Catalog 1308242  
Issued 3-03 (PDF Rev. 10-07)  
AGASTAT  
7000 series  
Industrial Electropneumatic  
Timing Relay  
File E15631  
File LR29186  
Note:7032 types and certain models with accessories are not agency approved.  
Users should thoroughly review the technical data before selecting a product  
part number. It is recommended that users also seek out the pertinent  
approvals files of the agencies/laboratories and review them to confirm the  
product meets the requirements for a given application.  
Consult factory for ordering information.  
Design Features  
On-delay model 7012 (delay on pickup)  
• Available in on-delay, true off-delay, and on/off-delay.  
Applying continuous voltage to the coil  
(L1-L2) starts a time delay lasting for  
the preset time. During this period the  
normally closed contacts (3-5 and 4-6)  
remain closed. At the end of the delay  
period the normally closed contacts  
break and the normally open contacts  
(1-5 and 2-6) make. The contacts re-  
main in this transferred position until  
the coil is deenergized, at which time  
the switch instantaneously returns to  
its original position.  
De-energizing the coil, either during  
or after the delay period, will recycle  
the unit within 50 msec.  
It will then provide a full delay period  
upon re-energization, regardless of  
how often the coil voltage is interrupt-  
ed before the unit has been permitted  
to "time-out" to its full delay setting.  
Timing from 0.1 seconds to 60 minutes, in linear increments.  
• Oversize time-calibrated adjustment knobs, serrated with high-resolution  
markings visible from all angles makes the timer easy to set timers.  
• Inherent transient immunity.  
• Standard voltages from 6-550VAC and 12-550VDC (special voltages available.)  
• Available in 2-pole or 4-pole models.  
• Numerous enclosure options: explosion proof, dust tight, watertight,  
hermetically-sealed, NEMA 1.  
• Auxiliary timed and instantaneous switches can be added for greater switching  
flexibility.  
• Many mounting options: Surface mount, Panel mount, Octal plug-in mounting.  
• Options: quick-connect terminals, dial stops, and transient protection module.  
• Easy-to-reach screw terminals, all on the face of the unit, clearly identified.  
• Modular assembly - timing head, coil assembly and switchblock are all  
individual modules, with switches field-replaceable.  
Design & Construction  
There are three main components of Series 7000 Timing Relays:  
Calibrated Timing Head uses no needle valve, recirculates air under  
controlled pressure through a variable orifice to provide linearly adjustable  
timing. Patented design provides instant recycling, easy adjustment and long  
service life under severe operating conditions.  
Off-delay model 7022 (delay on dropout)  
Applying voltage to the coil (for at  
least 50 msec) will instantaneously  
transfer the switch, breaking the nor-  
mally closed contacts (1-5 and 2-6),  
and making the normally open  
contacts (3-5 and 4-6). Contacts  
remain in this transferred position as  
long as the coil is energized. The  
time delay begins immediately upon  
de-energization. At the end of the de-  
lay period the switch returns to its  
normal position.  
Re-energizing the coil during the  
delay period will immediately return  
the timing mechanism to a point  
where it will provide a full delay  
period upon subsequent de-  
Precision-Wound Potted Coil module supplies the initial motive force  
with minimum current drain. Total sealing without external leads eliminates  
moisture problems, gives maximum insulation value.  
Snap-Action Switch Assembly  
- custom-designed over-center  
mechanism provides greater contact pressure up to transfer time for  
positive, no flutter action. Standard switches are DPDT arrangement, with  
flexible beryllium copper blades and silver-cadmium oxide contacts. Special  
"timing-duty" design assures positive wiping action, sustained contact pres-  
sure and greater heat dissipation during long delay periods.  
Each of these subassemblies forms a self-contained module which is  
then assembled at the factory with the other two to afford a wide choice of  
operating types, coil voltages, and timing ranges.  
The squared design with front terminals and rear mounting permits the  
grouping of Series 7000 units side-by-side in minimum panel space.  
