ECS130US18 [XPPOWER]
AC-DC Regulated Power Supply Module, 130W;型号: | ECS130US18 |
厂家: | XP POWER LIMITED |
描述: | AC-DC Regulated Power Supply Module, 130W 输出元件 |
文件: | 总5页 (文件大小:932K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
65/100/130 Watts
ECS Series
xppower.com
•
•
•
•
•
•
•
IT & Medical Safety Approvals
65/80/100 W - Convection-cooled Ratings
Class I & Class II Construction
Industry Standard 2”x 4”Package
<0.5 W No Load Input Power
Low Leakage Current
3 Year Warranty
Specification
Input
General
Efficiency
Isolation
• Up to 90% model dependent
Input Voltage
• 80-264 VAC (275 VAC ECS65)
(120-370 VDC), derate output power
<90 VAC, see derating curves
• 4000 VAC Input to Output, 2 x MOPP,
1500 VAC Input to Ground, 1 x MOPP,
500 VDC Output to Ground, 1 x MOPP
(1)
Input Frequency
Input Current
• 47-400 Hz
Switching Frequency
Power Density
• 65 KHz typical
• 65 W: 1.0/0.6 A typical at 115/230 VAC
100 W: 1.5/0.9 A typical at 115/230 VAC,
130 W: 1.9/1.1 A typical at 115/230 VAC
full load
• 40 A max at 230 VAC, cold start at 25 ˚C
• EN61000-3-2, class A
3
3
• 65 W: 7.7 W/in , 100 W: 10 W/in ,
3
130 W: 13 W/in
MTBF
• 65 W: 850 kHrs, 100 W: 834 kHrs,
130 W: 715 kHrs to MIL-HDBK-217F
at 25 ˚C, GB
Inrush Current
Power Factor
No Load Input Power • <0.5 W
Environmental
Operating Temperature • -20 ˚C (-40 ˚C, ECS130) to +70 ˚C derate
linearly from +50 ˚C at 2.5%/˚C to 50%
load at +70 ˚C.
Earth Leakage Current • 65/130 W: 260 µA at 264 VAC/60 Hz max
100 W: 230 µA at 264 VAC/60 Hz max
Input Protection
• Internal T3.15/T5 A/250 V fuse in line and
neutral
Cooling
• Convection & fan cooled ratings(see tables)
• 95% RH, non-condensing
• -40 ˚C to +85 ˚C
• 65-100 W: 3000 m, 130 W: 5000m
• 30 g pk, half sine, 6 axes
• 2 g rms, 5 Hz to 500 Hz, 3 axes
Operating Humidity
Storage Temperature
Operating Altitude
Shock
Output
Output Voltage
Output Voltage Trim
Initial Set Accuracy
Minimum Load
Start Up Delay
Start Up Rise Time
Hold Up Time
• 12-48 VDC (see tables)
•
•
10%
1%
Vibration
• No minimum load required
• 1 s typical
• 50 ms
EMC & Safety
Low Voltage PSU EMC • EN61204-3, high severity level
Emissions
• EN55011/22 level B conducted
EN55011/22 level A radiated, level B
Suffix ‘-B’ models
• EN61000-3-2, class A
• EN61000-3-3
• EN61000-4-2, 6 kV Contact, 15 kV Air
Discharge, Perf Criteria A
• EN61000-4-3, level 3 Perf Criteria A
• EN61000-4-4, level 3 Perf Criteria A
• EN61000-4-5, installation class 3
Perf Criteria A
• EN61000-4-6, level 3 Perf Criteria A
• EN61000-4-11, 30% 10 ms, 60% 100 ms,
100% 5000 ms, Perf Criteria A, B, B,
EN60601-1-2, 30% 500 ms, 60% 100 ms,
100% 10 ms, 100% 5000 ms, Perf Criteria
A, A, A, B - 230 VAC. Consult longform
datasheet for 115 V operation.
• 16 ms min at 115 VAC
Drift
•
•
•
0.2% after 20 min warm up
0.5% max
1%
Line Regulation
Load Regulation
Over/Undershoot
Transient Response
Harmonic Currents
Voltage Flicker
ESD Immunity
• 5% typical
• 4% max. deviation, recovery to within
1% in 500 µs for a 50-75-50% load
change
Radiated Immunity
EFT/Burst
Surge
Ripple & Noise
• 1% pk-pk, 20 MHz bandwidth
Overvoltage Protection • 115-140% Vnom, recycle input to reset
Overload Protection • 110-160%
Short Circuit Protection • Continuous trip and restart (hiccup mode)
Conducted Immunity
Dips & Interruptions
Temperature
Coefficient
• 0.05%/˚C
Safety Approvals
• IEC60950-1 CB report, CSA 22.2
No. 60950-1, UL60950-1, TUV EN60950-1
IEC60601-1 CB report, CSA 22.2
Notes
No. 60601-1, ANSI/AMMI ES60601-1,
TUV 60601-1, including risk management
1. Safety approvals cover frequency 47-63 Hz.
Equipment Protection • Class I & II (ECS65 Non ‘-B’ models,
Class
Class I only)
ECS65
Models and Ratings
Output Power
Output Voltage
Output Current
Model Number(1)
65 W
65 W
65 W
65 W
65 W
65 W
12.0 VDC
15.0 VDC
18.5 VDC
24.0 VDC
28.0 VDC
48.0 VDC
5.4 A
4.3 A
3.4 A
2.7 A
2.3 A
1.4 A
ECS65US12
ECS65US15
ECS65US18
ECS65US24
ECS65US28
ECS65US48
Notes
1. For Class B radiated emissions models, add suffix -B to model number. For covered versions, add suffix ‘-C’ to model number or order part no. ECM40/60 COVER
for standalone cover. Derate output power by 20% with cover. The cover is not suitable for Class II installations.
Mechanical Details
4.00 (101.6)
3.750 (95.25)
1.05
(26.7)
0.125 (3.17)
C4
1
2.00 (50.8)
1.75 (44.45)
2
1
C5
J1
T1
1
4
J2
0.95 (24.1)
0.96 (24.5)
0.25 Faston Ground Tab
0.125 (3.18)
0.20 (5.1)
Q1
0.14 (3.5)
SMD Component Height
0.20 (5.1)
4 X ø.156 (3.96) Mounting Holes
ø.312 (7.92) Clearance top and bottom
Input Connector J1
Molex PN 09-65-2038
Output Connector J2
Molex PN 09-65-2048
Pin 1
Pin 2
0.25” Faston
Line
Neutral
Earth
Pin 1
Pin 2
Pin 3
Pin 4
+V1
+V1
RTN
RTN
J1 mates with Molex Housing PN 09-50-1031, J2 mates with
Molex Housing PN 09-50-1041 and both with Molex Series 5194
Crimp Terminals
Notes
1. All dimensions in inches (mm).
2. Weight: 0.386 lbs (175 g)
Tolerance .xx = 0.02 (0.50); .xxx = 0.01 (0.25)
Derating Curve - ECS65 Models
100
90
100
90
Open Frame
80
80
70
60
50
40
70
60
50
40
37.5
30
80
85
90
275
75
40
50
60
-20
Input Voltage (VAC)
AmbientTemperature (ºC)
ECS100
Models and Ratings
Output Power
Output Voltage
Output Current
Model Number(1)
Forced Cooled (10 CFM)
Convection-cooled
100 W
100 W
100 W
100 W
100 W
100 W
80 W
80 W
80 W
80 W
80 W
80 W
12.0 VDC
15.0 VDC
18.0 VDC
24.0 VDC
28.0 VDC
48.0 VDC
8.3 A
6.7 A
5.5 A
4.2 A
3.6 A
2.1 A
ECS100US12
ECS100US15
ECS100US18
ECS100US24
ECS100US28
ECS100US48
Notes
1. For Class B radiated emissions models, add suffix -B to model number. For covered versions, add suffix ‘-C’ to model number or order part no. ECM40/60 COVER
for standalone cover. Derate output power by 20% with cover. The cover is not suitable for Class II installations. ‘-C’ not available for ‘-B’ models.
Mechanical Details
1.25 (31.8)
4.00 (101.6)
3.750 (95.25)
0.125 (3.18)
C4
Voltage
Adj.
1.750
2.00 +0.06/-0.00
(50.8 +1.5/-0.00)
(44.45)
J1
C5
T1
J2
Output Connector J2
Molex PN 09-65-2048
1.01
1.00
(25.4)
(25.7)
Pin 1
Pin 2
Pin 3
Pin 4
+V1
+V1
RTN
RTN
Q1
0.25 Faston
Ground Tab
0.20 (5.1)
0.14 (3.5)
0.125 (3.18)
0.20 (5.1)
SMD Component
Height
4 X ø.156 (3.96) Mounting Holes
Input Connector J1
ø.312 (7.92) Clearance top and bottom
Molex PN 09-65-2038
Pin 1
Pin 2
0.25” Faston
Line
Neutral
Earth
‘-B’ Model
4.50 (114.3)
3.75 (95.25)
1.25 (31.8)
0.37 (9.52)
J1 mates with Molex Housing
PN 09-50-1031, J2 mates with
Molex Housing PN 09-50-1041
and both with Molex Series
5194 Crimp Terminals
2.00 +0.06/-0.00
(50.8 +1.5/-0.00)
1.75
J1
(44.45)
Notes
J2
0.20
(5.1)
1. All dimensions in inches
(mm).
Tolerance .xx = 0.02
(0.50); .xxx = 0.01 (0.25)
2. Weight: 0.386 lbs (175 g)
1.00
1.01
(25.4)
(25.7)
0.20 (5.1)
0.14 (3.5)
0.125 (3.18)
SMD Component
Height
4 X ø.156 (3.96) Mounting Holes
ø.312 (7.92) Clearance top and bottom
0.10 (2.5)
0.25 Faston Ground Tab
Derating Curve - ECS100 Models
100
90
100
90
Force-cooled >10 CFM
Convection-cooled
80
80
70
60
50
40
70
60
50
40
30
Convection-cooled with cover
+70
80
85
90
264
-20
+40
+50
+60
Input Voltage (VAC)
Ambient Temperature (ºC)
ECS130
Models and Ratings
Output Power
Output Voltage
Output Current
Model Number(1)
Forced Cooled (10 CFM)
Convection-cooled
130 W
130 W
130 W
130 W
130 W
130 W
100 W
100 W
100 W
100 W
100 W
100 W
12.0 VDC
15.0 VDC
18.0 VDC
24.0 VDC
28.0 VDC
48.0 VDC
10.9 A
8.7 A
7.3 A
5.4 A
4.7 A
2.7 A
ECS130US12
ECS130US15
ECS130US18
ECS130US24
ECS130US28
ECS130US48
Notes
1. For covered versions, add suffix ‘-C’ to model number or order part no. ECM40/60 COVER for standalone cover, see derating curve.
The cover is not suitable for Class II installations. ‘-C’.
Mechanical Details
4.00 (101.6)
1.28
0.125 (3.17)
1.75 (44.45)
3.750 (95.25)
(32.5)
Voltage Adjust
C4
2.00 +0.06/-0.00
(50.8 +1.5/-0.00)
N
J1 2
1
4
1
T1
L
J2
C5
1.00 (25.4)
1.05 (26.7)
0.20 (5.1)
Q1
0.12 (3.18)
0.15 (3.8)
SMD COMPONENT HEIGHT
0.20 (5.1)
.25 FASTON
GROUND TAB
4X 0.156 (3.96) MOUNTING HOLES
0.312 (7.92) CLEARANCE TOP AND BOTTOM
Output Connector J2
Molex PN 09-65-2048
Input Connector J1
Notes
Molex PN 09-65-2038
1. All dimensions in inches (mm).
Tolerance .xx = 0.02 (0.50); .xxx = 0.01 (0.25)
2. Weight: 0.386 lbs (175 g)
Pin 1
Pin 2
Pin 3
Pin 4
+V1
+V1
RTN
RTN
Pin 1
Pin 2
0.25” Faston
Line
Neutral
Earth
J1 mates with Molex Housing PN 09-50-1031, J2 mates with Molex Housing PN 09-50-1041
and both with Molex Series 5194 Crimp Terminals
Derating Curve - ECS130 Models
130
130
120
110
120
110
Forced-cooled >10 CFM
Convection-cooled
Forced-cooled >10 CFM
Convection-cooled
100
90
100
90
80
70
80
70
60
60
Convection-cooled with cover
Convection-cooled with cover
50
40
30
20
10
50
40
30
20
10
80
90
100
264
-40
-20
0
50
60
70
Input Voltage (VAC)
Ambient Temperature (ºC)
ECS65/100/130
Mechanical Details
Covered Version (not available for ECS100-B Models)
4.49 (114.0)
2.52
Input Connector
Output Connector
(64.0)
0.25 (0.6) Ground
Faston Terminal
0.807
(20.50)
1.54
(39.0)
2 x M3 x 0.5 THD
0.16 (4.0)
Max Screw Penetration
4.055 (103.00)
4.055 (103.00)
0.22
(5.5)
0.22
(5.5)
0.79
(20.0)
0.984
(25.00)
4 x M3 x 0.5 THD
0.16 (4.0) Max Screw Penetration
Notes
1. All dimensions in inches (mm).
Tolerance .xx = 0.02 (0.50); .xxx = 0.01 (0.25)
2. Weight: 0.8 lbs (360 g)
Thermal Considerations - All Models
In order to ensure safe and reliable operation of the PSU in the most adverse conditions permitted in the end-use equipment, the temperature of the components
listed in the table below must not be exceeded. See mechanical drawing for component locations. Temperature should be monitored using K type thermocouples
placed on the hottest part of the component (out of any direct air flow).
Temperature Measurements (Ambient ≤ 50 °C)
Component
Max Temperature °C
110 °C
T1
C5
C4
Q1
100 °C
100 °C
110 °C
20-Jan-17
相关型号:
©2020 ICPDF网 联系我们和版权申明