PDRB-75-12 [CUI]
AC-DC DIN RAIL POWER SUPPLY;型号: | PDRB-75-12 |
厂家: | CUI INC |
描述: | AC-DC DIN RAIL POWER SUPPLY |
文件: | 总6页 (文件大小:712K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
For more information, please visit the product page.
date 05/08/2019
page 1 of 6
SERIES: PDRB-75 │ DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY
FEATURES
• universal AC input
• over current, over voltage, short circuit protection
• TUV certified
• EN55032 Class B
output
voltage
output
current
max
output
power
max
ripple
efficiency2
MODEL
and noise1
max
typ
(Vdc)
12
(A)
(W)
(mVp-p)
(%)
PDRB-75-12
PDRB-75-24
PDRB-75-48
6.3
3.13
1.6
75.6
75
100
100
150
87.5
88
24
48
76.8
89
Notes:
1. At full load, nominal input, 20 MHz bandwidth oscilloscope, with 0.1 µF ceramic and 47 µF electrolytic capacitors on the output,
2. At 230 Vac, 50 Hz, full load.
3. All specifications are measured at Ta=25°C, nominal input voltage, and rated output load unless otherwise specified.
PART NUMBER KEY
PDRB-75- XX
Base Number
Output Voltage
cui.com
For more information, please visit the product page.
CUI Inc │ SERIES: PDRB-75 │ DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY
date 05/08/2019 │ page 2 of 6
INPUT
parameter
conditions/description
min
typ
max
units
90
127
264
370
Vac
Vdc
voltage
frequency
current
47
63
Hz
at 115 Vac, full load
at 230 Vac, full load
1.4
0.9
A
A
at 110 Vac, full load, cold start
at 220 Vac, full load, cold start
20
35
A
A
inrush current
input to output
input to FG
3.5
3.5
mA
mA
leakage current
input fuse
3.15A/250 Vac
OUTPUT
parameter
conditions/description
min
typ
max
5,000
±1
units
µF
capacitive load
initial set point accuracy
line regulation
load regulation
%
at full load, 100~264 Vac
at 230 Vac, 100~0% load
±1
%
±1
%
via built in trim pot
12 Vdc output model
24 Vdc output model
48 Vdc output model
12
24
48
14
28
55
Vdc
Vdc
Vdc
adjustability
start-up time
rise time
at 115/230 Vac, full load
2.0
s
output voltage rise from 10~90% of output
voltage
60
ms
at 115 Vac, full load
at 230 Vac, full load
10
20
ms
ms
hold-up time
switching frequency
LED indicator
at Vi nom, full load
65
kHz
when LED is on, the power supply is operating and
DC output is good
cui.com
For more information, please visit the product page.
CUI Inc │ SERIES: PDRB-75 │ DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY
date 05/08/2019 │ page 3 of 6
PROTECTIONS
parameter
conditions/description
min
120
110
typ
typ
max
150
150
units
%
over voltage protection
over current protection
short circuit protection
output shutdown, must recycle power to recover
hiccup, auto recovery
%
hiccup, auto recovery
SAFETY & COMPLIANCE
parameter
conditions/description
input to output for 1 minute at 10 mA
input to FG for 1 minute at 10 mA
output to FG for 1 minute at 10 mA
input to output at 500 Vdc
EN 60950-1
min
3,000
1,500
500
max
units
Vac
isolation voltage
Vac
Vac
isolation resistance
safety approvals
safety class
5
MΩ
class I
conducted emissions
radiated emissions
ESD
EN55032, Class B
EN55032, Class B
EN61000-4-2, Level 4, Criteria B, Air Discharge: ±8 kV; Contact Discharge: ± 4 kV
radiated immunity
EFT/burst
EN61000-4-3, Level 3, Criteria A, 80-1000 MHz, 3 V/M, 80% modulation (1 kHz)
EN61000-4-4, Level 4, Criteria B, ±1 kV
surge
EN61000-4-5, Level 4, Criteria B, Common Mode: 2 kV; Differential Mode: 1 kV
pollution degree
degree of protection
MTBF
2
IP20
as per MIL-HDBK-217F, at 220 Vac, full load, 25°C
500,000
hours
RoHS
yes
Notes:
4. The power supply is considered a component which will be installed into final equipment. The final equipment still must be tested to meet the necessary EMC directives.
ENVIRONMENTAL
parameter
conditions/description
min
-25
-40
5
typ
max
70
units
°C
operating temperature
storage temperature
operating humidity
storage humidity
altitude
see derating curves
85
°C
non-condensing
non-condensing
90
%
5
95
%
2,000
m
cui.com
For more information, please visit the product page.
CUI Inc │ SERIES: PDRB-75 │ DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY
date 05/08/2019 │ page 4 of 6
MECHANICAL
parameter
conditions/description
min
typ
max
units
mm
kg
dimensions
126.00 x 102.50 x 34.50 (4.960 x 4.035 x 1.35 inches)
weight
0.36
cooling
natural convection
input/output connector
accepts 24~12 AWG wire
MECHANICAL DRAWING
units: mm
tolerance: ±0.3
unless otherwise noted
ꢊꢌ0ꢇꢍ2XWSXWꢍ7HUPLQDOV
3RWHQWLRQPHWHUꢍ2XWSXWꢍ$GMXVW
'&ꢍ2.ꢍ/('
TERMINAL 1
CONNECTIONS
TERMINAL
Function
1
2
3
L
N
ꢇꢌ0ꢇꢍ,QSXWꢍ7HUPLQDOV
TERMINAL 2
CONNECTIONS
ꢁꢉ
ꢀꢃꢁꢄꢅfꢀ
ꢀꢃꢋfꢀ
TERMINAL Function
ꢇꢊꢄꢅfꢀ
1
2
3
4
+V
+V
-V
-V
INSTALLATION
DIN RAIL
TS35/7.5 or TS35/15
24~12 AWG
(4.0 mm2)
Wire Range
Strip Length
Screw Torque
7 mm
0.5 N·m
cui.com
For more information, please visit the product page.
CUI Inc │ SERIES: PDRB-75 │ DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY
date 05/08/2019 │ page 5 of 6
DERATING CURVES
Temperature Derating Curve
(Output Load vs. Ambient Tempearature)
12 Vdc output models
all other models
100
80
75
60
40
20
-25
0
10
20
30
40
50 55
60
70
80
Ambient Temperature (°C)
Temperature Derating Curve
(Output Load vs. Input)
100
90
80
60
40
20
90
100
110
120
135
155 165
175
230
264
Input Voltage (Vac) 60Hz
cui.com
For more information, please visit the product page.
CUI Inc │ SERIES: PDRB-75 │ DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY
date 05/08/2019 │ page 6 of 6
REVISION HISTORY
rev.
description
date
1.0
initial release
05/08/2019
The revision history provided is for informational purposes only and is believed to be accurate.
Headquarters
20050 SW 112th Ave.
Tualatin, OR 97062
800.275.4899
Fax 503.612.2383
cui.com
techsupport@cui.com
CUI offers a two (2) year limited warranty. Complete warranty information is listed on our website.
CUI reserves the right to make changes to the product at any time without notice. Information provided by CUI is believed to be accurate and reliable. However, no responsibility is
assumed by CUI for its use, nor for any infringements of patents or other rights of third parties which may result from its use.
CUI products are not authorized or warranted for use as critical components in equipment that requires an extremely high level of reliability. A critical component is any component of a
life support device or system whose failure to perform can be reasonably expected to cause the failure of the life support device or system, or to affect its safety or effectiveness.
相关型号:
©2020 ICPDF网 联系我们和版权申明