PSAEK-3000-250 [WALL]

AC/DC Switching Power Supplies;
PSAEK-3000-250
型号: PSAEK-3000-250
厂家: WALL INDUSTRIES,INC.    WALL INDUSTRIES,INC.
描述:

AC/DC Switching Power Supplies

文件: 总7页 (文件大小:502K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
PSAEK3000HV SERIES  
Rev A  
Wall Industries, Inc.  
3000 Watts, AC/DC Switching Power Supplies  
FEATURES  
RoHS Compliant  
Remote Setting Multiple PSU via RS232, RS485 & I2C  
Programmable Output Voltage (0~105%)  
Programmable Output Current (0~105%)  
Universal Input Voltage Range: 90~264VAC (127~370VDC)  
Single Outputs Ranging from 150VDC to 400VDC  
Selectable +5V/0.5A or +9V/0.3A Auxiliary Output  
Forced Current Sharing at Parallel Operation  
Remote ON/OFF Function  
3000 Watts Output Power  
High Efficiency up to 93%  
3000VAC (4242VDC) I/O Isolation  
Constant Current Limiting  
Global Control via RS232  
Power OK Signal  
High Power Density 16.3W/in3  
UL60950-1 & EN60950-1 Safety Approvals Protection: OLP, OVP, OTP, SCP, Fan Failure  
DESCRIPTION  
Size:  
Weight  
The PSAEK3000HV series of AC/DC switching power supplies provides 3000 Watts of output power in an  
11.024” x 6.693” x 2.500” enclosed case. This series consists of single output models ranging from 150VDC  
to 400VDC with a universal input voltage range of 90~264VAC (127~370VDC). Standard features include  
high efficiency up to 93%, programmable output voltage and output current, remote on/off, and power OK  
signal. This series also has over temperature, over voltage, over load, and short circuit protection. All  
models are RoHS compliant and have UL60950-1 and EN60950-1 safety approvals.  
11.024 x 6.693 x 2.500 inches 8.38 lbs (3.8kg)  
280.00 x 170.00 x 63.50 mm  
MODEL SELECTION TABLE  
Input Voltage (2) Output Voltage Output Current Line Regulation Load Regulation Output Power Ripple & Noise (1) Efficiency  
Model Number  
PSAEK-3000-150  
PSAEK-3000-200  
PSAEK-3000-250  
PSAEK-3000-300  
PSAEK-3000-400  
150 VDC  
200 VDC  
250 VDC  
300 VDC  
400 VDC  
20A  
15A  
12A  
10A  
7.5A  
1.0%  
1.0%  
1.0%  
1.0%  
1.0%  
1.0  
1.0  
1.0  
1.0  
1.0  
3000W  
3000W  
3000W  
3000W  
3000W  
1500mVp-p  
1500mVp-p  
1500mVp-p  
1500mVp-p  
1500mVp-p  
93%  
93%  
93%  
93%  
93%  
90~264 VAC  
(127~370 VDC)  
NOTES  
1. Ripple & noise is measured at 20MHz limited bandwidth and using a 12" twisted pair-wire terminated with a 0.1µF & 47µF capacitors in parallel.  
2. For voltages near the low end of the input voltage range, see the derating curve for the power supply output rating.  
3. When in parallel operation only one unit might operate if the total output load is less than 5% of the rated load condition.  
4. The power supply is considered a component which will be installed into final equipment. The final equipment must be re-confirmed that it still meets  
EMC directives.  
DERATING CURVES  
Load vs Ambient Temperature  
Load vs Input Voltage  
120  
120  
Ta=25°C  
3000W  
100  
90  
80  
70  
60  
50  
40  
100  
80  
60  
50  
40  
2000W  
20  
90  
264  
-20  
0
10  
20  
30  
40  
50  
60  
70  
80  
115  
140  
180  
Input Voltage (VAC)  
Ambient Temperature (°C)  
Wall Industries, Inc. • 37 Industrial Drive, Exeter, NH 03833 • Tel: 603-778-2300 • Toll Free: 888-597-9255 • Fax 603-778-9797  
website: www.wallindustries.com • e-mail: sales@wallindustries.com  
06/19/2014  
Page 1 of 7  
PSAEK3000HV SERIES  
Rev A  
Wall Industries, Inc.  
3000 Watts, AC/DC Switching Power Supplies  
SPECIFICATIONS: PSAEK3000HV SERIES  
