TPS_RM4830 [CANDD]

MODULAR SWITCHED MODE RECTIFIER; 模块化开关式整流器
TPS_RM4830
型号: TPS_RM4830
厂家: C&D TECHNOLOGIES    C&D TECHNOLOGIES
描述:

MODULAR SWITCHED MODE RECTIFIER
模块化开关式整流器

开关
文件: 总4页 (文件大小:118K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
0RODUCT $ATA 3HEET  
ꢀꢁ !-0  
-/$5,!2 37)4#(%$ -/$% 2%#4)&)%2  
2-ꢀꢁꢂꢃ  
&%!452%3  
s
s
s
s
s
s
s
s
37)4#(%$ -/$%  
ꢅꢅ 0&#  
ꢇꢈ %&&)#)%.#9  
(/437!0 #!0!",%  
!54/-!4)# ,/!$ 3(!2).'  
#/-0!#4 3):%  
3(%,& -/5.4%$  
"%,,#/2% "!3%$ $%3)'.  
s
s
s
s
s
2%-/4% 2%34!24 &5.#4)/.  
&2/.4 0!.%, #522%.4 -%4%2  
"!44%29 /2 "!44%29,%33 /0%2!4)/.  
).4%,,)'%.4 ()'(6/,4!'% 3(54$/7.  
'5!2!.4%%$ ./ 3).',% 0!24 &!),52%7),,  
2%35,4 ). /54054 ()'( 6/,4!'%  
$%3#2)04)/.  
s
4($ ꢊꢇꢈ  
4HE 2-ꢀꢁꢂꢃ -ODULAR 3WITCHEDꢒ-ODE 2ECTIFIER IS ONE OF  
#ꢍ$ 4ECHNOLOGIESꢓ FAMILY OF RECTIFIERS THAT MAY BE USED IN  
MODULAR POWER PLANTSꢈ 4HIS UNIT WILL FUNCTION IN PARALLEL  
WITH ANY RECTIFIER WITH SIMILAR CURRENT SHARING CAPACITIESꢈ  
4HIS COMPACTꢉ VERSATILE AN
D E
FFICIENT UNIT IS IDEAL FOR USE IN  
SMALL TO MEDIUM CELLULAR AND 0#3 SITES
!'%.#9 !002/6!,3  
Contact Factory for Replacement Model  
)NTERNETꢇ HTTPꢇꢅꢅWWWꢈCDPOWERELECTRONICSꢈCOM  
0OWER %LECTRONICS $IVISIONꢂ 5NITED 3TATES  
ꢂꢀꢃꢃ % "RITANNIA $RIVE4UCSONꢉ !RIZONA ꢁꢊꢋꢃꢄ  
0HONEꢇ ꢁꢃꢃꢈꢊꢀꢋꢈꢌꢊꢂꢋ &AXꢇ ꢊꢌꢃꢈꢋꢋꢃꢈꢆꢂꢄꢆ  
0OWER %LECTRONICS $IVISIONꢂ %UROPE  
#ꢍ$ 4ECHNOLOGIES ꢎ0OWER %LECTRONICSꢏ ,TDꢈ  
ꢐꢂꢌ 3HANNON )NDUSTRIAL %STATE3HANNONꢉ #Oꢈ #LAREꢉ )RELAND  
4ELꢇ ꢑꢂꢊꢂꢈꢄꢐꢈꢀꢋꢀꢈꢐꢂꢂ  
&AXꢇꢑꢂꢊꢂꢈꢄꢐꢈꢀꢋꢀꢈꢐꢀꢐ  
2-ꢀꢁꢂꢃ ꢄꢅꢆꢁ 2%6 !  
0AGE ꢀ  
Input Specifications  
Parameter  
Operating Range  
Conditions  
45 - 65 Hz, single phase, no taps required  
Min  
106  
Typ  
Max  
264  
Units  
VAC  
Current (when supplying 30ADC at 48VDC)  
105VAC  
208VAC  
240VAC  
20  
10  
AAC  
AAC  
AAC  
%
8.5  
Efficiency  
>85  
Power Factor Correction (PFC)  
input range between 105VAC-264VAC  
>.99  
MEASUREMENTS OF RM4830  
Module  
Weight  
Height  
Depth  
Width  
Weight  
Height  
Depth  
Width  
14 lbs.  
5 U (8.75”)  
15.55”  
3.35”  
Shelf*  
21 lbs.  
5 U (8.75”)  
15.55”  
23” rack mount  
*These measurements are specifically for the 180A Power Shelf for up to 6 quantity RM 4830.  
Please contact factory for other shelf and power plant options.  
GENERAL FEATURES  
Current Limit  
Hot Swappable Modules  
When rectifier current reaches 30ADC - 32ADC, the unit  
will automatically limit the current down to short circuit con-  
ditions with no fold back.  
These shelf-mounted modules are easy and safe to install  
or remove while system is operational without affecting  
the overall system’s performance.  
LED Indicators  
Parallel Operation and Automatic Load Sharing  
A series of RM4830 rectifiers will automatically share equal  
amounts of the load current when operating in parallel  
within 5% of the average current for the load applied.  
The front panel includes a 10 segment yellow LED output  
current bar graph, a green normal operation LED, and a  
red rectifier failed LED.  
Safety  
N+1 Operation  
UL/CUL Recognized: UL 1950/CSA 950.  
File No.: E131694  
The rectifier can operate in true N + 1 redundacy mode.  
EMI filtering to FCC and VDE-0875 limits.  
Remote Equalize  
The rectifier output may be changed from float to equalize  
via remote signal.  
RM4830 6/98 REV A  
Page 2  
Output Specifications  
Parameter  
Conditions  
Min  
Typ  
Max  
Units  
Voltage Adjustment Range  
float voltage  
equalize voltage  
40  
40  
60  
60  
VDC  
VDC  
Regulation  
0-100% load within  
specified input voltage and frequency range  
within a 10 - 100% rating  
0.5  
10  
%
%
Load Current  
Filtering  
Voice band  
Wide band noise  
<32  
<250  
<40  
dBrnC  
mV p-p  
mVrms  
20 MHz bandwidth  
ENVIRONMENTAL  
Temperature  
Operating  
0
+32  
-50  
-58  
0.01  
0
+50  
122  
85  
°C  
°F  
Storage  
°C  
185  
°F  
Temperature Coefficient  
Humidity  
after half hour warm-up  
non-condensing  
V/°C  
%
95  
7000  
2133  
Altitude  
0
ft.  
0
m
Heat Dissipation  
Audible Noise  
@54V  
980  
Btu/hr  
dBa  
2 ft. from any vertical surface  
<65  
PROTECTION, ALARM AND CONTROL SYSTEMS  
Rectifier Failure Alarm (RFA)  
High Voltage Shutdown (HVSD)  
Problems occurring because of an unacceptable relation-  
ship between the output power and load conditions will  
cause a Rectifier Failure Alarm (RFA).This alarm consists  
of a red LED. Conditions which may lead to an RFA are:  
Low Current - Output current has decreased to below  
2% of its rated value.  
The unit’s built-in high voltage limit is permanently set at  
60.5VDC. When internal shutdown occurs, the unit may  
be restarted by a local switch or by a remote signal.  
Surge Protection  
The unit will withstand lightning and input surges of  
Unit Shutdown - Any shutdown occurrence due to  
overvoltage, external shutdown command, unacceptable  
ambient temperature conditions or low AC input voltage.  
Fan Malfunction - The fan has stopped operating or is  
not providing the airflow needed to cool the unit.  
Over Temperature - The ambient temperature has  
exceeded 50°C.  
6000V/3000A.  
Under Voltage Protection  
When input voltage is below 106 VAC (with tolerance),  
the rectifier’s operation is automatically inhibited.  
Output Circuit Protection Device (Fuse)  
The unit has one internal output protection fuse which is  
in series with the -48VDC output.  
RM4830 6/98 REV A  
Page 3  
Mechanical  
SIDE  
14.30  
1.25  
FRONT  
4.95  
+ .25  
3.35  
4.70  
+ .25  
FAN  
4830  
2.35  
+ .25  
4.35  
+ .25  
8.63  
2nd TEST  
1st TEST BURN-IN  
HI-POT  
QA  
PWR/RESET  
30 VOLTAGE  
FLT EQL  
27  
24  
21  
18  
15  
12  
9
6
3
Standard Options are shown, consult factory for other available options.  
The information provided herein is believed to be reliable; however, C&D TECHNOLOGIES assumes no responsibility for inaccuracies or omissions. C&D TECHNOLOGIES assumes  
no responsibility for the use of this information, and all use of such information shall be entirely at the user’s own risk. Prices and specifications are subject to change without notice.  
No patent rights or licenses to any of the circuits described herein are implied or granted to any third party. C&D TECHNOLOGIES does not authorize or warrant any C&D TECHNOLOGIES  
product for use in life support devices/systems or in aircraft control applications.  
RM4830 6/98 REV A  
Page 4  

相关型号:

TPS_RM4875

MODULAR SWITCH MODE RECTIFIER
CANDD

TPS_SX400

AC/DC POWER SUPPLY
CANDD

TPS_SX500

AC/DC POWER SUPPLY
CANDD

TPS_TX1000

1000 Watt, Single Output, AC/DC Power Supply
CANDD

TPS_TXD2000

AC/DC POWER SUPPLY
CANDD

TPT-13-6003

Temperature Compensated Amplifier 6 GHz - 13 GHz
TELEDYNE

TPT-13-6004

Temperature Compensated Amplifier 6 GHz - 13 GHz
TELEDYNE

TPT-13-6005

Temperature Compensated Amplifier 6 GHz - 13 GHz
TELEDYNE

TPT-13-6006

Temperature Compensated Amplifier 6 GHz - 13 GHz
TELEDYNE

TPT-13-6014

Temperature Compensated Power Amplifier 6 GHz - 13 GHz
TELEDYNE

TPT-13-6015

Temperature Compensated Power Amplifier 6 GHz - 13 GHz
TELEDYNE

TPT-13-6016

Temperature Compensated Power Amplifier 6 GHz - 13 GHz
TELEDYNE