GPM41-24G [SLPOWER]
AC-DC Regulated Power Supply Module, 40W,;型号: | GPM41-24G |
厂家: | SL Power Electronics |
描述: | AC-DC Regulated Power Supply Module, 40W, 输出元件 |
文件: | 总2页 (文件大小:216K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
GPC41 Commercial/GPM41 Medical
41 WATT GLOBAL PERFORMANCE SWITCHERS
GLOBAL PERFORMANCE SWITCHERS
Summary:
D C P o w e r S u p p l i e s
• Ultra small (2.00” x 4.00” x 1.50”)
• Wide-range ac input 85-264 Vac
• 2-year warranty
• Conducted EMI exceeds FCC Class B and CISPR
22 Class B (Commercial models) and CISPR 11
Class B (Medical models)
• Commercial Approved to UL1950, IEC950,
EN60950 and CSA22.2-234 L3
• Medical Approved to UL2601-1, IEC601-1 and
CSA22.2 No. 601
• RoHS Compliant (G suffix)
•
marked to LVD
SPECIFICATIONS
Ac Input
Output Noise
85-264 Vac, 47-63 Hz single phase.
0.5% rms, 1% pk-pk, 20 MHz bandwidth, differential mode. Measured with noise
probe directly across output terminals of the power supply.
Input Current
Maximum input current at 120 Vac, 60 Hz with full rated output load: 1.3 A
Transient Response
Hold-Up Time
Main output—500 μs typical response time for return to within 0.5% of final value
for a 50% load step change. ∆i/ ∆t<0.2 A/μs. Maximum voltage deviation is 3.5%.
Startup/ shutdown overshoot less than 3%.
20 ms minimum from loss of ac input at full load, nominal line (115 Vac).
Output Power
40 W continuous, 50 W peak. Peak ratings are for 60 s maximum duration,
10% duty cycle. During peak load condition, output regulation may exceed
total regulation limits.
EMI/EMC Compliance
All models include built-in EMI filtering to meet the
following emissions requirements:
Overload Protection
Fully protected against short circuit and output overload.
Short circuit protection is cycling type power limit.
EMI SPECIFICATIONS
COMPLIANCE LEVEL
Recovery after fault is automatic. Factory set to begin power limiting at ap-
proximately 55 W. See output ratings chart for additional notes or conditions.
Conducted Emissions GPC41
Conducted Emissions GPM41
Static Discharge
RF Field Susceptibility
Fast Transients/Bursts
Surge Susceptibility
EN55022 Class B; FCC Class B
EN55011 Class B; FCC Class B
EN61000-4-2, 6 kV contact, 8 kV air
EN61000-4-3, 3 V/meter
EN61000-4-4, 2 kV, 5 kH
EN61000-4-5, 1 kV diff., 2 kV com.
Overvoltage Protection.
See output ratings chart.
Efficiency
69-77% at full rated load, nominal input voltage, depending
on model.
Commercial Leakage Current
60 μA single fault; 60 Hz input.
Turn-on Time
Less than 1 s at 120 Vac, 25°C (inversely proportional to input voltage).
Commercial Safety
Input Protection
Approved to UL1950, CSA22.2 No. 234 Level 3, IEC950 and EN60950. UL file
#E135803 commercial; CSA #LR46516 all models. All dc outputs are SELV under
normal and single fault conditions.
Requires external ac line fusing. A 2.5 A, 250 V rated fuse with I2t > 20 is
recommended.
Inrush Current
Inrush is limited by internal thermistor. Inrush at 240 Vac under cold start
conditions will not exceed 34 A.
Medical Leakage Current
35 μA , 254 Vac 60 Hz input.
Temperature Coefficient
0.03%/°C typical on all outputs.
Medical Safety
Approved to UL2601, CSA22.2 No. 601 Level 3, IEC601.
UL file E116994; CSA #LR46516. The output(s) are intended for safety earthed Sig-
nal Output and Intermediate Circuits only. The output(s) are not acceptable for
patient connection without additional isolation. All dc outputs are SELV under
normal and single fault conditions.
Environmental
Designed for 0 to 50°C operation at full rated output
power; derate output current and total output power by
2.5% per °C above 50°C. See Environmental and
Packaging Specifications on next page.
All specifications are typical at nominal input, full load at 25OC unless otherwise stated
Commercial
Model
Medical
Model
Minimum
Load
Load
Regulation
Initial Setpoint
Tolerance
OVP
Setpoint
Ripple and
Noise
Output
5.1 V
12 V
Current
6.0 A
3.3 A
2.7 A
1.7 A
1.4 A
GPC41-5
GPM41-5
0.15
0.03
0.03
0.01
0.01
0.75%
0.75%
0.75%
0.75%
0.75%
2%
2%
2%
2%
2%
6.2 0.6 V
14 1.0 V
19 1.5 V
28 2.5 V
34 2.8 V
1%
1%
1%
1%
1%
GPC41-12
GPC41-15
GPC41-24
GPC41-28
GPM41-12
GPM41-15
GPM41-24
15 V
24 V
28 V
Note: Add “G”suffix to model number for RoHS compliant model.
GPC41/GPM41 MECHANICAL SPECIFICATIONS
3
3
ENVIRONMENTAL SPECIFICATIONS
OPERATING
See individual specs.
NON-OPERATING
-40 to +85°C
Temperature (A)
Humidity (A)
Shock (B)
0 to 95% RH
0 to 95% RH
20 gpk
40 gpk
Altitude
-500 to 10,000 ft
-500 to 40,000 ft
Vibration (C)
1.5 g rms’0.003 g2/Hz
5 g rms’0.026 g2/Hz
A. Units should be allowed to warm up/operate under non-condensing conditions before application of power. Derate output
current and total output power by 2.5% per °C above 50°C. For operation in a confined space, moving air may be required. Under
all conditions, the cooling vs. load profile should be such that heat sinks and/or heatsink temperatures do not exceed 90 °C for
extended periods.
B. Shock testing—half-sinusoidal, 10 3 ms duration, direction, 3 orthogonal axes, total 6 shocks.
C. Random vibration—10 to 2000Hz, 6dB/octave roll-off from 350 to 2000Hz, 3 orthogonal axes. Tested for 10 min./axis operating
and 1 hr./axis non-operating.
SL Power Electronics Corp., 6050 King Drive, Bldg.A, Ventura, CA, 93003, USA. Phone:(805) 486 4565 Fax:(805) 487 8911 Email: info@slpower.com. Rev. 4/08.
Data Sheet © 2008 SL Power Electronics Corp. The information and specifications contained in this data sheet are believed to be correct at time of publication.
However, SL Power accepts no responsibility for consequences arising from reproduction errors or inaccuracies. Specifications are subject to change without notice.
相关型号:
SI9130DB
5- and 3.3-V Step-Down Synchronous ConvertersWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135LG-T1-E3
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9135_11
SMBus Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9136_11
Multi-Output Power-Supply ControllerWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130CG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130LG-T1-E3
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9130_11
Pin-Programmable Dual Controller - Portable PCsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137DB
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9137LG
Multi-Output, Sequence Selectable Power-Supply Controller for Mobile ApplicationsWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
SI9122E
500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification DriversWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY
©2020 ICPDF网 联系我们和版权申明