All specifications are based on 25°C, Nominal Input Voltage, and Maximum Output Current unless otherwise noted.  
We reserve the right to change specifications based on technological advances.  
SPECIFICATION  
TEST CONDITIONS  
Min  
Typ  
Max  
Unit  
INPUT SPECIFICATIONS  
AC input voltage range  
DC input voltage range  
90  
127  
47  
264  
370  
63  
VAC  
VDC  
Hz  
Input Voltage (See Note 2)  
Input Frequency  
AC Current  
At 115VAC (2000W)  
19.7  
14.5  
33  
A
A
At 230VAC (3000W)  
At 115VAC and cold start  
At 230VAC and cold start  
At 115VAC and full load  
At 230VAC and full load  
Inrush Current  
Power Factor  
65  
0.98  
0.95  
OUTPUT SPECIFICATIONS  
Output Voltage  
See Table  
Voltage Tolerance  
Voltage Adjustability  
Line Regulation  
Load Regulation  
Output Power  
Includes set-up tolerance, line regulation, and load regulation  
Typical adjustment by potentiometer (VR1)  
Low Line to High Line  
-2.0  
-5.0  
-1.0  
-1.0  
+2.0  
+5.0  
+1.0  
+1.0  
%
%
%
%
0% to 100% full load  
See Table  
See Table  
1500  
Output Current  
Ripple & Noise (20MHz BW)  
Hold-up Time  
Measured with 0.1µF and 47µF capacitors in parallel  
mVp-p  
ms  
At 230VAC and full load  
full load  
14  
Setup Time  
800  
50  
ms  
Rise Time  
full load  
ms  
Temperature Coefficient  
PROTECTION  
0~50°C  
-0.02  
+0.02  
%/°C  
Over Voltage Protection (see page 4) Protection type: latch-style. Recovery after reset AC power ON or inhibit  
Variable OVP, 120% 7% Vout  
105% rated output power  
Over Load Protection  
Over Temperature Protection  
GENERAL SPECIFICATIONS  
Efficiency  
Protection type: constant current limit  
Protection type: auto-recovery after temperature goes down  
85°C 5°C detect on heatsink of pri. & sec. side  
93  
%
Input to Output  
3000VAC (4242VDC)  
1500VAC (2121VDC)  
500VAC (707VDC)  
Isolation Voltage  
Test is done without enclosure  
Input to FG  
Output to FG  
Input to Output 500VDC  
100  
100  
100  
Isolation Resistance Input to FG  
Output to FG  
500VDC  
MΩ  
mA  
500VDC  
Leakage Current  
FUNCTIONS  
At 240VAC  
1.0  
Auxiliary Power  
Selectable +5V/0.5A or +9V/0.3A aux. output  
By external switch  
Remote ON/OFF Control (see page 5) Isolated from output  
Power OK Signal  
Sink Current: 20mA max.; Drain Voltage: 40V max.  
Open drain signal low when PSU turns on  
Output Voltage Trim  
Output Current Trim  
Parallel Operation (Current Sharing)  
ENVIRONMENTAL SPECIFICATIONS  
Operating Temperature  
Storage Temperature  
Operating Humidity  
Storage Humidity  
0
0
105  
105  
%Vo  
%Io  
See page 5  
See derating curve  
Non-condensing  
-20  
-40  
20  
+60  
+85  
90  
°C  
°C  
% RH  
% RH  
10  
95  
Cooling  
Load and temperature control fan  
Vibration  
10~500Hz, 5G 10 min./1 cycle, period for 60 min. each along X, Y, Z axes. Certified IEC60068-2-6, IEC60068-2-64  
PHYSICAL SPECIFICATIONS  
Weight  
8.38 lbs (3.8kg)  
Dimensions (W x H x D)  
SAFETY & EMC (See Note 4)  
Safety Approvals  
11.024 x 6.693 x 2.500 inches (280.00 x 170.00 x 63.50 mm)  
UL60950-1; EN60950-1  
EN55022, EN61204-3, EN61000-6-3  
EMI (Conduction & Radiation)  
Harmonic & Flicker  
EMS Immunity  
EN61000-3-2; EN61000-3-3  
EN55024; EN61204-3; EN61000-6-1; IEC61000-4-2, 3, 4, 5, 6, 8, 11  
Wall Industries, Inc. • 37 Industrial Drive, Exeter, NH 03833 • Tel: 603-778-2300 • Toll Free: 888-597-9255 • Fax 603-778-9797  
website: www.wallindustries.com • e-mail: sales@wallindustries.com  
06/19/2014  
Page 2 of 7  
PSAEK3000HV SERIES  
Rev A  
