SS-I [GAMEWELL-FCI]
Intelligent Addressable Plug-In Ionization Smoke Detector; 智能寻址插件离子式烟雾探测器型号: | SS-I |
厂家: | GAMEWELL-FCI BY HONEYWELL |
描述: | Intelligent Addressable Plug-In Ionization Smoke Detector |
文件: | 总2页 (文件大小:93K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Features
SS-I
• Sleek, low-profile design.
• Addressable-analog communica-
tion.
Intelligent Addressable Plug-In
Ionization Smoke Detector
• Stable communication technique
with noise immunity.
• Low standby current.
• Two-wire SLC connection.
Description
• Rotary, decimal addressing (1 –
99).
Gamewell’s
intelligent
SmartScanTM plug-in smoke
detector with integral commu-
nication provides features
that surpass conventional de-
tectors. Detector sensitivity
can be programmed in the
control panel software. Sen-
sitivity is continuously moni-
tored and reported to the
panel. Point ID capability al-
lows each detector’s address
to be set with decade address
switches, providing exact de-
• Optional remote, single-gang LED
accessory (RA400Z).
• Dual LED design provides 360°
viewing angle.
• Visible bicolor LEDs blink green
every time the detector is ad-
dressed, and illuminate steady red
on alarm.
• Remote test feature from the
panel.
6934pho1.jpg
• Built-in functional test switch
activated by external magnet.
SS-I with SS-B6 base
• Built-in tamper-resistant feature.
• Sealed against back pressure.
• Constructed of off-white
Bayblend®, designed to commer-
cial standards, and offers an
attractive appearance.
tector locations for selective maintenance when chamber contamination reaches
an unacceptable level. The SS-I ionization detector incorporates a unique single-
source, dual-chamber design to respond quickly and dependably to a broad range of
fires. The SS-I detector is compatible with Gamewell’s 602, 610, 632, 654 and 658
FACPS with a SmartScanTM SLC.
• 94-5V plastic flammability rating.
• SEMS screws for wiring of the
separate base.
• Optional relay, isolator, or sounder
bases.
Installation
• Backward-compatible.
The SS-I plug-in detector uses a separate base to simplify installation, service, and
maintenance. A special tool allows maintenance personnel to plug in and remove
detectors without using a ladder.
Listings
Mount base on an electrical backbox which is at least 1.5" (3.81 cm) deep. Suitable
mounting back boxes include:
Listings and approvals below
apply to the SS-I Intelligent Plug-In
Ionization Smoke Detector. In
some cases, the detector may not
be listed by certain approval
agencies, or listing may be in
process. Consult factory for latest
listing status.
• 4.0" (10.16 cm) square box.
• 3.5" (8.89 cm) or 4.0" (10.16 cm) octagonal box.
• Single-gang box (except for relay or isolator base).
• With B501BH or B501BHT base, use a 4.0" (10.16 cm) square box.
• With B224RB or B224BI base, use a 3.5" (8.89 cm) octagonal box, or a 4.0"
• UL Listed: file S1195.
(10.16 cm) octagonal or square box.
• CSFM approved:
file 7271-1288:168.
NOTES: 1) Because of the inherent supervision provided by the SLC loop, end-of-
line resistors are not required. Wiring “T-taps” or branches are permitted for Style 4
(Class “B”) wiring. 2) When using relay or sounder bases, consult data sheet CS-
2464 (SS-LI) for device limitations between isolator modules and isolator bases.
Bayblend® is a registered trademark of Bayer Corporation.
SS-I CS-2459 09/01/06
Page 1 of 2
Specifications
Product Line Information
SS-I: Low-profile intelligent ionization
smoke detector. Must be mounted to one
of the bases listed below.
Size
M02-09-00: Test magnet with telescope
stick.
XR2B: Detector removal tool. Allows
installation and/or removal of SS-I
detector heads from base in high ceiling
installations.
2.1" (5.3 cm) high x 4.1" (10.4 cm)
diameter installed in B501 base, 6.1"
(15.5 cm) diameter installed in SS-B6
base.