Auxiliary switches may be added in the base of the unit, without affecting  
the overall width or depth.  
energization. The switch remains in  
the transferred position.  
Operation  
Two basic operating types are available.  
To increase the versatility of the basic timer models, auxiliary switches may  
be added to either on-delay or off-delay types. They switch additional circuits,  
provide two-step timing action, or furnish electrical interlock for sustained coil  
energization from a momentary impulse, depending on the type selected and  
its adjustment. Because of their simple attachment and adjustment features,  
they can be installed at the factory or in the field, by any competent mechanic.  
All auxiliary switches are SPDT with UL listings of 10A @ 125, 250, or 480  
VAC. A maximum of one Code T or two Code L auxiliary switches may be  
added to each relay. The L or LL switch is available with on-delay relays only.  
The T switch is available with both the on-delay and off-delay relays.  
Auxiliary Switch Options for On-Delay  
“On-Delay” models provide a delay period on energization, at the end of  
which the switch transfers the load from one set of contacts to another. De-  
energizing the unit during the delay period immediately recycles the unit,  
readying it for another full delay period on re-energization.  
In "Off-Delay" models the switch transfers the load immediately upon  
energization, and the delay period does not begin until the unit is de-  
energized. At the end of the delay period the switch returns to its original po-  
sition. Re-energizing the unit during the delay period immediately resets the  
timing, readying it for another full delay period on de-energization. No power  
is required during the timing period.  
In addition to these basic operating types, "Double-Head" models offer  
sequential delays on pull-in and drop-out in one unit. With the addition of  
auxiliary switches the basic models provide two-step timing, pulse actuation  
for interlock circuits, or added circuit capacity.  
Instant Transfer (Auxiliary Switch Code L,  
maximum of 2 per relay.)  
1. Energizing coil begins time delay and transfers auxiliary switch.  
2. Main switch transfers after total preset delay.  
3. De-energizing coil resets both switches instantly.  
Auxiliary switch is nonadjustable.  
NOTE: Seismic & radiation tested E7000 models are available.  
Consult factory for detailed information.  
Two-Step Timing (Auxiliary Switch Code T,  
maximum of 1 per relay.)  
Dimensions are shown for  
reference purposes only.  
Dimensions are in inches over  
(millimeters) unless otherwise  
specified.  
Specifications and availability  
subject to change.  
www.tycoelectronics.com  
Technical support:  
Refer to inside back cover.  
1248  
Catalog 1308242  
Issued 3-03 (PDF Rev. 10-07)  
AGASTAT  
Auxiliary switch options  
To increase the versatility of the basic timer models, auxiliary switches may  
be added to either on-delay or off-delay types. They switch additional circuits,  
provide two-step timing action, or furnish electrical interlock for sustained coil  
energization from a momentary impulse, depending on the type selected and  
its adjustment. Because of their simple attachment and adjustment features,  
they can be installed at the factory or in the field, by any competent mechanic.  
All auxiliary switches are SPDT with UL listings of 10A @ 125, 250, or 480 VAC.  
A maximum of one Code T or two Code L auxiliary switches may be added to  
each relay. The L or LL switch is available with on-delay relays only. The T  
switch is available with both the on-delay and off-delay relays.  
Auxiliary Switch Options for On-Delay  
Instant Transfer (Auxiliary Switch Code L, maximum of 2 per relay.)  
1. Energizing coil begins time delay and transfers auxiliary switch.  
2. Main switch transfers after total preset delay.  
3. De-energizing coil resets both switches instantly.  
Auxiliary switch is nonadjustable.  
4. De-energizing coil resets both switches instantly. First delay is  
independently adjustable, up to 30% of overall delay.  
(Recommended maximum 100 seconds.)  
Auxiliary Switch Options for Off-Delay  
In these models the same auxiliary switch provides either two-step timing or  
instant transfer action, depending on the adjustment of the actuator.  
Two-Step Timing (Auxiliary Switch Code T, maximum of 1 per relay.)  
