BSM-7100-1

更新时间:2024-09-18 22:07:44
品牌:GAMEWELL-FCI
描述:Compact Analog Addressable Fire Alarm Control Panel

BSM-7100-1 概述

Compact Analog Addressable Fire Alarm Control Panel

BSM-7100-1 数据手册

通过下载BSM-7100-1数据手册来全面了解它。这个PDF文档包含了所有必要的细节,如产品概述、功能特性、引脚定义、引脚排列图等信息。

PDF下载
7100 Series  
Description  
Compact Analog Addressable  
Fire Alarm Control Panel  
The Gamewell-FCI, 7100 Series fire alarm control panel is  
a multi processor-based, analog addressable system. The  
control panel is a compact, yet expandable, platform.  
Intended for commercial, industrial and institutional instal-  
lations, the 7100 Series is ideal for life safety and property  
protection fire alarm applications.  
The basic 7100 Series control panel provides one analog  
addressable Signaling Line Circuit (SLC), whether sup-  
ports up to 99 analog addressable sensors, as well as sup-  
porting up to 98 addressable monitor modules and/or  
control points, totaling 197 addresses. The 7100 uses an  
advanced protocol that ensures an almost instant  
response to events while at the same time suppressing  
nuisance alarms.  
7100 Series  
The system may be programmed with the CAMWorks™  
programming utility tool or configured through a compre-  
hensive set of intuitive, secure password-protected, front-  
panel programming options. This important feature allows  
the system to quickly adapt to any future requirements due  
to changes in occupancies, building remodels, or other  
contingencies.  
Features  
Listed under ANSI/UL® Standard 864 9th Edition.  
IBC Seismic Certified.  
120 or 240 VAC (optional) input line voltage.  
Front panel programming with day/night sensitivity  
adjustments.  
80-character alpha-numeric display.  
One Style 4 (Class “B”) signaling line circuit. Style 6  
(Class “A”) with optional CAOM Module.  
Two Style Y (Class “B”) regulated notification appliance  
circuits rated for 1.5 amp each. Style Z (Class “A”) with  
optional CAOM Module.  
The sophisticated circuitry and powerful analog software  
enables the 7100 Series fire alarm control panel to read  
the specific sensitivity level of each sensor and compen-  
sate for changes due to age, dust accumulation or other  
environmental factors. The 7100 incorporates the  
Gamewell-FCI Listed Integrated Sensitivity Testing (LIST)  
which meets NFPA 72 sensitivity testing and maintenance  
requirements. The LIST testing allows substantial savings  
in both maintenance and service while eliminating nui-  
sance alarms.  
FM/UL® Listed for Pre-action/Deluge with optional  
MCOM Module.  
Periodic trouble reminder.  
Individual sensor drift compensation.  
Dual-stage maintenance alerts (“dirty” and “very dirty”).  
Multilevel sensor sensitivity adjustments (front panel  
programmable).  
The Model 7100-1D features an integral Digital Alarm  
Communicator Transmitter (DACT) with all popular trans-  
mission formats and a 16-digit telephone number field. It is  
8-digit Carrier Information Code (CIC) compliant and also  
prevents “dialer-runaway” in the event of intermittent sys-  
tem faults. The 7100-1D is UL Listed for Remote Station,  
Proprietary, and Central Station fire alarm systems. It  
allows ample space for wiring and room for batteries up to  
12 A/H capacity.  
Alarm verification per individual sensor.  
Positive alarm sequence for sensors or monitor  
modules.  
continued on the next page  
SIGNALING  
FM  
MEA  
APPROVED  
Approved  
6911-1703:0116 (Non-High Rise) Reference Certificate  
3003549 FDNY  
S1869  
CAMWorks™ is a trademark of Honeywell International, Inc.  
Microsoft® Word® is a registered trademark of Microsoft® Corporation.  
UL® is a registered trademark of Underwriter’s Laboratories Inc.  
COA #s 307-99-E 6911-1703:0118 (High Rise)  
of Compliance  
7300-1703:0106 (LCD-7100)  
VMA-45894-02C  
(Revision 1)  
307-99-E Vol. II  
GAMEWELL-FCI  
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118  
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.  
©2015 by Honeywell International Inc. All rights reserved.  
www.gamewell-fci.com  
9020-0466 Rev. N page 1 of 3  
Features (Continued)  
Optional Accessories  
LCD-7100  
Four levels of system access using six digit passwords  
with up to five user passwords per Level.  
Duplicate and extra address indications.  
March time (60 or 120 BPM)/temporal pattern/coded  
fours/California Code/user-defined zone coding.  
Cross zoning.  
System configuration programming and 280 event log  
stored in non-volatile memory.  
Fan restart with sequential restart delay.  
Upload/download of panel configuration between panel  
and CAMWorks program (password protected feature).  
Up to 64, 7100 panels in the E3 Broadband network  
with an optional INI-7100 Module.  
The LCD-7100 remote serial display offers an 80-character  
alphanumeric readout for the remote display of all system  
events. It duplicates all the information on the 7100 Series  
panel display and provides key switch protected functions  
such as System Reset, Alarm Acknowledge, Trouble  
Acknowledge, Signal Silence, and Drill Test.  
LEDs on the LCD-7100 indicate Alarm, Supervisory, Sys-  
tem Trouble, Power Fault, Systems Silenced, NAC#1, and  
NAC#2 Silenced conditions.  
The LCD-7100 can be surface or semi-flush mounted on a  
standard four-gang electrical box. It can be installed up to  
3,000 feet (914.4 m) from the main control panel. The 7100  
Series fire alarm control panel supports up to five remote  
LCD-7100 annunciators using one pair of twisted, non-  
shielded 18 AWG min. wire or serial communication and  
uses another pair of 16 AWG min. for operating voltage.  
(For additional information, refer to the LCD-7100 data  
sheet, Part Number: 9020-0486).  
Specifications  
Primary Input Power 120 VAC, 50/60 Hz @ 2.0 amps.  
or 240 VAC, 50/60 Hz @ 1.0 amp  
3.335 amps. @ 24 VDC (total)  
Output Power  
Non-resettable Power: 1.0 amp max.  
Resettable Power:  
RAN-7100  
The RAN-7100 maintains the same character display as  
1.0 amp max.  
the 7100 Series. The RAN-7100 is mounted in a RAN2-BB  
backbox for surface or flush mounting retrofits.  
1.0 amp max. from both power  
circuits  
Two Notification  
Appliance Circuits:  
Current:  
(For additional information, refer to the Gamewell Retrofit  
Kits Data Sheet, P/N: 9020-60678).  
1.5 amp each @ 24 VDC  
Supervisory  
0.065 amp  
Alarm  
0.085 amp  
CAOM  
7100-1 (One SLC)  
The Class “A” Optional Module (CAOM) allows Style Y and  
Z (Class “B” and “A”) operation for both Notification Appli-  
ance Circuits and allows Style 4 and 6 (Class “B” and “A”)  
for the Signaling Line Circuit. It also provides a disconnect  
switch for the signaling line circuit and a common discon-  
nect switch for both notification appliance circuits.  
7100-1D  
(One SLC w/DACT) 0.075 amp  
LCD-7100  
INI-7100-UTP,-FO  
Operating  
Temperature:  
Relative Humidity:  
Battery Charger  
Capacity:  
0.095 amp  
0.075 amp  
0.040 amp  
0.050 amp  
0.040 amp  
32° - 120° F (0° - 49° C)  
93 % (non-condensing)  
MCOM  
The Municipal Connection Option Module (MCOM) pro-  
vides three choices of outputs. It can be configured as a  
Municipal Circuit (City Box) output. It may also be set to  
serve as a Reverse Polarity output with a nominal voltage  
output of 24 VDC at 0.012 amp maximum alarm and  
supervisory current. The MCOM’s third option provides a  
releasing solenoid output rated at:  
31 A/H (Cabinet accommodates  
12 A/H size batteries)  
Alarm & Trouble  
Relay Contacts:  
Form “C”, 2 amps. @ 24 VDC  
(resistive)  
24 VDC nominal voltage.  
0.005 amp supervisory current.  
0.710 amp maximum alarm current.  
2 ohms maximum line resistance.  
PTRM  
The Printer Transient Module (PTRM) provides RS-232  
Isolator/Transient protection for the 7100’s RS-232 port  
(BSM connector J2). It is used in conjunction with a serial  
printer applied to the RS-232 port for permanent record  
keeping.  
INI-7100  
The Intelligent Network Interface Module allows the 7100  
Series fire alarm control panel to become the platform of a  
peer-to-peer, token ring, self-regenerative network com-  
prised of up to 64, 7100 panels.  
GAMEWELL-FCI  
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118  
9020-0466 Rev. N page 2 of 3  
www.gamewell-fci.com  
Ordering Information (Continued)  
Ordering Information  
Replacement Parts  
Systems  
Part Number  
7100-1-PNL  
Part Number  
BSM-7100-1  
BSM-7100-1D  
BSM-7100-2  
BSM-7100-2D  
Description  
Description  
Replacement board for 7100-1  
Replacement board for 7100-1D  
Replacement board for 7100-2  
Replacement board for 7100-2D  
7100 Addressable FACP, 1 SLC mounted  
in the 7100-CAB enclosure, red  
7100 Addressable FACP w/DACT, One  
SLC mounted in 7100-CAB enclosure,  
red  
7100-1D-PNL  
Seismic Battery Bracket Kits  
Basic Kits  
1100-1313  
90516  
7100-Slim 7 A/H Seismic Battery  
Bracket kit  
Basic System Kit, 2 SLC, 240 VAC  
E3 B-Slim 7 A/H Seismic Battery  
Bracket Kit  
7100-Slim 12 A/H Seismic Battery  
Bracket Kit E3 B-Slim 12 A/H Seismic  
Battery Bracket Kit  
NetSOLO 7100 7 A/H Seismic Battery  
Bracket Kit  
Optional Modules  
LCD-7100 Remote Serial Annunciator, LCD Display  
(80-character).  
90517  
90518  
Dimensions: 4.25” H x 8.25” W x 1.90”  
(43 H x 37 W x 7.7 D cm)  
Remote Series Annunciator, LCD Display  
RAN-7100  
(80-character).  
Dimensions: 10” W x 5 1/4” H x 2 7/16” D  
For additional information on the Seismic Battery Brackets,  
refer to the following documents:  
(25 1/4 W x 13 1/3 H x 6 9/10 D cm)  
Class A Option Combination Module with  
Seismic Battery Bracket Installation Guide, P/N: 53839  
E3 Series Cabinets Data Sheet, P/N: 9020-0649  
CAOM  
disconnect switches for both signaling  
line circuits and notification appliance  
circuits.  
MCOM  
Municipal Connection Option Module for  
local energy city box reverse polarity sig-  
naling, or releasing solenoid.  
Printer Transient Module.  
PTRM  
INI-7100-FO  
Intelligent Network Interface Module,  
Fiber-Optic.  
Intelligent Network Interface Module,  
Unshielded, Twisted-Pair.  
INI-7100-UTP  
GAMEWELL-FCI  
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118  
9020-0466 Rev. N page 3 of 3  
www.gamewell-fci.com  