Wall Industries, Inc.  
3000 Watts, AC/DC Switching Power Supplies  
MECHANICAL DRAWING  
Unit: inches [mm]  
11.024 [280.00]  
2.500 [63.50]  
1.870 [47.50]  
8.189 [208.00]  
4-M4 NUT  
CN5  
1.339 [34.00]  
9.331 [237.00]  
4-M4 NUT Both Side  
AC Input Terminal  
Control Pin Number Assignment (CN5): JST S24B-PHDSS or Equivalent  
Pin  
1
Function  
ACL  
Pin  
Function  
NC  
Description  
No Connect  
Pin  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
Function  
ACI  
Description  
I Program  
1
2
2
ACN  
NC  
No Connect  
GND  
VCI  
Ground  
3
3
NC  
No Connect  
V Program  
4
NC  
No Connect  
GND  
AUX  
GND  
SCL  
Ground  
5
POK  
GND  
PAR  
VSET  
EN-  
Power OK  
+5V/0.5A or +9V/0.3A Auxiliary Power  
Ground  
6
Ground  
7
Parallel Operation Current Sharing  
AUX Output Set  
Inhibit ON/OFF (-)  
Ground  
Serial Clock used in the I2C Interface  
Serial Data used in the I2C Interface  
+5V/0.5A or +9V/0.3A Auxiliary Power  
Ground  
8
SDA  
AUX  
GND  
NC  
9
10  
11  
12  
GND  
EN+  
AUX  
Inhibit ON/OFF (+)  
+5V/0.5A or +9V/0.3A Auxiliary Power  
For RS232 Transmission Function  
For RS232 Receiver Function  
NC  
Mating Housing / contact: JST PHDR-24VS or equivalent and JST SPHD-002T-P0.5 or equivalent  
Wall Industries, Inc. • 37 Industrial Drive, Exeter, NH 03833 • Tel: 603-778-2300 • Toll Free: 888-597-9255 • Fax 603-778-9797  
website: www.wallindustries.com • e-mail: sales@wallindustries.com  
06/19/2014  
Page 3 of 7  
PSAEK3000HV SERIES  
Rev A  
Wall Industries, Inc.  
3000 Watts, AC/DC Switching Power Supplies  
LED STATUS  
LED  
LED Signal  
Status  
Power OK (Local Mode)  
Power OK (Remote Mode)  
Power Standby  
Solid (Green)  
Solid (Orange)  
Slow Blink (Green)  
Fast Blink (Red)  
Solid (Red)  
Over Voltage Protection (OVP)  
Over Load Protection (OLP)  
Over Temperature Protection (OTP)  
Fan Failure  
Slow Blink (Red)  
Intermittent Blink (Red)  
Interlace Blink (Red)  
Power Failure  
* Local mode: Use ACI/VCI to control output current and voltage  
* Remote Mode: Use RS232 or I2C command to control output current and voltage  
CURVES  
CMD vs Output Curve  
VCI vs OVP Curve  
External Voltage (VDC)  
External Resistor (KΩ)  
Wall Industries, Inc. • 37 Industrial Drive, Exeter, NH 03833 • Tel: 603-778-2300 • Toll Free: 888-597-9255 • Fax 603-778-9797  
website: www.wallindustries.com • e-mail: sales@wallindustries.com  
06/19/2014  
Page 4 of 7  
PSAEK3000HV SERIES  
Rev A  
Wall Industries, Inc.  
3000 Watts, AC/DC Switching Power Supplies  
CURRENT SHARING  
NC  
NC  
NC  
NC  
NC  
NC  
NC  
NC  
NC  
NC  
NC  
NC  
NC  
NC  
NC  
NC  
GND  
POK  
GND  
POK  
GND  
POK  
GND  
POK  
VSET PAR  
VSET PAR  
VSET PAR  
VSET PAR  
GND  
AUX  
GND  
GND  
GND  
SDA  
GND  
EN-  
EN+  
ACI  
GND  
AUX  
GND  
GND  
GND  
SDA  
GND  
NC  
EN-  
EN+  
ACI  
GND  
AUX  
GND  
GND  
GND  
SDA  
GND  
NC  
EN-  
EN+  
ACI  
GND  
AUX  
GND  
GND  
GND  
SDA  
GND  
NC  
EN-  
EN+  
ACI  
VCI  
VCI  
VCI  
VCI  
AUX  
SCL  
AUX  
NC  
AUX  
SCL  
AUX  
NC  
AUX  
SCL  
AUX  
NC  
AUX  
SCL  
AUX  
NC  
NC  
24  
23  
24  
23  
24  
23  
24  
23  
REMOTE ON/OFF  
(1) Using Internal 5V Auxiliary Source  
(2) ON/OFF Control by NPN Transistor  
(3) Using External Voltage Source  
AUX  
AUX  
AUX  
SW  
2KΩ  
2KΩ  
EN+  
2KΩ  
EN+  
EN+  
SW  
AUX  
AUX  
AUX  
AUX  
EN-  
EN-  
Tr  
EN-  
Ctrl  
GND  
GND  
GND  
GND  
L
Power OFF  
Power ON  
OFF Power OFF  
ON Power ON  
OFF Power OFF  
ON Power ON  
Ctrl  
sw  
sw  
H
Default setting  