1. Energizing coil transfers main and auxiliary switches instantly.  
2. De-energizing coil begins time delay.  
3. After first delay auxiliary switch transfers.  
4. Main switch transfers after total preset delay. First delay is independently  
adjustable, up to 30% of overall delay. (Recommended maximum 100 sec-  
onds.)  
Instant Transfer (Auxiliary Switch Code L, maximum of 1 per relay.)  
1. Energizing coil transfers main and auxiliary switches instantly.  
2. De-energizing coil resets auxiliary switch and begins time delay.  
3. Main switch transfers after total preset delay.  
Auxiliary switch is factory adjusted to give instant transfer operation, but may  
be easily adjusted in the field to provide two-step timing.  
Two-Step Timing (Auxiliary Switch Code T, maximum of 1 per relay.)  
1. Energizing coil begins time delay.  
2. After first delay auxiliary switch transfers.  
3. Main switch transfers after total preset delay.  
On-delay, off-delay model 7032 (double head)  
The Double Head model provides delayed switch transfer on  
energization of its coil, followed by delayed resetting upon coil de-  
energization. Each delay period is independently adjustable.  
In new circuit designs or the improvement of existing controls now  
using two or more conventional timers, the Double Head unit offers distinct  
advantages.  
Its compact design saves precious panel space, while the simplified  
wiring reduces costly interconnection.  
Four pole model 7014. 7024  
With the addition of an extra switch block at the bottom of the basic unit,  
this version of the Series 7000 offers four pole switch capacity with simul-  
taneous timing or two-step timing. The two-step operation is achieved by  
factory adjustment to your specifications.  
For two-step operation, a maximum timing ratio between upper and  
lower switches of 3:2 is recommended. Once adjusted at the factory, this  
ratio remains constant regardless of changes in dial settings. (Ex: If upper  
switch transfer is set on dial at 60 sec., minimum time on lower switch  
should be 40 sec.)  
This Series 7000 unit offers many of the performance features found in  
basic models - voltage ranges, timing and switch capacities are virtually iden-  
tical.  
Four pole models add approximately 1-1/4" to the maximum height of the  
basic model, approximately 1/8" to the depth. They are designed for vertical  
operation only.  
Surge/transient protection option  
Features  
The Surge/Transient Protection Option protects electronic control circuits from  
transients and surges which are generated when the timer coil is activated.  
Built with a minimum of moving parts, the unit provides a fast response to rap-  
idly rising voltage transients. The accurate, precision-made device is not polari-  
ty sensitive and permits the user to initiate, delay, sequence and program  
equipment actions over a wide range of applications under the most severe  
operating conditions.  
It consists of a specially modified coil case, varistor, varistor cover, terminal  
extensions and cup washers so that normal terminations can be used. The  
varistor will not affect the operating characteristics of the 7000 Timer. The  
varistor has bilateral and symmetrical voltage and current characteristics and  
therefore can be used in place of the back-to-back zener diodes. This charac-  
teristic also means that the coil will not be polarity sensitive.  
• Protect electronic control circuits  
from voltage transients generated  
by the timer coil.  
• Fast response to the rapidly rising  
back E.M.F.  
• High performance clamping voltage  
characteristics.  
• UL recognized, (except varistor and  
coil together).  
Timer NOT polarity sensitive.  
Transient Suppressor  
Option "V"  
Dimensions are shown for  
reference purposes only.  
Dimensions are in inches over  
(millimeters) unless otherwise  
specified.  
Specifications and availability  
subject to change.  
www.tycoelectronics.com  
Technical support:  
Refer to inside back cover.  
1249  
Catalog 1308242  
Issued 3-03 (PDF Rev. 10-07)  
AGASTAT  
Timing Specifications (All values shown are at nominal voltage and 25°C unless otherwise specified).  
Operating Modes:  
Minimum operating voltages are based on vertically mounted 7012 units.  
Model 7012/7014: On-delay (delay on pick-up).  
7012 horizontally mounted or 7022 vertically or horizontally mounted units  
will operate satisfactorily at minimum voltages approximately 5% lower than  
those listed.  
Model 7022/7024: Off-delay (delay on drop-out).  
Model 7032: On-delay, off-delay (double head).  
Timing Adjustment: Timing is set by simply turning the dial to the desired  
time value. In the zone of approximately 25° separating the high and low  
end of timing ranges A,D,E, and K, instantaneous operation (no time delay)  
will occur. All other ranges produce an infinite time delay when the dial is  
set in this zone.  
AC units drop out at approximately 50% of rated voltage. DC units drop out  
at approximately 10% of rated voltage.  
All units may be operated on intermittent duty cycles at voltages 10% above  
the listed maximums (intermittent duty - maximum 50% duty cycle and 30  
minutes "on" time.)  
Models 7014 and 7032 are available with letter-calibrated dials only. The  
upper end of the time ranges in these models may be twice the values  
shown.  
Surge/Transient Protection Option Characteristics (DC Timers Only)  
Coil Voltage  
Nominal (DC)  
Max Excess  
Energy Capacity (Joule)  
Max De-energization  
Transient Voltage  
Linear Timing Ranges:  
Models 7012,  
7022, 7024  
Models 7014,  
7032  
Code  
A
B
C
D
E
F
H
I
.1 to 1 Sec.  
.2 to 2 Sec.  
.7 to 7 Sec.  
2 to 20 Sec.  
10 to 100 Sec.  
30 to 300 Sec.  
1.5 to 15 Min.  
3 to 30 Min.  
Not Avail.  
12 V  
24 V  
28 V  
32 V  
48 V  
60 V  
96 V  
110 V  
125 V  
220 V  
250 V  
0.4 J  
1.8 J  
1.8 J  
2.5 J  
3.57 J  
6 J  
10 J  
10 J  
10 J  
17 J  
17 J  
48 V  
.5 to 5 Sec.  
93 V  
1.5 to 15 Sec  
5 to 50 Sec.  
20 to 200 Sec.  
1 to 10 Min.  
3 to 30 Min.  
6 to 60 Min.  
3 to 120 Cyc.  
1 to 300 Sec.  
93 V  
135 V  
145 V  
250 V  
340 V  
340 V  
340 V  
366 V  
366 V  
J
K
Not Avail.  
Not Avail.  
Repeat Accuracy:  
For delays of 200 seconds or less:  
7012*, 7022, 7024:  
7014*:  
7032:  
+5%  
+10%  
+15%  
Surge Life  
Applied 100,000 times continuously with the interval of 10 seconds at room  
temperature. Below 68 VAC: 12A; Above 68 VAC: 35A  
Temperature Range  
For delays greater than 200 seconds: 7012*, 7022, 7014*, 7024: +10%  
7032: +15%  
* The first time delay afforded by Model 7012 with H (3 to 30 min.) and I (6  
to 60 min.) time ranges or Model 7014 with H time range will be approx.  
15% longer than subsequent delays due to coil temperature rise.  
Reset Time: 50 msec. (except model 7032)  
Operating: -22°F to +167°F (-30°C to + 75°C)  
Storage: -40°F to +167°F (-40°C to +75°C)  
Output/Life Contact Ratings: Contact Capacity in Amps (Resistive Load)  
Contact  
Min. 100,000 Min. 1,000,000  
Relay Release Time: 50 msec. for on-delay models (7012/7014)  
Relay Operate Time: 50 msec. for off-delay models (7022/7024)  
Voltage  
Operations  
15.0  
Operations  
7.0  
30 VDC  
110 VDC  
120 V 60Hz  
240 V 60Hz  
480 V 60Hz  
1.0  
0.5  
20.0  
20.0  
15.0  
15.0  
Operating Voltage Coil Data (for DPDT)  
12.0  
10.0  
Operating*  
Voltage  
Range  
Operating  
Voltage  
Range  
10 Amps Resistive, 240 VAC  
Coil  
Code  
Rated  
Rated  
Voltage  
1/4 Horsepower, 120 VAC/240VAC (per pole)  
Part # Letter Voltage  
15 Amps 30 VDC (per pole)  
@ 60Hz  
@50Hz  
5 Amps, General Purpose, 600VAC (per pole)  
7000  
AC  
A
B
C
D
E
F
G
H
I
120  
240  
480  
550  
24  
102-132  
204-264  
408-528  
468-605  
20.5-26.5  
110  
220  
93.5-121  
187-242  
Dielectric: Withstands 1500 volts RMS 60Hz between terminals and  
ground. 1,000 volts RMS 60 Hz between non-connected terminals. For  
dielectric specification on hermetically sealed models consult factory.  