BSM-7100-1 相关器件

型号 制造商 描述 价格 文档
BSM-7100-1D GAMEWELL-FCI Compact Analog Addressable Fire Alarm Control Panel 获取价格
BSM-7100-2 GAMEWELL-FCI Compact Analog Addressable Fire Alarm Control Panel 获取价格
BSM-7100-2D GAMEWELL-FCI Compact Analog Addressable Fire Alarm Control Panel 获取价格
BSM05GD100D ETC TRANSISTOR | IGBT POWER MODULE | 3-PH BRIDGE | 1KV V(BR)CES | 5A I(C) 获取价格
BSM05GD100DN1 INFINEON Insulated Gate Bipolar Transistor, 5A I(C), 1000V V(BR)CES, N-Channel 获取价格
BSM080D12P2C008 ROHM 本品是使用ROHM生产的SiC-DMOSFET和SiC肖特基势垒二极管的斩波结构的SiC MOSFET模块。 获取价格
BSM100GAL100D ETC TRANSISTOR | IGBT POWER MODULE | INDEPENDENT | 1KV V(BR)CES | 100A I(C) 获取价格
BSM100GAL120D INFINEON Insulated Gate Bipolar Transistor, 100A I(C), 1200V V(BR)CES, N-Channel 获取价格
BSM100GAL120DLCK INFINEON IGBT-modules 获取价格
BSM100GAL120DN2 INFINEON IGBT Power Module (Single switch with chopper diode Including fast free-wheeling diodes) 获取价格

BSM-7100-1 相关文章

  • Bourns 密封通孔金属陶瓷微调电位计产品选型手册(英文版)
    2024-09-20
    6
  • Bourns 精密环境传感器产品选型手册(英文版)
    2024-09-20
    9
  • Bourns POWrTher 负温度系数(NTC)热敏电阻手册 (英文版)
    2024-09-20
    8
  • Bourns GMOV 混合过压保护组件产品选型手册(英文版)
    2024-09-20
    6