Wall Industries, Inc. • 37 Industrial Drive, Exeter, NH 03833 • Tel: 603-778-2300 • Toll Free: 888-597-9255 • Fax 603-778-9797  
website: www.wallindustries.com • e-mail: sales@wallindustries.com  
06/19/2014  
Page 5 of 7  
PSAEK3000HV SERIES  
Rev A  
Wall Industries, Inc.  
3000 Watts, AC/DC Switching Power Supplies  
POWER OK SIGNAL  
* Place an additional capacitor to have a better performance of auxiliary power operation.  
P.OK  
Good  
Failure  
AUX  
LOAD  
470µF  
16V  
*
DC / DC  
5V/0.5A  
or  
AUX  
VSET  
9V/0.3A  
* The grounding of “AUX” power should be connected to “GND” port. If “V-“ is connected as Grounding  
make sure to short the “GND” and “V-“ ports.  
GND  
Internal Circuit  
Open (Default Setting)  
Short to GND  
5V  
9V  
VSET  
AUX and P.OK Signal  
INSTALLATION INSTRUCTIONS  
1. Mounting Directions  
1-1 Recommended Standard Mounting Methods  
(a)  
(b)  
(c)  
4-M4  
L=4mm max.  
4-M4  
L=4mm max.  
4-M4  
L=4mm max.  
2. Mounting Method  
2-1 There are ventilating holes on the front and back side panels. Do not obstruct; allow at least 50mm for airflow  
2-2 The maximum allowable penetration for the screw is 4mm. Incomplete threading should not be penetrated.  
2-3 Recommended torque of mounting screw: M4 screw: 1.27N • m (13.0kgf • cm)  
More than 50mm  
More than 50mm  
FAN  
FAN  
Air ow  
Wall Industries, Inc. • 37 Industrial Drive, Exeter, NH 03833 • Tel: 603-778-2300 • Toll Free: 888-597-9255 • Fax 603-778-9797  
website: www.wallindustries.com • e-mail: sales@wallindustries.com  
06/19/2014  
Page 6 of 7  
PSAEK3000HV SERIES  
Rev A  
Wall Industries, Inc.  
3000 Watts, AC/DC Switching Power Supplies  
COMPANY INFORMATION  
Wall Industries, Inc. has created custom and modified units for over 50 years. Our in-house research and development engineers will provide  
a solution that exceeds your performance requirements on-time and on budget. Our ISO9001-2008 certification is just one example of our  
commitment to producing a high quality, well-documented product for our customers.  
Our past projects demonstrate our commitment to you, our customer. Wall Industries, Inc. has a reputation for working closely with its  
customers to ensure each solution meets or exceeds form, fit and function requirements. We will continue to provide ongoing support for  
your project above and beyond the design and production phases. Give us a call today to discuss your future projects.  
Contact Wall Industries for further information:  
Phone:  
Toll Free:  
Fax:  
(603)778-2300  
(888)597-9255  
(603)778-9797  
E-mail:  
Web:  
Address:  
sales@wallindustries.com  
www.wallindustries.com  
37 Industrial Drive  
Exeter, NH 03833  
Wall Industries, Inc. • 37 Industrial Drive, Exeter, NH 03833 • Tel: 603-778-2300 • Toll Free: 888-597-9255 • Fax 603-778-9797  
website: www.wallindustries.com • e-mail: sales@wallindustries.com  
06/19/2014  
Page 7 of 7  

相关型号:

PSAEK-3000-30

AC/DC Switching Power Supplies
WALL

PSAEK-3000-300

AC/DC Switching Power Supplies
WALL

PSAEK-3000-36

AC/DC Switching Power Supplies
WALL

PSAEK-3000-400

AC/DC Switching Power Supplies
WALL

PSAEK-3000-48

AC/DC Switching Power Supplies
WALL

PSAEK-3000-60

AC/DC Switching Power Supplies
WALL

PSAEK3000

AC/DC Switching Power Supplies
WALL

PSAEK3000HV

AC/DC Switching Power Supplies
WALL

PSAES60

AC/DC Switching Power Supplies
WALL

PSAES60C-12S

AC/DC Switching Power Supplies
WALL

PSAES60C-15S

AC/DC Switching Power Supplies
WALL

PSAES60C-24S

AC/DC Switching Power Supplies
WALL