Bases:
SS-B6: Standard U.S. low-profile base,
UL Listing.
Shipping weight
T55-127-000: Detector removal tool
without pole.
XP-4: Extension pole for XR2B. Comes
in three 5-ft. sections.
5.4 oz. (154 g).
B501BP: Standard European flangeless
base, pkg. of 10.
B501BH: Sounder base, includes B501
base above.
B501BHT: Same as B501BH, but
includes temporal sounder.
B224RB: Intelligent relay base.
Operating temperature
0°C to 49°C (32°F to 120°F).
UL-Listed velocity range:
ION: 0 – 1200 ft./min. (365.76 m/min.).
Relative humidity
Detector Guards:
NOTE: The following guards are not UL
listed with the SS-I detectors. Consult AHJ.
10% – 93% noncondensing.
STI 9601: Low-profile, flush-mount smoke
detector guard, wire.
STI 9602: Low-profile, surface-mount,
smoke detector guard, wire.
STI 9609: High-profile, flush-mount, smoke
detector guard, wire.
STI 9605: High-profile, surface-mount,
smoke detector guard, wire.
Accessories:
DETECTOR SPACING:
RA400Z: Remote LED annunciator. 3 –
32 VDC. Fits U.S. single-gang electrical
box. Supported by SS-B6 and B501
bases only.
SMK400: Surface mounting kit provides
for entry of surface wiring conduit. For
use with B501 base only.
Gamewell recommends spacing detec-
tors in compliance with NFPA 72. In low
airflow applications with smooth ceilings,
space detectors 30 feet (9.144 m). For
specific information regarding detector
spacing, placement, and special applica-
tions, refer to NFPA 72. System Smoke
Detector Application Guide, document
A05-1003, is available at
STI 9604: Flush-mount heat detector
guard, wire.
RMK400: Recessed mounting kit. For
use with B501 base only.
systemsensor.com.
SMB600: Surface mounting kit for use
STI 9610: Surface-mount heat detector
with SS-B6.
guard, wire.
ELECTRICAL SPECIFICATIONS:
Voltage range
15 - 32 volts DC peak.
BCK-200B: Black detector covers, box of STI-8200-SS: Flush-mount stainless
10. Use with SS-I.
M02-04-01: Test magnet.
steel smoke detector guard
STI-8230-SS: Surface-mount stainless
steel smoke detector guard
Standby current (max. avg.)
200 µA @ 24 VDC (without communica-
tion); 300 µA @ 24 VDC (one communi-
cation every 5 seconds with LED
enabled).
Wiring Diagrams
LED current (max.)
6.5 mA @ 24 VDC (“ON”).
BASES AVAILABLE:
SS-B6: 6.1" (15.5 cm) diameter.
B501: 4.1" (10.4 cm) diameter.
B501BH or B501BHT: Sounder base
assembly. Includes B501 base.
B224RB Relay Base: Screw terminals:
up to 14 AWG (2.0 mm²). Relay type:
Form-C. Rating: 2.0 A @ 30 VDC
resistive; 0.3 A @ 110 VDC inductive; 1.0
A @ 30 VDC inductive. Dimensions:
6.2" (15.748 cm) x 1.2" (3.048 cm).
B224BI Isolator Base: Dimensions:
6.2" (15.748 cm) x 1.2" (3.048 cm).
Maximum: 25 devices between isolator
bases.
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
Address dial on back of detector.
Specifications and wiring information are provided for information only and are believed
to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring instructions
shipped with the product shall always be used for actual installation. For more
information, contact Gamewell-FCI.
www.gamewell-fci.com
AHoneywell Company
© 2006 Gamewell-FCI
Page 2 of 2
SS-I
CS-2459
09/01/06
相关型号:
SS0.22M50-0405
Aluminum Electrolytic Capacitor, Polarized, Aluminum, 50V, 20% +Tol, 20% -Tol, 0.22uF
YSTONE
©2020 ICPDF网 联系我们和版权申明