TIB080EX [TRACOPOWER]

Industrial Power Supplies;
TIB080EX
型号: TIB080EX
厂家: TRACO ELECTRONIC AG    TRACO ELECTRONIC AG
描述:

Industrial Power Supplies

文件: 总6页 (文件大小:669K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Industrial Power Supplies  
TIB 080EX Series, 80 Watt  
UL Hazloc Class I, division 2 approval  
and ATEX certification  
SEMI F47 compliant for voltage sag  
immunity  
Rugged metal case with optional  
side-mounting  
Very high efficiency up to 90%  
Back power immunity  
150% peak current for 4 sec.  
Operating Temp –40°C to +70°C  
(full load up to 60°C)  
Adjustable output voltage  
High Reliability: MTBF 1 mill hrs per  
IEC 61709  
CB  
Short circuit and overload protection  
5-year product warranty  
Scheme  
UL508  
UL60950-1  
ATEX II3G  
The TIB 080-EX family of next generation of 80 Watt din rail power supplies fea-  
ture high efficiency operation of up to 90% enabling a slim design with alterna-  
tive side-mounting for flat panels (DC OK Indicator on both front and side panel).  
These products certified to UL Hazloc Class 1 / Div 2, and ATEX (EN60079-0,  
EN60079-7. EN600079-15) for operation in hazardous locations. These convec-  
tion cooled power supplies have a -40°C to +60°C full load operating tempera-  
ture range. 150% peak power for up to 4 seconds which is ideal for stepper  
motors, solenoids or actuators. The TIB 080-EX series has an important Back  
Power Immunity feature that helps protect against shut-down or malfunction  
with loads such as inductors and decelerating motors that can feed voltage back  
to the power supply. Outputs are radio-interference-suppressed to impede ra-  
diation at long output lines which reduces the common mode current to within  
limits of telecommunication ports. The series operate with a high power factor  
of up to 99% which also minimizes inrush current.  
Other output power of same series:  
www.tracopower.com/overview/tib-ex  
Additional qualifications include IEC/EN/UL 60950-1, UL508 and CB Report  
with EMC compliance to IEC/EN61000-6-2 and IEC/EN61000-6-3.  
Models  
Output Power  
Output Voltage  
nom. (adjustable)  
Output Current  
Efficiency  
Order Code  
(max.)  
(max.)  
(typ.)  
TIB 080-112EX  
TIB 080-124EX  
TIB 080-148EX  
80 W  
80 W  
80 W  
12 VDC (11.8–15.0)  
24 VDC (23.5–28.0)  
48 VDC (47.0–56.0)  
6.7 A  
3.4 A  
1.7 A  
88.0 %  
90.0 %  
90.0 %  
www.tracopower.com  
Page 1 of 6  
TIB 080EX Series, 80 Watt  
Input Specifications  
Input voltage  
– nominal ranges  
– effective ranges  
100 – 240VAC  
85 – 264VAC  
(below 90 VAC a derating of 3%/V is required)  
Input voltage frequency  
45 – 65 Hz  
Standby power cunsumption  
0.9/1.45 W (115/230 VAC)  
0.48/0.48 (115/230 VAC)  
class A  
Power Factor Correction (PFC)  
Harmonic limits  
Inrush current  
– acc. EN 61000-3-2  
15/30A max. (115/230 VAC)  
Output Specifications  
Output voltage adjustment 1)  
12 Vout models: 11.8 – 15.0 V  
24 Vout models: 23.5 – 28.0 V  
48 Vout models: 47.0 – 56.0 V  
Regulation  
– Input variation  
– Load variation (10–90 %)  
0.1 % max.  
0.5 % max.  
Temperature coefficient  
Hold-up time  
0.02 %/K  
20/160ms min. (115/230 VAC)  
Start-up time  
2s max.  
Ripple and Noise (20MHz bandwidth)  
12 & 24 Vout models: 100 mVp-p max.  
48 Vout models: 200 mVp-p max.  
Output overvoltage protection (OVP) 2)  
12 Vout models: 16 – 19V  
24 Vout models: 32 – 35V  
48 Vout models: 56 – 60V  
Power back immunity 3)  
< OVP level  
Operation  
– Nominal operation  
100 % of Iout nom.  
– Peak power operation  
– Constant current (cc)  
105 150 % of Iout nom.  
> 155 % of Iout nom.  
Duty cycle 4)  
– Threshold  
> 105 %  
(for peak and cc mode)  
– CC or peak opeartion timer  
– normal operation / off period  
4 s max. (switch off)  
6 s typ. (automatic restart after switch off or  
peak and cc operation timer reset)  
Short circuit  
DC OK signal  
Switch off after 4s delay, automatic restart  
– Threshold for Vout  
12 Vout models: on: > 10.9 V typ., off: < 10.7V typ.  
24 Vout models: on: > 22.5 V typ., off: < 21.5 V typ.  
48 Vout models: on: > 45 V typ., off: < 43 V typ.  
relay contact closed, 1 A max., < 100 mOhm  
(also indicated by green LEDs: front and side)  
relay contact open, 30 V max.  
– DC ON  
– DC OFF  
1) Output voltage can be adjusted as indicated. However, output power has to be maintained at nominal value. This means the output  
nominal current has to be reduced in accordance with the increase of output voltage.  
2) In case of an internal error a second voltage regulation loop keeps the output voltage at a save level, the power supply turns off and  
restarts after typ. 6 seconds.  
3) When external voltage is supplied above set output voltage and below OVP threshold, the power supply will function normally without  
switch off or destruction, even if external voltage is applied continuously.  
4) In case of overload or short circuit, the unit switches the output voltage off after 4 seconds and tries to restart every typ. 6 seconds.  
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.  
www.tracopower.com  
Page 2 of 6  
TIB 080EX Series, 80 Watt  
General Specifications  
Operating temperature range  
Derating  
–40°C to +70°C max.  
2 %/K above +60°C  
Cooling  
convection cooling, no internal fan  
switch off at overtemperature  
5–95 % rel. H max.  
Overtemperature protection  
Humidity (non condensing)  
Altitude during operation  
2000 m max.  
Isolation Voltage  
– Input/Ouput  
– Input/Chassis  
– Ouput/Chassis  
4250 VDC  
1500 VDC  
750 VDC  
Creepage Clearance  
– Input/Ouput  
8 mm  
– Input/Chassis  
– Output/Chassis  
4 mm  
1.5 mm  
MTBF (acc. to IEC 61709 at 25°C)  
Safety standards – Information technology equipment  
> 1‘950‘000 h  
IEC/EN 60950-1, UL 60950-1  
CSA 22.2 No 60950-1-03  
UL 508  
EN 60079-15, EN 60079-15, EN 60079-15  
(EX II3G Ex ec nC IIC GC)  
Class I, Division 2  
– Safety low voltage switchgear and controlgear  
– ATEX for hazardous location  
– UL HazLoc  
– Certification documents  
www.tracopower.com/overview/tib  
Electromagnetic compatibility (EMC), Emissions  
– Conducted emission input  
EN 61000-6-3, EN 61204-3  
EN 55032, EN 55011 class B  
EN 55032, EN 55011 class B  
– Radiated RI emission  
Electromagnetic compatibility (EMC), Immunity  
EN 61000-6-2, EN 61204-3  
EN 50121-4  
– Railway applications signalling apparatus  
– Railway applications rolling stock apparatus  
– Electrostatic discharge (ESD)  
– Radiated RF field immunity  
– Electrical fast transient / burst immunity  
– Surge immunity  
EN 50121-3-2  
IEC/EN 61000-4-2 4 kV/8 kV criteria A  
IEC/EN 61000-4-3 10 V/m  
IEC/EN 61000-4-4 2 kV  
IEC/EN 61000-4-5 1 kV/2 kV criteria B  
criteria A  
criteria B  
– Immunity to conducted RF disturbances  
– Power frequency field immunity  
– Mains voltage dips and interruptions  
– Voltage sag immunity  
IEC/EN 61000-4-6 10 V  
IEC/EN 61000-4-8 30 A/m  
IEC/EN 61000-4-11  
criteria A  
criteria A  
criteria B/C  
criteria A  
SEMI F47 (230 VAC)  
Environment  
– Railway applications shock and vibration  
– Vibration acc. IEC 60068-2-6-3  
– Shock acc. IEC 60068-2-27  
according EN 61373  
3 axis, 2 g sine sweep, 10–55 Hz, 11 okt/min  
3 axis, 25 g half sine, 11 ms  
Enclosure material  
Mounting  
– Chassis  
– Cover  
aluminium  
stainless steel  
– DIN-rail mounting  
for DIN-rails as per EN 50022-35ꢀ15/7.5  
Environmental compliance – Reach  
www.tracopower.com/products/reach-declaration.pdf  
RoHS directive 2011/65/EU  
– RoHS  
Connection  
screw terminals  
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.  
www.tracopower.com  
Page 3 of 6  
TIB 080EX Series, 80 Watt  
Function Specification  
Output Characteristic  
Characteristic: Output voltage vs output current for overload conditions until switch off after  
4s at nominal input voltages  
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.  
www.tracopower.com  
Page 4 of 6  
TIB 080EX Series, 80 Watt  
Output Characteristic (continued)  
Derating: max load vs input voltage  
160  
140  
120  
100  
80  
4 seconds  
continious  
60  
40  
20  
30  
40  
50  
60  
70  
80  
-40  
Ambient Temperature [°C]  
Derating: Load vs ambient temperature  
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.  
www.tracopower.com  
Page 5 of 6  
TIB 080EX Series, 80 Watt  
Outline Dimensions  
* Measurement from front panel to DIN-Rail  
32 ± ±  
6,35  
98,6 ± ± *  
94,2 ± ±  
M3  
Combi Head  
24 VDC/ DC OK  
3.4 A  
DC  
ON  
V adj.  
Industrial Power Supply  
80 W  
Model  
TIB 080-124EX  
100-240 VAC,50-60 Hz  
2.00-0.90 A  
L
N
6,35  
M3  
Combi Head  
DIN-Rail  
Hook  
Weight: 367g (±2.95 oz)  
Alternative side mounting:  
24 VDC/ DC OK  
3.4 A  
DC  
ON  
DC ON  
V adj.  
Industrial Power Supply  
80 W  
Model  
TIB 080-124EX  
100-240 VAC,50-60 Hz  
2.00-0.90 A  
L
N
©
Copyright 2019 Traco Electronic AG  
Specifications can be changed without notice!  
Rev. March 22, 2019  
www.tracopower.com  
Page 6 of 6  

相关型号:

TIB120-112EX

Industrial Power Supplies
TRACOPOWER

TIB120-124EX

Industrial Power Supplies
TRACOPOWER

TIB120-148EX

Industrial Power Supplies
TRACOPOWER

TIB120EX

Industrial Power Supplies
TRACOPOWER

TIB82S105BC

16 × 48 × 8 FIELD-PROGRAMMABLE LOGIC SEQUENCER WITH 3-STATE OUTPUTS OR PRESET
TI

TIB82S105BCFK

暂无描述
TI

TIB82S105BCFN

16 × 48 × 8 FIELD-PROGRAMMABLE LOGIC SEQUENCER WITH 3-STATE OUTPUTS OR PRESET
TI

TIB82S105BCN

16 × 48 × 8 FIELD-PROGRAMMABLE LOGIC SEQUENCER WITH 3-STATE OUTPUTS OR PRESET
TI

TIB82S105BCN

OT PLD, 20ns, TTL, PDIP28, DIP-28
ROCHESTER

TIB82S105BMFK

OT PLD, 25ns, CQCC28
TI

TIB82S105BMFKB

IC,SIMPLE-PLD,PLS-TYPE,TTL,LLCC,28PIN,CERAMIC
TI

TIB82S105BMJ

OT PLD, 25ns, CDIP28
TI