Insulation Resistance: 500 Megohms with 500VDC applied.  
Temperature Range: Operating: -20°F to +165°F (-29°C to 74°C)  
Storage: -67°F to +165°F (-55°C to 74°C)  
Temperature Variation: Using a fixed time delay which was set and  
measured when the ambient temperature was 77°F (25°C), the maximum  
observed shift in the average of three consecutive time delays was -20% at  
-20°F (-29°C) and +20% at 165°F (74°C).  
Mounting/Terminals: Normal mounting of the basic unit is in a vertical  
position, from the back of the panel. A front mounting bracket is also  
supplied with each basic unit, for installation from the front of the panel.  
All units are calibrated for vertical operation. Basic models (7012, 7022)  
may also be horizontally mounted, and will be adjusted accordingly when  
Accessory Y1 is specified in your order.  
Standard screw terminals (8-32 truss head screws supplied) are located  
on the front of the unit, with permanent schematic markings. Barrier  
isolation is designed to accommodate spade or ring tongue terminals, with  
spacing to meet all industrial control specifications.  
The basic Series 7000 may also be panel mounted with the addition of a  
panelmount kit that includes all necessary hardware and faceplate. This  
offers the convenience of "out-front" adjustment, with large calibrated dial  
skirt knob. The faceplate and knob blend with advanced equipment and  
console designs, while the body of the unit and its wiring are protected  
behind the panel.  
Other mounting options include plug-in styles and special configurations  
to meet unusual installation requirements. Contact factory for details.  
Power Consumption: Approximately 8 watts power at rated voltage .  
Approximate Weights:  
127  
240  
108-140  
204-264  
12  
6
208  
10.2-13.2  
5.1-6.6  
J
K
178-229  
Dual Voltage Coil  
(Combines A&B)  
Special AC Coils  
(L1, L2, etc.)  
L
7010  
DC  
M
N
O
P
28  
48  
22.4-30.8  
38.4-52.8  
19.2-26.4  
100-137.5  
9.6-13.2  
24  
125  
12  
60  
Q
R
S
48-66  
250  
550  
16  
200-275  
440-605  
T
U
V
W
Y
Z
X
12.8-17.6  
25.8-35.2  
76.8-105.6  
4.8-6.6  
32  
96  
6
220  
176-242  
Special DC Coils  
(X1, X2, etc.)  
*Four pole Models: Operational voltage range 90% to 110% for AC units;  
85% to 110% for DC units.  
Models  
7012, 7022 . . . . . . . 2 lbs. 4 ozs.  
7014, 7024 . . . . . . . 2 lbs. 10 ozs.  
7032 . . . . . . . . . . . . 3 lbs. 5 ozs.  
Weight may vary slightly with coil voltage.  
See next column for more coil data.  
Dimensions are shown for  
reference purposes only.  
Dimensions are in inches over  
(millimeters) unless otherwise  
specified.  
Specifications and availability  
subject to change.  
www.tycoelectronics.com  
Technical support:  
Refer to inside back cover.  
1250  
Catalog 1308242  
Issued 3-03 (PDF Rev. 10-07)  
AGASTAT  
Outline Dimensions (Dimensions in inches).  
