation may exceed total regulation limits.
Voltage Adjustment
Built-in potentiometer adjusts V1 ±5%.
Overload Protection
Fully protected against short circuit and output overload. Short
circuit protection is cycling type power limit on outputs 1 & 2;
foldback type on output 3. Recovery after fault is automatic. See
output ratings chart for additional notes or conditions.
Overload Protection
Factory set to begin power limiting at 60 W.
EMI/EMC Compliance
All models include built-in EMI filtering to meet the following
emissions requirements:
Efficiency
70-85% at full rated load, nominal input voltage, depending on
model and load distribution.
EMISPECIFICATIONS
ConductedEmissions
Conducted Emissions Medical
Static Discharge
RF Field Susceptibility
Fast Transients/Bursts
Surge Susceptibility
COMPLIANCELEVEL
EN55022 Class B; FCC Class B
EN55011 Class B; FCC Class B
EN61000-4-2, 6 kV contact, 8 kV air
EN61000-4-3, 3V/meter
Minimum Load
Operating without minimum load will not degrade reliability, but
regulation may be affected. Multiple output models require 20%
minimum load on V1 for proper regulation. Single models require
5% minimum load.
EN61000-4-4, 2 kV, 5 kHz
EN61000-4-5, 1 kV diff., 2 kV com.
Commercial Leakage Current
160 µA 254 Vac @ 60 Hz input (with no deviations).
Turn-on Time
Less than 1 second at 120 Vac, 25°C (inversely proportional to input
voltage and thermistor temperature).
Commercial Safety
All GLC models are approved to UL1950, CSA22.2 No. 234 Level
3, IEC950 and EN60950. Consult factory for approval status.
Input Protection
Internal ac fuse provided. Designed to blow only if a catastrophic
failure occurs in the unit—fuse does not blow on overload or short
circuit.
Medical Leakage Current
100 µA 264 Vac @ 60 Hz input (normal conditions).
Inrush Current
Medical Safety
Inrush is limited by internal thermistors. Inrush at 240 Vac, averaged
over the first ac half-cycle under cold start conditions will not exceed
37 A.
All GLM models are approved to UL2601, CSA22.2 No. 601,
IEC601-1 and EN60601. Consult factory for approval status.
Temperature Coefficient
0.03%/ºC typical on all outputs.
Condor D.C. Power Supplies, Inc./A subsidiary of SL Industries, Inc.
2311 Statham Parkway, Oxnard, CA 93033 • 800-235-5929 • 805-486-4565 • FAX 805-487-8911 • www.condorpower.com
52
GLC50 Commercia/GLM50 Medical 50Watt Multiple Output
Commercial
Model
Medical
Model
Total
Regulation (A)
Output No.
Output
Current
Minimum Load
0.8 A
OVP Setpoint
6.2 ± 0.6 V
Noise P-P
GLC50A
GLC50B
GLC50D
GLC50G
GLM50A
GLM50B
GLM50D
GLM50G
1
2
3
+5.05 V
+12 V
-12 V
4 A
2.5 A
0.2 A
50 mV
120 mV
120 mV
2%
+10%, -5%
3%
1
2
3
+ 5.1 V
+15 V
-15 V
4 A
2.5 A
0.2 A
0.8 A
0.8 A
0.8 A
6.2 ± 0.6 V
6.2 ± 0.6 V
4.2 ± 0.6 V
50 mV
150 mV
150 mV
2%
+10%, -5%
3%
1
2
3
+5.1 V
+24 V
-12 V
4 A
1.5 A
0.2 A
50 mV
240 mV
120 mV
2%
+10%, -5%
3%
1
2
3
+3.3 V
+12 V
-12 V
4 A
2.5 A
0.2 A
33 mV
120 mV
120 mV
2%
+10%, -5%
3%
GLC50-3.3
GLC50-5
GLM50-3.3
GLM50-5
1
1
1
1
1
1
1
3.3 V
5.1 V
12 V
15 V
24 V
28 V
48 V
8 A
0
0
0
0
0
0
0
4.2 ± 0.6 V
6.2 ± 0.6 V
14 ± 1.1 V
18.5 ± 1.5 V
28 ± 2.5 V
34.5 ± 2.8 V
54 ± 3.0 V
33 mV
50 mV
2%
2%
2%
2%
2%
2%
2%
8 A
GLC50-12
GLC50-15
GLC50-24
GLC50-28
GLC50-48
GLM50-12
GLM50-15
GLM50-24
GLM50-28
GLM50-48
4.2 A
3.3 A
2.1 A
1.8 A
1.1 A
120 mV
150 mV
240 mV
280 mV
480 mV
A. Totalregulationisdefinedasthemaximumdeviationfromthenominalvoltageforallsteady-stateconditionsofinitialvoltagesetting, inputlinevoltageandoutputload.
GLC50/GLM50 MECHANICAL SPECIFICATIONS
4.25 [107.95mm]
INPUT J1:
AMP P/N 640445-3, 0.156 CTR 0.045
SQUARE PIN HEADER
4.00 [101.60mm]
0.125
[3.18mm]
PIN 3) AC NEUTRAL
PIN 2) NO PIN
PIN 1) AC LINE
A2
OUTPUT J2:
AMP P/N 640445-6, 0.156 CTR 0.045
SQUARE PIN HEADER
2.50
[63.50mm]
J1
MULTIPLE OUTPUT
PIN 1) OUTPUT #2
PIN 2) OUTPUT #1
PIN 3) OUTPUT #1
PIN 4) COMMON
PIN 5) COMMON
PIN 6) OUTPUT #3
SINGLE OUTPUT
PIN 1-3) OUTPUT
PIN 4-6) RETURN
T2
2.25
[57.15mm]
F1
C4
MATING CONNECTORS: AMP P/N
HOUSING
INPUT
OUTPUT
644329-3
644329-6
0.125
[3.18mm]
NOTE: 5A MAXIMUM RECOMMENDED
CURRENT PER CONNECTOR PIN
1.25" [31.75mm]
MOUNTING HOLE
WEIGHT: 5 OZ. [0.142 KG]
0.138 TYP.
[3.51mm]
TOLERANCES: X.XX=0.030 [0.76mm]
X.XXX=0.010 [0.25mm]
MAX. LEAD PROTRUSION 0.10" [2.54mm]
MAX. COMPONENT HEIGHT 1.15" [29.21mm]
Environmental
Operating
Non-operating
Specification
Temperature (A)
Humidity (A)
Shock (B)
See individual specs
0 to 95% RH
-40 to +85ºC
0 to 95% RH
40 gpk
A. Units should be allowed to warm up/operate under non-condensing conditions
before application of power.
B. Random vibration—10 to 2000Hz, 6dB/octave roll-off from 350 to 2000Hz, 3
orthogonal axes. Tested for 10 min./axis operating and 1 hr./axis non-operating.
C. Shock testing—half-sinusoidal, 10 ± 3 ms duration, ± direction, 3 orthogonal axes,
total 6 shocks.
20 gpk
Altitude
-500 to 10,000 ft
1.5 grms, 0.003 g2/Hz
-500 to 40,000 ft
5 grms, 0.026 g2/Hz
Vibration (C)
Condor D.C. Power Supplies, Inc./A subsidiary of SL Industries, Inc.
2311 Statham Parkway, Oxnard, CA 93033 • 800-235-5929 • 805-486-4565 • FAX 805-487-8911 • www.condorpower.com
53
相关型号: