PSAE-800-36 [WALL]

AC/DC Switching Power Supplies;
PSAE-800-36
型号: PSAE-800-36
厂家: WALL INDUSTRIES,INC.    WALL INDUSTRIES,INC.
描述:

AC/DC Switching Power Supplies

文件: 总8页 (文件大小:469K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
PSAE800 SERIES  
Rev B  
Wall Industries, Inc.  
Up to 804 Watts, AC/DC Switching Power Supplies  
FEATURES  
RoHS Compliant  
Programmable Output Voltage (0~105%)  
Programmable Output Current (0~105%)  
Power OK Signal (Power Good, Logic Low)  
Remote ON/OFF, Remote Sense Functions  
Universal Input Voltage Range: 90-264VAC  
Single Outputs Ranging from 12~60VDC  
+5V/0.5A or +8V/0.3A Auxiliary Output  
Selectable by User  
Active PFC > 0.95 at 230VAC  
Up to 804 Watts Output Power  
High Efficiency up to 93%  
4242VDC I/O Isolation  
Constant Current Limiting  
Intelligent LED Indicators  
Optional RS232 Function  
Built-in I2C Serial Data Bus  
1U Profile, High Power Density  
Size:  
9.80 x 5.00 x 1.61 inches  
(249.0 x 127.0 x 41.0 mm)  
Forced Current Sharing at Parallel Operation  
UL 60950-1, 2nd edition, TUV EN60950-1:  
Protection: OLP, OVP, OTP, Fan Failure  
2006+A11 Approvals  
DESCRIPTION  
The PSAE800 series of AC/DC switching power supplies provides up to 804 Watts of output  
power in a 9.80” x 5.00” x 1.61” enclosed case. This series consists of single output models  
ranging from 12~60VDC with an input voltage range of 90~264VAC. Standard features  
include high efficiency up to 93%, active PFC, programmable output voltage and output  
current, remote on/off, remote sense, power OK signal, and internal ball bearing fan. This  
series also has over voltage, over load, and over temperature protection. All models are  
RoHS compliant and have UL 60950-1, 2nd edition and TUV EN60950-1: 2006+A11 safety  
approvals.  
MODEL SELECTION TABLE  
Model Number  
PSAE-800-12  
PSAE-800-15  
PSAE-800-24  
PSAE-800-30  
PSAE-800-36  
PSAE-800-48  
Input Voltage  
Output Voltage  
12 VDC  
Output Current  
66.7A  
Output Power  
800W  
Ripple & Noise (1)  
120mVp-p  
150mVp-p  
240mVp-p  
300mVp-p  
360mVp-p  
480mVp-p  
600mVp-p  
Efficiency  
89%  
15 VDC  
53.4A  
801W  
90%  
24 VDC  
33.5A  
804W  
92%  
90~264 VAC  
30 VDC  
26.7A  
801W  
92%  
36 VDC  
22.3A  
802.8W  
801.6W  
804W  
92%  
48 VDC  
16.7A  
92%  
PSAE-800-60  
NOTES  
60 VDC  
13.4A  
93%  
1. Ripple & noise is measured at 20MHz limited bandwidth and using a 12" twisted pair-wire terminated with a 0.1µF & 47µF  
capacitors in parallel.  
2. For voltages near the low end of the input voltage range, see the derating curve for the power supply output rating.  
3. When in parallel operation only one unit might operate if the total output load is less than 5% of the rated load condition.  
4. The power supply is considered a component which will be installed into final equipment. The final equipment must be re-  
confirmed that it still meets EMC directives.  
Wall Industries, Inc. • 37 Industrial Drive, Exeter, NH 03833 • Tel: 603-778-2300 • Toll Free: 888-597-9255 • Fax 603-778-9797  
website: www.wallindustries.com • e-mail: sales@wallindustries.com  
07/23/2013  
Page 1 of 8  
PSAE800 SERIES  
Rev B  
Wall Industries, Inc.  
Up to 804 Watts, AC/DC Switching Power Supplies  
SPECIFICATIONS: PSAE800 SERIES  
All specifications are based on 25°C, Nominal Input Voltage, and Maximum Output Current unless otherwise noted.  
We reserve the right to change specifications based on technological advances.  
SPECIFICATION  
INPUT SPECIFICATIONS  
Input Voltage  
TEST CONDITIONS  
Min  
Typ  
Max  
Unit  
See Note 2  
90  
47  
264  
63  
VAC  
Hz  
Input Frequency  
At 100VAC and full load  
At 230VAC and full load  
At 115VAC and cold start  
At 230VAC and cold start  
At 115VAC and full load  
At 230VAC and full load  
9.3  
4.7  
AC Current  
A
A
30  
Inrush Current  
Power Factor  
60  
0.98  
0.95  
OUTPUT SPECIFICATIONS  
Output Voltage  
See Table  
Voltage Tolerance  
Voltage Adjustability  
Line Regulation  
Includes set-up tolerance, line regulation, and load regulation  
Typical adjustment by potentiometer (VR1)  
Low Line to High Line  
-2.0  
-5.0  
-1.0  
-1.0  
+2.0  
+5.0  
+1.0  
+1.0  
%
%
%
%
Load Regulation  
Output Power  
0% to 100% full load  
See Table  
Output Current  
See Table  
See Table  
Ripple & Noise (20MHz BW)  
Hold-up Time  
Measured with 0.1µF and 47µF capacitors in parallel  
At 230VAC and full load  
full load  
14  
ms  
ms  
Setup Time  
800  
100  
Rise Time  
full load  
ms  
Temperature Coefficient  
PROTECTION  
Over Voltage Protection (see page 4) Protection type: latch-style. Recovery after reset AC power ON or inhibit  
0~50°C  
-0.02  
+0.02  
%/°C  
Variable OVP, 120% 7% Vout  
105% rated output power  
Over Load Protection  
Over Temperature Protection  
GENERAL SPECIFICATIONS  
Efficiency  
Protection type: constant current limiting  
Protection type: shutdown output voltage (auto-recovery after temp. goes down)  
85°C 5°C detect on heatsink of sec. side  
See Table  
Input to Output  
4242VDC (3000VAC)  
2121VDC (1500VAC)  
707VDC (500VAC)  
Isolation Voltage  
Input to FG  
Output to FG  
Isolation Resistance  
Leakage Current  
Input to output, input to FG, output to FG; 500VDC  
At 240VAC  
100  
MΩ  
mA  
1
FUNCTIONS  
Auxiliary Power  
+5V/0.5A or +8V/0.3A auxiliary output selectable by user  
External switch or NPN transistor to turn ON/OFF  
Remote ON/OFF Control  
Power OK Signal  
Open drain signal low when PSU turns on; sink current: 20mA max.; drain voltage: 40V max.  
Adjustment of output voltage is between 0~105% of rated output  
Adjustment of output current is between 0~105% of rated output  
See page 6  
Output Voltage Trim  
Output Current Trim  
Parallel Operation (Current Sharing)  
ENVIRONMENTAL SPECIFICATIONS  
Operating Temperature  
Storage Temperature  
Operating Humidity  
Storage Humidity  
With derating (see derating curve)  
Non-condensing  
-20  
-40  
20  
+60  
+85  
90  
°C  
°C  
% RH  
% RH  
10  
95  
Cooling  
Controlled by power rating and temperature (internal ball bearing fan)  
Vibration  
10~500Hz, 2G 10 min./1 cycle, period for 60 min. each along X, Y, Z axes. Compliance to IEC 68-2-6, IEC 68-2-64  
PHYSICAL SPECIFICATIONS  
Weight  
3.75 lbs (1700g)  
Dimensions (W x H x D)  
SAFETY & EMC (See Note 4)  
Safety Approvals  
9.80 x 5.00 x 1.61 inches (249.0 x 127.0 x 41.0 mm)  
UL 60950-1, 2nd edition, TUV EN60950-1: 2006+A11  
EN55022: 2006+A1:2007 Class B, EN61204-3:2000, EN61000-6-3: 2007  
EMI (Conduction & Radiation)  
Harmonic Current  
EN61000-3-2: 2006+A2: 2009 Class A, EN61000-3-3: 2008  
EMS Immunity  
EN55024: 1998+A1: 2001+A2: 2003 light industry level, criteria A, EN61204-3: 2000, EN61000-6-1: 2007  
Wall Industries, Inc. • 37 Industrial Drive, Exeter, NH 03833 • Tel: 603-778-2300 • Toll Free: 888-597-9255 • Fax 603-778-9797  
website: www.wallindustries.com • e-mail: sales@wallindustries.com  
07/23/2013  
Page 2 of 8  
PSAE800 SERIES  
Rev B  
Wall Industries, Inc.  
Up to 804 Watts, AC/DC Switching Power Supplies  
MECHANICAL DRAWING  
Unit: inches [mm]  
1.61 [40.9]  
9.80 [249.0]  
+V  
-V  
M6  
3-M4 L=0.157 [4]  
VR1  
LED  
Air!ow  
Direction  
3
2
1
7.80 [198.0]  
1.46 [37.0] 1.06 [26.9]  
0.55 [14.0]  
6-M4 (Both Sides) L=0.236 [6]  
0.81 [20.5]  
0.45 [11.5]  
0.98 [25.0]  
0.32 [8.0]  
8.70 [221.0]  
AC Input Terminal  
Pin No. Function  
Control Pin Number Assignment (CN2)  
Description Pin No. Function  
Pin No. Function  
Description  
Inhibit ON/OFF (+)  
+5V/0.5A, +8V/0.3A Auxiliary Power  
Inhibit ON/OFF (-)  
1
2
3
ACL  
1
2
NC  
NC  
For RS232 Receiver Function  
For RS232 Transmission Function  
+5V/0.5A, +8V/0.3A Auxiliary Power  
Ground  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
EN+  
AUX  
EN-  
ACN  
3
AUX  
GND  
SCL  
4
GND  
PAR  
VSET  
POK  
GND  
VS-  
Ground  
5
Serial Data used in the I2C Interface  
Serial Data used in the I2C Interface  
+5V/0.5A, +8V/0.3A Auxiliary Power  
Ground  
Parallel Operation Current Sharing  
AUX Output Set  
6
SDA  
AUX  
GND  
VCI  
7
Power OK  
8
Ground  
9
V Program  
Remote Sense (-)  
10  
11  
12  
GND  
ACI  
Ground  
VO-  
Negative Output Voltage  
Resmote Sense (+)  
Positive Output Voltage  
I Program  
VS+  
VO+  
GND  
Ground  
Wall Industries, Inc. • 37 Industrial Drive, Exeter, NH 03833 • Tel: 603-778-2300 • Toll Free: 888-597-9255 • Fax 603-778-9797  
website: www.wallindustries.com • e-mail: sales@wallindustries.com  
07/23/2013  
Page 3 of 8  
PSAE800 SERIES  
Rev B  
Wall Industries, Inc.  
Up to 804 Watts, AC/DC Switching Power Supplies  
DERATING CURVES  
Load vs Ambient Temperature  
Load vs Input Voltage  
Ta=25°C  
100  
100  
80  
60  
40  
20  
90  
80  
70  
60  
50  
40  
-20  
0
10  
20  
30  
40  
50  
60  
70  
90  
264  
100  
110  
120  
Ambient Temperature (°C)  
Input Voltage (VAC)  
CURVES  
CMD vs Output Curve  
VCI vs OVP Curve  
Wall Industries, Inc. • 37 Industrial Drive, Exeter, NH 03833 • Tel: 603-778-2300 • Toll Free: 888-597-9255 • Fax 603-778-9797  
website: www.wallindustries.com • e-mail: sales@wallindustries.com  
07/23/2013  
Page 4 of 8  
PSAE800 SERIES  
Rev B  
Wall Industries, Inc.  
Up to 804 Watts, AC/DC Switching Power Supplies  
LED STATUS  
LED  
LED Signal  
Status  
Power OK (Local Mode)  
Power OK (Remote Mode)  
Power Standby  
Solid (Green)  
Solid (Orange)  
Slow Blink (Green)  
Fast Blink (Red)  
Solid (Red)  
Over Voltage Protection (OVP)  