Model 7032  
Models 7012, 7022  
Models 7014, 7024  
Panel mount Option "X"  
Surge/Transient Protection Option  
Dimensions are shown for  
reference purposes only.  
Dimensions are in inches over  
(millimeters) unless otherwise  
specified.  
Specifications and availability  
subject to change.  
www.tycoelectronics.com  
Technical support:  
Refer to inside back cover.  
1251  
Catalog 1308242  
Issued 3-03 (PDF Rev. 10-07)  
AGASTAT  
Ordering Information  
Typical Part No.  
70  
1
2
A
D
GZ  
1. Basic Series:  
70 = 7000 series electropneumatic timing relay  
2. Operation:  
1 = On-delay  
2 = Off-delay  
3 = On-delay, off-delay (double head)  
3. Contact Arrangement:  
2 = 2PDT (2 form C)  
**4 = 4PDT (4 form C)  
4. Coil Voltage:  
AC Coils  
DC Coils  
A = 120VAC, 60 Hz.; 110VAC, 50Hz.  
B = 240VAC, 60 Hz.; 220VAC, 50Hz.  
C = 480VAC, 60 Hz.  
M = 28VDC  
N = 48VDC  
O = 24VDC  
P = 125VDC  
Q = 12VDC  
R = 60VDC  
D = 550VAC, 60 Hz.  
E = 24VAC, 60 Hz.  
F = 127VAC, 50 Hz.  
G = 240VAC, 50Hz.  
S = 250VDC  
T = 550VDC  
U = 16VDC  
H = 12VAC, 60 Hz.  
K = Dual voltage (combines A & B)  
L = Special AC coils (L1, L2, etc.)  
V = 32VDC  
W = 96VDC  
Y = 6VDC  
Z = 220VDC  
X = Special DC coils (X1, X2, etc.)  
5. Timing Range:  
Models 7012, 7022 & 7024  
A = .1 to 1 sec.  
†Models 7014 & 7032  
For model 7032 specify separate time  
range code for each head. Example: AB.  
Any two ranges may be selected.  
A = .2 to 2 sec.  
B = .5 to 5 sec.  
C = 1.5 to 15 sec.  
D = 5 to 50 sec.  
E = 20 to 200 sec.  
F = 1 to 10 min.  
H = 3 to 30 min.  
I = 6 to 60 min.  
B = .7 to 7 sec.  
C = 2 to 20 sec.  
D = 10 to 100 sec.  
E = 30 to 300 sec.  
J = 3 to 120 cyc.  
K = 1 to 300 sec.  
F = 1.5 to 15 min.  
H = 3 to 30 min.  
6. Options:  
A1 = Single quick-connect terminals (note 4).  
K = Explosion-proof Enclosure (note 1).  
L = Auxiliary Switch, instant transfer. 7012 only (notes 2 & 6).  
LL = Two Aux. Switches, instant transfer. On Model 7014 Factory Installed Only. (notes 2 & 6)  
M = Dust-tight Gasketing (notes 4 & 5).  
A2 = Double quick-connect terminals (note 4).  
B = Plug-in connectors (note 4).  
GZ = Enclosure with bottom knockouts (note 1).  
H2 = Hermetically sealed enclosure, 8 pin solder (notes 1 & 4).  
H3 = Hermetically sealed enclosure, 8 pin octal (notes 1 & 4).  
H4 = Hermetically sealed enclosure, 8 screw terminal block (notes 1 & 4).  
*H6 = Hermetically sealed enclosure, 11 pin solder (notes 1 & 4).  
*H7 = Hermetically sealed enclosure, 11 pin octal (notes 1 & 4).  
*H8 = Hermetically sealed enclosure, 11 screw terminal block (notes 1 & 4).  
l1 = Tamper-proof Cap, opaque black (Cannot be combined with Option X).  
l2 = Tamper-proof Cap, transparent (Cannot be combined with Option X).  
P = Octal Plug Adapter. Can be combined only with options l1,l2. M, S, X, or Y1. (note 4).  
S = Dial Stops.  
