FCX –A SERIES
FCX – AX SERIES
REMOTE SEAL TYPE
PRESSURE TRANSMITTER
...
FHB, FKB 3
DATA SHEET
The FCX – AX pressure transmitter accurately measures
gauge pressure and transmits a proportional 4 to 20mA signal.
The transmitter utilizes a unique micromachined capaci-
tance silicon sensor with state-of -the-art microprocessor
technology to provide exceptional performance and func-
tionality.
Totally welded construction of the seals assures excel-
lent reliability in high temperature and highly corrosive
process conditions.
7. Dry calibration without reference pressure
FEATURES
1. High accuracy
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry
calibration without reference pressure is at equal level
as wet calibration.
0.2% accuracy for all calibrated spans is a standard fea-
ture for all GP models covering 6.4kPa{0.064bar} range
to 50000kPa{500bar} high pressure range. 0.1% accu-
racy is available as option. Fuji's micro-capacitance sili-
con sensor assures this accuracy for all elevated or sup-
pressed calibration ranges without additional adjustment.
2. Minimum environmental influence
The "Advanced Floating Cell" design which protects the
pressure sensor against changes in temperature, and
overpressure substantially reduces total measurement
error in actual field applications.
SPECIFICATIONS
Functionalspecifications
Type:
Model FHB: 4 to 20mA
Model FKB: 4 to 20mA with digital signal
Service:
Liquid, gas, or vapour
3. Replaceable Communication Module
Span,range,andoverrangelimit:
Fuji micro-electronics manufacturing technology offers
replaceable communication module that makes FCX – AX
transmitter very unique in design. In case of change in
communication protocol, all that needs to be done is just
to replace the module and the transmitter gets upgraded
to the new version.
4. Fuji/HART bilingual communication module
The communication module is "bilingual" to speak both Fuji
proprietary protocol and HART. Any HART compatible
devices can communicate with FCX–AX series transmit-
ters.
Span limit [kPa]{bar}
Overrange
limit
[MPa] {bar}
Range limit
[kPa]{bar}
Type
Min.
Max.
FHB/FKB
64
FHB
6.4
{0.064}
50
{0.5}
300
{3}
1000
{10}
5000
{50}
FKB
0.64
F
F
F
F
F
B
B
B
B
B
1
2
3
4
5
–64 to +64
1
{0.0064} {0.64}
{–0.64 to +0.64} {10}
5
500
{5}
–100 to +500
{–1 to +5}
–100 to +3000
{–1 to +30}
–100 to +10000
{–1 to +100}
–100 to +50000
{–1 to +500}
1.5
{15}
9
{90}
15
{150}
75
{750}
{0.05}
30
{0.3}
100
{1}
3000
{30}
10000
{100}
50000
{500}
5. Application flexibility
Various options that render the FCX – AX suitable for
almost any process applications include:
500
{5}
Remark: To minimize environmental influence, span should be greater
than 1/40 of the max. span in most applications.
—
Analog indicator at either the electronics side or ter-
minal side
—
Lower range limit (vacuum limit) ;
—
—
—
—
—
—
Full range of hazardous area approvals
Built-in RFI filter and lightning arrester
4 12 -digits LCD meter
Stainless steel electronics housing
Wide selection of materials
Silicone fill sensor: See Fig. 1
Fluorinated fill sensor: Atmospheric pressure
Conversion factors to different units;
1MPa=103kPa=10bar=10.19716kgf/cm2=145.0377psi
1kPa=10mbar=101.9716mmH2O=4.01463inH2O
—
High temperature, high vacuum seals
Output signal:
Model FHB: 4 to 20mA DC 2-wire
6. Burnout current flexibility (Under Scale: 3.2 to 3.8mA,
Over Scale: 20.8 to 21.6mA)
Burnout signal level is adjustable using Model FXW hand
Held Communicator (HHC) to comply with NAMUR NE43.
(Available for amplifier unit from version 24 and FXW(HHC) version
5.3.)
Model FKB: 4 to 20mA DC with digital signal super-
imposed on the 4 to 20mA signal.
Power supply:
Transmitter operates on 10.5V to 45V DC
at transmitter terminals.
10.5V to 32V DC for the units with op-
tional arrester.
EDSX5-72
Date
Mar. 15, 1999
...
FHB, FKB 3
Load limitations: see figure below
[Ω]
Model FHB: Unless otherwise specified in the order,
the transmitter will be shipped in “Output
Hold” mode.
(Output signal just before failure happens
is maintained.)
2000
1533Ω
Model FKB: Selectable from HHC
“Output Hold”:
1500
Output signal is hold as the value just be-
fore failure happens.
“Output Overscale”:
1000
600Ω
Operating
area
Approx. 21.6mA
500
(Adjustable within the range 20.8mA to
21.6mA from HHC)
“Output Underscale”:
24V
45V
50
250
10 16.1
10.5V
[ V ]
Approx. 3.8mA
(Adjustable within the range 3.2mA to
3.8mA from HHC)
Power voltage
Note: For communication with HHC (Model: FXW), min. of 250Ω is required.
Hazardous locations: (Approval pending)
4
3.8
20 20.8
3.2
Over scale
Burnout
Type N
Nonincendive
Authorities
Flameproof
Intrinsic safety
0
21.6
Probable over range
BASEEFA
Factory
Mutual
Ex ds IIC T5, T6
Class I II III
Div. 1
EEx ia IIC T4, T5
Class I II III
Div. 1
Ex N II T5
Class I II III
Div. 2
Normal operating range
Probable under range
Under scale
Burnout
Groups B thru. G Groups A thru. F
Groups A thru. G
Class I II III
Div. 2
CSA
Class I II III
Div. 1
Class I II III
Div. 1
Loop-check output:
Model FHB: Transmitter can output constant signal of
4mA, 12mA, or 20mA if MODE SWITCH
is set to the loop check mode.
Groups C thru. G Groups A thru. G Groups A thru. G
RIIS
SAA
Ex ds IIB+H T4
Ex d II C T5,2T6
IP 66/67
—
—
Ex n II C T5, T6
IP 66/67
Ex ia II C T5, T6
IP 66/67
Model FKB: Transmitter can be configured to provide
constant signal 3.8mA through 21.6mA by
HHC.
Zero/span adjustment:
Model FHB: Zero is adjustable from the external ad-
justment screw.
Temperature limit:
Ambient: –40 to +85°C
The adjustment screw can also function to
adjust span when MODE SWITCH (lo-
cated on the electronics unit) is in the span
mode. INHIBIT mode to disable the ad-
justment screw is also available.
(–20 to +80°C for LCD indicator)
(– 40 to +60°C for arrester option)
(–10 to +60°C for fluorinated oil fill transmitter)
(–10 to +85°C for silicone oil "H", "S", "K")
(+20 to +85°C for silicone oil "J", "T")
For explosionproof units (flameproof or intrinsic safety),
ambient temperature must be within the limits speci-
fied by each standard.
Model FKB: Zero and span are adjustable from the
HHC. Zero is also adjustable externally
from the adjustment screw.
Adjustable electrical damping.
Model FHB: The time constant is adjustable to 0, 0.3,
1.2, 4.8, or 19.2 seconds.
Damping:
Process:
Code in the
13th digit of
"Code symbols"
Lower limit
of
static press.
Process
temperature
Fill fluid
Model FKB: The time constant is adjustable between 0
to 38.4 seconds.
Fluorinated oil W, A and D
–20 to 120°C Atmospheric
pressure
Zero elevation/suppression:
Silicone oil
H
–15 to 250°C
Zero can be elevated or suppressed within
the specified range limit of each sensor
model.
J
85 to 300°C
Y and G
–40 to 120°C 2.7kPa abs
{20mmHg
abs}
S
T
–15 to 250°C
Normal/reverse action:
85 to 300°C
Selectable by moving a jumper pin located
on the electronics unit.
0.13kPa abs
{1mmHg abs}
or more
K
–15 to 200°C
Indication:
Analog indicator or 412 -digit LCD meter, as
specified.
Storage: –40 to +90°C
Burnout direction:If self-diagnostic detect transmitter fail-
ure, the analog signal will be driven to ei-
ther “Output Hold”, “Output Overscale”
or “Output Underscale” modes.
2
Humidity limit:
Communication: (Model FKB only)
With HHC (Model FXW, consult Data
0 to 100% RH
Step response: Time constant: 0.3s (with 1.5m capillary)
Dead time: approximately 0.3s
(without electrical damping)
Dielectric strength:
Sheet No. EDS8-47), following informa-
tion can be remotely displayed or recon-
figured.
500V AC, 50/60Hz 1 min., between circuit
and earth.
Insulation resistance:
Items
Display
Set
v
More than 100MΩ/500V DC.
v
v
Tag No.
Turn-on time:
4 sec.
Model No.
v
Internal resistance for external field indicator:
Serial No.
v
—
v
12Ω or less
Engineering unit
Range limit
v
v
—
v
v
Measuring range
Damping
Physical specifications
v
v
Output mode
Burnout direction
Adjustment
Output adjust
Data
v
v
Electrical connections:
G1/2, 1/2-14 NPT, Pg13.5, or M20 × 1.5
conduit, as specified.
Process connections:
v
v
v
v
—
v
v
JIS, ANSI, or DIN raised face flanges or
screw connection JIS/ISO G1 external
thread.
—
—
—
v
v
Self diagnoses
Printer
—
v
Refer to "Code symbols."
External switch lock
Transmitter display(*)
Process-wetted parts material:
v
v
Diaphragm: 316L stainless steel, Hastelloy-C
Monel, Tantalum, Titanium or
Zirconium
Note: (*) HHC's version must be more than 5.0 (or
FXW
1– 2), to use this function.
Flange face:316 stainless steel, Hastelloy-C
Monel, Tantalum, Titanium or
Zirconium
Extension: 316 stainless steel, Hastelloy-C
(Refer to "Code symbols")
Performance specifications
Non-wetted parts material:
Accuracy rating: (including linearity, hysteresis, and re-
Electronics housing: Low copper die-cast
aluminum alloy (standard), finished
with polyester coating, or 316 stainless
steel (SCS14 per JIS G5121), as speci-
fied.
Capillary: In case of 13th code "Y, W, G, A,
D", PVC armored stainless steel.
In case of 13th code "H, J, S, T, K",
stainless steel armored stainless steel.
Mounting flange: 304 stainless steel or
carbon steel
peatability)
(Standard)
For spans greater than 1/10 of URL: ±0.2% of span
For spans below 1/10 of URL (Model FKB only):
0.1 × URL
±
0.1+0.1
% of span
(
)
Span
(Option) Not available for Max span 50000kPa model.
For spans greater than 1/10 of URL: ±0.1% of span
For spans below 1/10 of URL (Model FKB only):
0.1 × URL
±
0.05+0.05
% of span
(
)
Span
Fill fluid: Silicone oil (standard) or fluori-
nated oil (Daifloil)
Linearity:
Stability:
0.1% of calibrated span
±0.2% of upper range limit (URL) for 24
Mounting bracket: Carbon steel with ep-
oxy coating or 304 stainless steel, as
specified
months
Temperature effect:
Effect per 28°C change between the lim-
Environmental protection:
its of –40°C and +85°C
IEC IP67 and NEMA 4X
(Standard)
(Option)
Zero shift: ±0.35% of URL
Total effect: ±0.5% of URL
Zero shift: ±0.25% of URL
Total effect: ±0.275% of URL
Mounting:
On 60.5mm (JIS 50A) pipe using mount-
ing bracket, direct wall mounting
Transmitter approximately 10kg without
options.
Add; 0.5kg for mounting bracket
0.8kg for indicator option
4.5kg for stainless steel housing
option
1.5kg per 50mm extension of diaphragm
Mass {weight}:
Overrange effect: Zero shift; 0.2% of URL for any overrange
to maximum limit
Supply voltage effect:
Less than 0.05% of calibrated span per
10V
RFI effect:
Less than 0.2% of URL for the frequen-
cies of 20 to 1000MHz and field strength
30 V/m when electronics covers on.
(Classification: 2-abc: 0.2% span per
SAMA PMC 33.1)
3
...
FHB, FKB 3
Optional features
ACCESSORIES
Indicator:
A plug-in analog indicator (1.5% accuracy)
Hand-held communicator:
can be housed in the electronics compart-
ment or in the terminal box of the hous-
ing.
(Model FXW, refer to Data Sheet No.
EDS8-47)
Communication module: (Standard for FKB)
An optional 4 21 digits LCD meter is also
available.
By adding communication module, re-
mote setting function becomes available
Arrester:
A built-in arrester protects the electronics
from lightning surges.
Lightning surge immunity:
4KV (1.2 × 50µs)
for FHB.
Remark: When the communication module is con-
nected, the operation mode of external
zero/span adjustment screw is limited to
zero adjustment only.
Oxygen service: Special cleaning procedures are followed
throughout the process to maintain all pro-
cess wetted parts oil-free.
The fill fluid is fluorinated oil.
Chlorine service: Oil-free procedures as above. Includes
fluorinated oil for fill.
Not available with material code “W”.
Degreasing:
Process-wetted parts are cleaned, but the
fill fluid is standard silicone oil. Not for use
on oxygen or chlorine measurement.
Vacuum and high temperature service:
Special silicone oil and filling procedure
are applied.
See below figure.
Silicone (Code Y,G)
[kPa abs]
{mbar abs}
Silicone (Code S)
[kPa abs]
{mbar abs}
Silicone (Code T)
Sealing liquid:Silicone (Code K)
Operating arear
101
{1010}
101
{1010}
53.3
{533}
Operating arear
13.3
{133}
Non-operating
area
0.27
{2.7}
0.13
{1.3}
2.7
{27}
–40 –15
60 85 120
Process temperature[°C ]
200 230 250
300
–15
100
200
Process temperature[°C ]
Fig. 1 Relation between process temperature and
operating pressure
Fig. 2 Relation between process temperature and
operating pressure
Customer tag:
A stainless steel tag for customer tag data
is wired to the transmitter.
Coating of cell: Cell's surface is finished with epoxy/poly-
urethane double coating. Specify if envi-
ronment is extremely corrosive.
The product conforms to the requirements of the
Electromagnetic compatibility Directive 89/336/EEC as
detailed within the technical construction file number
TN510412. The applicable standards used to demonstrate
compliance are :-
EMS (Immunity) EN50082-1 : 1992
Test
specification
Basic
standard
Performance
criteria
No. Test item
Electrostatic
discharge
1
8kV (Air)
IEC 801-2:1984
IEC 801-3:1984
B
Radio-frequency 27-500MHz
electromagnetic 3V/m
field.
2
3
A
EMI (Emission)
EN50081-1 : 1992
(Unmodulated)
Test item
Frequency range
Basic standard
0.5kV, 5/50
(Tr/Th) ns
5kHz Rep.
Fast transients
common mode
Applicable Electro-
magnetic Radiation
Disturbance
IEC 801-4:1988
B
EN55022
Class B
30-1000MHz
"LVD - The transmitter is not covered by the requirements
of the LVD standard."
4
CODE SYMBOLS
1
2
3
4
5
6
7
8
9 10 11 12 13
Description
3
Type
4 to 20mA, Output type
4 to 20mA with digital signal, Output type
FHB
FKB
Conduit connection
G 1/2
1/2-14NPT
Pg 13.5
S
T
V
W
M20 × 1.5
Flanges
Ranges
Flange size and rating
1
2
3
4
5
Mounting flange
0
1
2
3
4
5
6
7
8
JIS 10K 80A
JIS 10K 100A
JIS 30K 50A
ANSI/JPI 150LB "3"
ANSI/JPI 150LB "4"
ANSI/JPI 600LB "2"
DIN PN16/40 DN80
DIN PN16 DN100
DIN PN40 DN50
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
304 stainless
steel
*
*
*
*
A
B
C
D
E
F
G
H
J
JIS 10K 80A
JIS 10K 100A
JIS 30K 50A
ANSI/JPI 150LB "3"
ANSI/JPI 150LB "4"
ANSI/JPI 600LB "2"
DIN PN16/40 DN80
DIN PN16 DN100
DIN PN40 DN50
Screw type, JIS/ISO G1
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
Carbon steel
*
*
*
*
K
*
*
P
Q
R
3 inch wafer
4 inch wafer
2 inch wafer
*
*
*
*
*
*
*
None
(wafer type)
Span limit (*2) [kPa]{bar}
FHB/FKB
1
2
3
4
5
6.4/0.64…64/64
{0.064/0.0064…0.64/0.64}
50/5…500/500
{0.5/0.05…5/5}
300/30…3000/3000
{3/0.3…30/30}
1000/100…10000/10000
{10/1…100/100}
5000/500…50000/50000
{50/5…500/500}
Available only with
material code "W"
}
Material/diaphragm extension
Diaphragm
Flange face
Diaph. extension [mm]
(*1)
W
A
B
C
D
0
50
316L stainless
steel
316 stainless
steel
100
(*3)
150
}
200
H
F
G
K
L
0
50
Hastelloy-C
Hastelloy-C
100
150
200
Monel
Monel
M
T
P
R
0
0
0
Tantalum
Titanium
Zirconium
Tantalum
Titanium
Zirconium
(*4)
}
0
Notes: * (1) If range 4 or 5 is selected, specify material "W" in any cases.
(2) 100: 1 turn down is possible for model FKB, but should be used at a span greater than
1/40 of the maximum span for better performance.
(3) In case of 7th digit code "A", "B", "C", "D" and 13th digit code "S", "T", "K", 5th digit code
“1“,“4“,“7“,“B“,“E“,“H“,“Q“ is available.
(4) In case of 6th digit code "2",“3“ and 5th digit “0“,“3“,“6“,“A“,“D“,“G“,“P“ is available.
5
...
FHB, FKB 3
1
2
3
4
5
6
7
8
9
10 11 12 13
14 15
F H B
F K B
3
3
Description
Indicator and arrester
Indicator
None
Arrester
None
None
None
None
Yes
Yes
Yes
A
B
D
J
E
F
H
K
L
P
Q
S
Analog, 0 to 100% linear scale
Analog, custom scale
Analog, double scale
None
Analog, 0 to 100% linear scale
Analog, custom scale
Analog, double scale
Digital, 0 to 100%
Digital, custom scale
Digital, 0 to 100%
Digital, custom scale
Yes
None
None (Model FKB only)
Yes
Yes (Model FKB only)
Approvals for hazardous locations (Approval pending)
A
B
C
D
E
M
N
H
J
K
P
R
T
Q
None (for ordinary locations)
JIS, Flameproof (Conduit seal)
(Available for 4th digit code “S“)
JIS, Flameproof (Cable gland seal) (Available for 4th digit code “S“)
FM, Flameproof (or explosionproof) (Available for 4th digit code “T“)
CSA, Flameproof (or explosionproof) (Available for 4th digit code “T“)
BASEEFA, Flameproof (Conduit seal)
BASEEFA, Flameproof (Cable gland seal) (Conduit connection G 1/2 only)
FM, Intrinsic safety and nonincendive
CSA, Intrinsic safety and nonincendive
CENELEC, Intrinsic safety
CENELEC, Intrinsic safety and BASEEFA, Type N
SAA Flameproof (Conduit seal)(Available for 4th digit cord (S,T,W)
SAA Intrinsic safety (Available for 4th digit cord (S,T,W)
SAA Type–N (non-sparking)(Available for 4th digit cord (S,T,W)
Capillary and mounting bracket
Capillary
Mounting bracket
A
B
G
C
H
J
K
D
E
L
1.5 m
Carbon steel
Carbon steel
Carbon steel
Carbon steel
Carbon steel
Carbon steel
Carbon steel
Stainless steel
Stainless steel
Stainless steel
Stainless steel
Stainless steel
Stainless steel
Stainless steel
3
5
6
7
8
(*1)
(*1)
10 (*1)
1.5
3
5
F
6
7
8
(*1)
(*1)
M
N
P
10 (*1)
Stainless steel parts (*2)
Stainless steel tag plate
Stainless steel elec. housing
Coating of cell
Y
B
C
E
M
N
P
None
Yes
None
Yes
None
Yes
None
Yes
None
None
Yes
None
None
None
None
Yes
Yes
Yes
Yes
None
None
Yes
Q
Yes
Yes
Special applications and fill fluid
Treatment
Fill fluid
Silicone oil
Y
W
G
A
D
H
J
S
T
K
None (standard)
None (standard)
Degreasing
Oxygen service
Chlorine service
High temp. 250°C
High temp. 300°C
High temp. and vacuum (250°C) Silicone oil
High temp. and vacuum (300°C) Silicone oil
High temp. and high vacuum
Fluorinated oil
Silicone oil
Fluorinated oil (7th digit code "W", "A", "B", "C" and "D")
Fluorinated oil (7th digit code "H", "F", "G", "K", "L" and "T")
Silicone oil
Silicone oil
(*3)
• Available for 6th digit code "1", "2" or "3".
In case of 13th code "S", "T", "K", available for
6th digit code "2" only.
• Available for 7th digit code "W", "A", "B", "C" or
Silicone oil
"D".
Teflon membrane
Y
C
None
Yes (Available for the 5th digit code "0", "2", "3", "5", "6", "8", "A", "C", "D", "F", "G", "J", "P", "R".
and 7th digit code "W", "H", "M", "T", "P", "R".)
Bolt/nut
None
(6th digit code "1", "2", "3")
Y
A
B
E
F
Cr-Mo alloy hexagon socket head cap screw/carbon steel nut
Cr-Mo alloy hexagon bolt/nut
(6th digit code "4", "5")
}
}
304 stainless steel/304 stainless steel
630 stainless steel/304 stainless steel
(6th digit code "4")
(6th digit code "5")
(*4)
Notes: * (1) Available for 5th digit code "0, 1, 3, 4, 6, 7, A, B, D, E, G, H, P, Q and 13th digit code "Y,
W, G, A, D". Inquire about in case of 13th other code.
(2) Not applicable to carbon steel flange material.
(3) Treatment; None
(4) In case of tropical use, select a stainless bolts and nuts.
6
OUTLINE DIAGRAM (Unit:mm)
In case of 4th
digit code
“S,V,W,X“
Fastener
Zero/span ADJ. screw
Mtg.pipe
JIS 50A (2")
(In case of 10th
U - Bolt M8
digit code
“B,C,M,N“)
Up
Down
30
38
“A“
Conduit conn.
4 Holes
9 dia
224
58
N holes h DIA.
“B“
Cable gland (option)
see note
Inner of gasket
Conduit conn.
No flange is attached
in case of 5th digit code
“P,Q,R”.
Earth terminal
(both side)
see table 1
51
71
191
(27)
20
t
L
Detail “A“
(Conduit conn.)
Detail “B“
ø13
ø15
With field ind .
(option)
J
G1/2
S
See table 1
2-M8 × 12
L
Mass approx.(kg)
9.5
7th digit code
11th digit code
S
(m)
1.5
A
D
W
H
M
T
0
B
E
3
5
6
7
8
50
70
P
G
L
R
120
A
F
50
100
150
200
10.5
11.5
12
C
F
øD øE øF øG øH
t
P
N-øh
Flange
B
G
H
M
150 126 100 73 38 118 8–19 JIS–10K–-80A
175 151 103 96 38 143 8–19 JIS–10K–100A
185
210
165
191
C
K
J
N
130
152.5 126 100 73 44 118 4–20 ANSI/JPI
–150LB–3"
84 52 48 42
50 8–19 JIS–30K–50A
D
L
12.5
K
P
10
190.5 151 103 96 44 143 8–20 ANSI/JPI
229
Conduit conn.
4th digit
code
Earth
terminal
–150LB–4"
CONNECTION
DIAGRAM
J
K
M
8
165 127
84 52 48 45.5 50 8–20 ANSI/JPI
–600LB–2"
S
T
G1/2
17
16
M4
S
T
V
W
X
–
+
CK+ CK–
1/2
5
No. 8
1
2
3
200 160 126 100 73 44 118 8–18 DIN PN40 DN80
220 180 151 103 96 40 143 8–18 DIN PN16 DN100
–14NPT
–32UNC
H
K
B
F
3
4.5
5
V
Pg13.5
8
M4
M4
165 125
84 52 48 40 50
4–18 DIN PN40 DN50
16
W
M20 × 1.5
+
–
Table 1
Note) : Cable gland is supplied in case of flameproof packing type.
ø11 cable is suitable.
7
...
FHB, FKB 3
Fastener
(In case of 10th
digit code
Zero/span ADJ. screw
In case of 4th
digit code
“S,V,W,X“
Mtg.pipe
JIS 50A (2")
“B,C,M,N“)
U - Bolt M8
Up
S
Down
38
30
“A“
4 Holes
9 dia
Conduit conn.
224
58
With field ind .
(option)
Cable gland (option)
see note
“B“
Conduit conn.
51
71
191
(27)
Earth terminal
(both side )
see table 1
G1
Packing
-0.1
ø23.6
-0.2
-0.1
-0.2
ø30
Detail “B“
ø13
Detail “A“
(Conduit conn.)
ø15
2–M8 12
J
G1/2
50
70
See table 1
120
Conduit conn.
11th digit code
S (m)
1.5
4th digit
code
Earth
terminal
C
D
17
16
8
E
A
D
S
T
G1/2
8
M4
1/2-14NPT
Pg13.5
5
No.8-32UNC
3
5
6
7
8
B
E
V
4.5
5
M4
M4
M20 × 1.5
W
16
G
L
CONNECTION
DIAGRAM
Table 1
C
F
–
+
CK+ CK–
H
M
+
–
S
V
H
M
T
T
V
J
N
H
F
B
K
W3
K
W
X
K
P
10
Note) : Cable gland is supplied in case of flameproof packing type.
ø11 cable is suitable.
Head office
Sales Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202
11-2 Osaki 1-chome, Shinagawa-ku, Tokyo, 141-0032 Japan
Phone: 81-3-5435-7111
http://www.fujielectric.co.jp/eng/sg/KEISOKU/welcome.htm
Fax: 81-42-585-6187, 6189
Printed in Japan
Information in this catalog is subject to change without notice.