Over Load Protection (OLP)  
Over Temperature Protection (OTP)  
Fan Failure  
Slow Blink (Red)  
Intermittent Blink (Red)  
Interlace Blink (Red)  
Power Failure  
* Local mode: Use ACI/VCI to control output current and voltage  
Remote Mode: Use RS232 or I2C command to control output current and voltage  
REMOTE ON/OFF  
(1) Using Internal 5V Auxiliary Source  
(2) ON/OFF Control by NPN Transistor  
(3) Using External Voltage Source  
AUX  
AUX  
AUX  
SW  
2KΩ  
EN+  
2KΩ  
EN+  
2KΩ  
EN+  
SW  
AUX  
AUX  
AUX  
AUX  
EN-  
EN-  
Tr  
EN-  
Ctrl  
GND  
GND  
GND  
GND  
OFF Power OFF  
ON Power ON  
L
Power OFF  
Power ON  
OFF Power OFF  
ON Power ON  
sw  
Ctrl  
sw  
H
Default setting  
POWER OK SIGNAL  
* Place an additional capacitor to have a better performance of auxiliary power  
operation.  
P.OK  
Good  
Failure  
* The grounding of “AUX” power should be connected to “GND” port. If “V-“ is  
connected as Grounding, make sure to short the GND and V- ports.  
DC / DC  
5V / 0.5A  
8V / 0.3A  
Open  
5V  
8V  
(Default Setting)  
AUX  
Vset  
Short to GND  
VSET  
GND  
Internal Circuit  
AUX  
LOAD  
470µF  
16V  
*
AUX and P.OK Signal  
Wall Industries, Inc. • 37 Industrial Drive, Exeter, NH 03833 • Tel: 603-778-2300 • Toll Free: 888-597-9255 • Fax 603-778-9797  
website: www.wallindustries.com • e-mail: sales@wallindustries.com  
07/23/2013  
Page 5 of 8  
PSAE800 SERIES  
Rev B  
Wall Industries, Inc.  
Up to 804 Watts, AC/DC Switching Power Supplies  
CURRENT SHARING  
1) Remote Sense  
2) Current Sharing with Remote Sensing  
1
2
CN2  
NC  
NC  
AUX  
SCL  
AUX  
VCI  
GND  
SDA  
GND  
GND  
GND  
AUX  
GND  
ACI  
EN+  
EN-  
PAR VSET  
POK  
VS-  
GND  
VO-  
VS+  
VO+  
23  
24  
Load  
1
2
1
2
1
2
1
2
NC  
AUX  
SCL  
AUX  
VCI  
NC  
NC  
AUX  
SCL  
AUX  
VCI  
NC  
NC  
AUX  
SCL  
AUX  
VCI  
NC  
NC  
AUX  
SCL  
AUX  
VCI  
NC  
GND  
SDA  
GND  
GND  
GND  
AUX  
GND  
GND  
SDA  
GND  
GND  
GND  
AUX  
GND  
GND  
SDA  
GND  
GND  
GND  
AUX  
GND  
GND  
SDA  
GND  
GND  
GND  
AUX  
GND  
ACI  
ACI  
ACI  
ACI  
EN+  
EN-  
EN+  
EN-  
EN+  
EN-  
EN+  
EN-  
PAR VSET  
PAR VSET  
PAR VSET  
PAR VSET  
POK  
GND  
VO-  
POK  
GND  
VO-  
POK  
GND  
VO-  
POK  
GND  
VO-  
VS-  
VS-  
VS-  
VS-  
VS+  
VO+  
VS+  
VO+  
VS+  
VO+  
VS+  
VO+  
23  
24  
23  
24  
23  
24  
23  
24  
3) Local Sense (Default Setting)  
4) Current Sharing with Local Sensing  
1
2
CN2  
NC  
AUX  
SCL  
AUX  
VCI  
NC  
GND  
SDA  
GND  
GND  
GND  
AUX  
GND  
ACI  
EN+  
EN-  
PAR VSET  
POK  
VS-  
GND  
VO-  
Load  
VS+  
VO+  
23  
24  
1
2
1
2
1
2
1
2
NC  
AUX  
SCL  
AUX  
VCI  
NC  
NC  
AUX  
SCL  
AUX  
VCI  
NC  
NC  
AUX  
SCL  
AUX  
VCI  
NC  
NC  
AUX  
SCL  
AUX  
VCI  
NC  
GND  
SDA  
GND  
GND  
GND  
AUX  
GND  
GND  
SDA  
GND  
GND  
GND  
AUX  
GND  
GND  
SDA  
GND  
GND  
GND  
AUX  
GND  
GND  
SDA  
GND  
GND  
GND  
AUX  
GND  
ACI  
ACI  
ACI  
ACI  
EN+  
EN-  
EN+  
EN-  
EN+  
EN-  
EN+  
EN-  
PAR VSET  
PAR VSET  
PAR VSET  
PAR VSET  
POK  
GND  
VO-  
POK  
GND  
VO-  
POK  
GND  
VO-  
POK  
GND  
VO-  
VS-  
VS-  
VS-  
VS-  
VS+  
VO+  
VS+  
VO+  
VS+  
VO+  
VS+  
VO+  
23  
24  
23  
24  
23  
24  
23  
24  
Wall Industries, Inc. • 37 Industrial Drive, Exeter, NH 03833 • Tel: 603-778-2300 • Toll Free: 888-597-9255 • Fax 603-778-9797  
website: www.wallindustries.com • e-mail: sales@wallindustries.com  
07/23/2013  
Page 6 of 8  
PSAE800 SERIES  
Rev B  
Wall Industries, Inc.  
Up to 804 Watts, AC/DC Switching Power Supplies  
INSTALLATION INSTRUCTIONS  
1. Mounting Directions  
1-1 Recommended Standard Mounting Methods  
(a)  
(b)  
(c)  
CN2  
23  
24  
1
2
3-M4  
L=4mm max.  
3-M4  
L=4mm max.  
3-M4  
L=4mm max.  
2. Mounting Method  
2-1 There are ventilating holes on the front and back side panels. Do not obstruct; allow at least 50mm for airflow  
2-2 The maximum allowable penetration for the screw is 4mm. Incomplete threading should not be penetrated.  
2-3 Recommended torque of mounting screw: M4 screw: 1.27N • m (13.0kgf • cm)  
More than 50mm  
More than 50mm  
FAN  
FAN  
Airflow  
Wall Industries, Inc. • 37 Industrial Drive, Exeter, NH 03833 • Tel: 603-778-2300 • Toll Free: 888-597-9255 • Fax 603-778-9797  
website: www.wallindustries.com • e-mail: sales@wallindustries.com  
07/23/2013  
Page 7 of 8  
PSAE800 SERIES  
Rev B  
Wall Industries, Inc.  
Up to 804 Watts, AC/DC Switching Power Supplies  
COMPANY INFORMATION  
Wall Industries, Inc. has created custom and modified units for over 50 years. Our in-house research and development engineers will  
provide a solution that exceeds your performance requirements on-time and on budget. Our ISO9001-2008 certification is just one  
example of our commitment to producing a high quality, well-documented product for our customers.  
Our past projects demonstrate our commitment to you, our customer. Wall Industries, Inc. has a reputation for working closely with its  
customers to ensure each solution meets or exceeds form, fit and function requirements. We will continue to provide ongoing  
support for your project above and beyond the design and production phases. Give us a call today to discuss your future projects.  
Contact Wall Industries for further information:  
Phone:  
Toll Free:  
Fax:  
(603)778-2300  
(888)597-9255  
(603)778-9797  
E-mail:  
Web:  
Address:  
sales@wallindustries.com  
www.wallindustries.com  
37 Industrial Drive  
Exeter, NH 03833  
Wall Industries, Inc. • 37 Industrial Drive, Exeter, NH 03833 • Tel: 603-778-2300 • Toll Free: 888-597-9255 • Fax 603-778-9797  
website: www.wallindustries.com • e-mail: sales@wallindustries.com  
07/23/2013  
Page 8 of 8  

相关型号:

PSAE-800-48

AC/DC Switching Power Supplies
WALL

PSAE-800-60

AC/DC Switching Power Supplies
WALL

PSAE1500

AC/DC Switching Power Supplies
WALL

PSAE800

AC/DC Switching Power Supplies
WALL

PSAEK-3000-12

AC/DC Switching Power Supplies
WALL

PSAEK-3000-15

AC/DC Switching Power Supplies
WALL

PSAEK-3000-150

AC/DC Switching Power Supplies
WALL

PSAEK-3000-200

AC/DC Switching Power Supplies
WALL

PSAEK-3000-24

AC/DC Switching Power Supplies
WALL

PSAEK-3000-250

AC/DC Switching Power Supplies
WALL

PSAEK-3000-30

AC/DC Switching Power Supplies
WALL

PSAEK-3000-300

AC/DC Switching Power Supplies
WALL