T = Auxiliary Switch, two-step timing (notes 2 & 6).  
V = Transient/Surge Protection (for DC coil voltage only).  
W = Watertight Enclosure (note 1).  
X = Panelmount includes hardware and adjustment for horizontal operation (note 4)  
Y1 = Horizontal calibration, for horizontal operation without panelmounting (note 4).  
Y2 = Horizontal calibration, with Compensating Spring for vertical operation (note 4).  
Notes:  
1. Cannot be combined with B, P or X Options  
2. Cannot be combined with B, P or Y2 Options  
3. Cannot be combined with GZ, H, l1, l2, K, W or Y1 Options  
4. Not Avail. on 4-Pole Models  
5. Not Available with L, T or LL options.  
6. Not Available on hermetically sealed units.  
*
Sized to accommodate one L or T Auxiliary Switch  
** Not available on On-Delay, Off-Delay (Double Head) model.  
Available with letter calibrated dials only. Upper end of time range may be twice the value shown  
†† 120 cycles = 2 sec.  
Our authorized distributors are more likely to maintain the following items in stock for immediate delivery..  
7012AA  
7012AB  
7012AC  
7012AD  
7012AE  
7012AF  
7012AH  
7012AK  
7012ACL  
7012BC  
7012NC  
7012PA  
7012PB  
7012PC  
7012PD  
7012PF  
7012PJ  
7012PK  
7012PKX  
7012PJX  
7022AA  
7022AB  
7022AC  
7022AD  
7022AE  
7022AF  
7022AH  
7022AI  
7022AJ  
7022AKT  
7022BC  
7022BK  
7022PA  
7022PB  
7022PC  
7022PK  
Dimensions are shown for  
reference purposes only.  
Dimensions are in inches over  
(millimeters) unless otherwise  
specified.  
Specifications and availability  
subject to change.  
www.tycoelectronics.com  
Technical support:  
Refer to inside back cover.  
1252  
Catalog 1308242  
Issued 3-03 (PDF Rev. 10-07)  
AGASTAT  
Ordering options – can only be orderd as factory installed options (Dimensions, where shown, are in inches.)  
A1 – Single Quick-Connect Terminals  
A2 – Double Quick-Connect Terminals  
B – Plug-In Connectors  
Use with Accessory  
“C” or “D” below.  
GZ – Total Enclosure  
With knockouts for bottom  
connection.  
H – Hermetically Sealed Enclosure  
I – Tamper-Proof Cover  
3.16" W x 3.84" D x 7.63"H  
K – Explosion proof Enclosure  
L – Auxiliary Switch  
LL – Auxiliary Switch  
(Meets requirements for  
Class I, Groups C&D  
locations).  
7.50"W x 6.00" D x 10.38" H  
M – Dustight  
P – Octal Plug Adapter  
S – Dial Stops  
Gasket  
Gasket  
V – Transient/Surge Protection  
W – Watertight Enclosure (NEMA-4)  
T – Auxiliary Switch  
4.75" W x 4.44" D x 9.75" H  
Transient  
Protection  
X – Panelmount Kit  
Mounting hardware  
included.  
Accessories (Not available for 7032 models)  
Plug-In Receptacle (Accessory D)  
Plug-In Receptacle (Accessory C)  
Screw Terminals Catalog  
No. 700137. For use with  
"B" Option  
Quick Connect  
Terminals  
Catalog No. 700141.  
For use with "B"  
Option.  
Ordering options can only be ordered as factory installed options.  
Dimensions are shown for  
reference purposes only.  
Dimensions are in inches over  
(millimeters) unless otherwise  
specified.  
Specifications and availability  
subject to change.  
www.tycoelectronics.com  
Technical support:  
Refer to inside back cover.  
1253  

相关型号:

SI9130DB

5- and 3.3-V Step-Down Synchronous Converters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1-E3

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135_11

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9136_11

Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130CG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130LG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130_11

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137DB

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137LG

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9122E

500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification Drivers

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY