Multi-Voltage  
Conventional Relays  
System Sensor’s multi-voltage conventional relays  
are used for high-current switching applications such  
as fan and damper assembly control, door control,  
air handling unit controls, and other types of system  
interfacing.  
Features  
• Multi-voltage operation  
The R-10T, R-20T, R-14T, and the R-24T models are multi-  
voltage relays with terminal strip field wiring connections, mounting  
track, and hardware. The R-10T is a single FORM–C (SPDT) relay with  
a red activation LED, and the R-14T is a four-gang 1 FORM–C (SPDT)  
relay with four red activation LEDs. The R-20T is a single 2 FORM–C  
(DPDT) relay with a red activation LED, and the R-24T is a four-gang 2  
FORM–C (DPDT) relay with four red activation LEDs.  
• Activation LEDs  
• Easy and flexible installation  
• Reliable and robust design  
• Multipurpose field installations  
• Multi-voltage relays with terminal strip field wiring connections,  
mounting track, and hardware for R-10T/20T and R-14T/24T  
The R-10E/R-20E and R-14E/R-24E are similar to the T-series  
track mount relays, but they are mounted into a steel enclosure. The  
enclosure has a removable front cover that provides easy access and  
an LED viewing hole on the top of the cover.  
• Removable front cover on steel enclosure for R-10E/R-20E and R-  
14/R-24E, which mount inside the enclosure  
• LED viewing hole on top of the steel enclosure’s cover  
• Extra pair of wires for redundant power input on PR-3  
PR-1/PR-2/PR-3 are epoxy encapsulated multi-voltage relays. They  
are single-pole double-throw relays that use a red LED as a visible  
indication of relay coil energization. PR–3 is  
identical to PR–2, except it has an extra pair of wires for redundant  
power input.  
• Terminal strip field wiring connections, mounting track, and  
hardware  
Model EOLR-1 is an epoxy encapsulated, single-pole single-throw,  
normally open relay that can be used as an end of line device in fire  
alarm systems, e.g. to supervise power supplies.  
Agency Listings  
Multi-Voltage Conventional Relay Specifications  
Specifications: R-10T/R-14T/R-20T/R-24T  
Specifications: PR-1  
Operating Voltage  
Operating Current  
18 – 35 VDC, 18 – 35 VAC, 115 VAC, 230 VAC  
Operating Voltage  
Operating Current  
Operating Temperature  
Humidity Range  
Wire Length  
18 – 35 VDC, 18 – 35 VAC, 120 VAC  
15 mA DC max. @ 24 VDC, 24 VAC, 120 VAC  
–40°F to 158°F (–40°C to 70°C)  
10 – 93% RH  
20 mA DC max. @ 24 VDC, 24 VAC, 115 VAC,  
230 VAC (R-10T/R-14T)  
40 mA DC max. @ 24 VDC, 24 VAC, 115 VAC,  
230 VAC (R-20T/R-24T)  
8˝ minimum  
Operating Temperature  
Humidity Range  
Dimensions  
–40°F to 158°F (–40°C to 70°C)  
10% – 93% non-condensing  
Dimensions  
0.87˝H × 2.01˝W × 1.42˝D  
Contact Ratings  
24 VDC: 7 A with L/R = 5 mS  
120 VAC: 7 A max. (0.35 PF)  
250 VAC: 10 A resistive  
R-10T/R-20T: 2.5˝L × 3.35˝W × 1.2˝H  
R-14T/R-24T: 10˝L × 3.35˝W × 1.2˝H  
Contact Ratings  
24 VDC: 7 A with L/R = 5 mS  
120 VAC: 10 A  
120 VAC: 1/6 HP  
230 VAC: 7 A  
30 VDC: 10 A resistive  
Specifications: PR-2/PR-3  
Operating Voltage  
Operating Current  
Operating Temperature  
Humidity Range  
Wire Length  
10 to 40 VDC  
30 mA DC max.  
Specifications: R-10E/R-14E/ R-20E/R-24E  
–40°F to 158°F (–40°C to 70°C)  
10 – 93% RH  
Operating Voltage  
Operating Current  
18 – 35 VDC, 18 – 35 VAC, 115 VAC, 230 VAC  
20 mA DC max. @ 24 VDC, 24 VAC, 115 VAC,  
230 VAC (R-10E/R-14E)  
8˝ minimum  
40 mA DC max. @ 24 VDC, 24 VAC, 115 VAC,  
230 VAC (R-20E/R-24E)  
Dimensions  
0.91˝H × 1.65˝W × 1.22˝D  
Contact Ratings  
120 VAC: 10 A max. (resistive load)  
120 VAC: 7 A max. (0.35 PF)  
250 VAC: 10 A max. (resistive load)  
30 VDC: 10 A max. (resistive load)  
Operating Temperature  
Humidity Range  
Dimensions  
–40°F to 158°F (–40°C to 70°C)  
10% – 93% non-condensing  
R-10E/R-20E: 5.1˝L × 3.75˝W × 2.5˝H  
R-14E/R-24E: 11˝L × 5.3˝W × 2.5˝H  
Specifications: EOLR-1  
Operating Voltage  
Operating Current  
Operating Temperature  
Humidity Range  
9 to 40 VDC  
Contact Ratings  
24 VDC: 7 A with L/R = 5 mS  
120 VAC: 10 A  
120 VAC: 1/6 HP  
230 VAC: 7 A  
20 mA DC max.  
–22°F to 140°F (–30°C to 60°C)  
10 – 93% RH  
Wire Length  
8˝ minimum  
Contact Ratings  
120 VAC: 0.5 A max. (resistive load)  
30 VDC: 3 A max. (resistive load)  
PR–1  
E0LR–1  
PR–3  
R-10E & R-20E Enclosure  
PR–2  
R–10T  
R–14T  
R-14E & R-24E Enclosure  
©2007 System Sensor.  
3825 Ohio Avenue • St. Charles, IL 60174  
Phone: 800-SENSOR2 • Fax: 630-377-6495  
Product specifications subject to change without notice. Visit systemsensor.com for  
current product information, including the latest version of this data sheet.  
A05-0372-005 • 3/07 • #1782  

相关型号:

PR-21675

NO HOLES IN TERMINALS TERMINALS ARE PLATED SWITCH MATERIALS WILL WITHSTAND TEMPERATURE OF 300
HONEYWELL

PR-21SR/80427.35-2.5

TRANSMITTER PIEZORESITIV
ETC

PR-3

Multi-Voltage Conventional Relays
SYSTEMSENSOR

PR-30

Photo-reflector
CITIZEN

PR-30_12

Photo-reflector
CITIZEN

PR-40

Photo-reflector
CITIZEN

PR-40_12

Photo-reflector
CITIZEN

PR-JJFREQ1

Parallel - Fundamental Quartz Crystal, 12MHz Min, 40MHz Max
MTRONPTI

PR-JJFREQ2

Parallel - 3Rd Overtone Quartz Crystal, 40MHz Min, 100MHz Max
MTRONPTI

PR-JPFREQ1

Parallel - Fundamental Quartz Crystal, 12MHz Min, 40MHz Max
MTRONPTI

PR-JPFREQ2

Parallel - 3Rd Overtone Quartz Crystal, 40MHz Min, 100MHz Max
MTRONPTI

PR-MJFREQ2

Parallel - 3Rd Overtone Quartz Crystal, 40MHz Min, 100MHz Max
MTRONPTI