RCP-1U [MEANWELL]

UNIVERSAL AC INPUT / FULL RANGE;
RCP-1U
型号: RCP-1U
厂家: MEAN WELL ENTERPRISES CO., LTD.    MEAN WELL ENTERPRISES CO., LTD.
描述:

UNIVERSAL AC INPUT / FULL RANGE

输入元件
文件: 总6页 (文件大小:232K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
1000 ~ 3000W 1U Distributed Power System  
RCP-1U Rack System  
Rack Dimension  
L
*
W
*
H
Bauart gepruft  
Sicherheit  
483.6 * 350.8 * 44 (1U) mm  
19 1.73(1U) inch  
egelma ge  
o s  
g
od  
be wac  
www.tuv.com  
ID 2000000000  
*
*
13.8  
Features  
Applications  
Universal AC input / Full range  
1U profile 19rack shelf, fitting three 1000W modules  
up to 3000W with active current sharing  
Output voltage programmable  
Support hot swap (hot plug)  
Industrial automation  
Distributed power architecture system  
Wireless/telecommunication solution  
Redundant power system  
Electric vehicle charger system  
Constant current source system  
5 years warranty  
Description  
RCP-1U rack system is a power distribution solution utilizing the rack configuration with 1U low profile.  
Starting with a single unit of 1000W, RCP-1000 is the front end rectifier (or, power supply). With the active  
current sharing function, up to 3000W is able to be provided by 1 stack of the 19rack mountable shelf  
RCP-1U and 8000W by 3 stacks. The design flexibility for system applications is ideally fulfilled by various  
built-in features, such as output programming, remote ON-OFF, auxiliary power, etc.  
Model Encoding / Order Information  
Rack Shelf:  
RCP-1U I  
Whole System:  
RCP-3K1U I -12 - C  
C: With I2C Interface  
: Without I2C Interface  
Output voltage  
I: AC Inlet (IEC320-C14)  
T: Terminal block  
Profile of the system  
Series name  
I: AC Inlet (IEC320-C14)  
T: Terminal block  
1U: Profile of the system  
3K: Maximum wattage with  
fully-populated shelf  
Series name  
File Name:RCP-1U Rack System-SPEC 2016-07-26  
1000 ~ 3000W 1U Distributed Power System  
RCP-1U Rack System  
SPECIFICATION - Power Supply System  
MODEL  
RCP-3K1U-12  
RCP-3K1U-24  
RCP-3K1U-48  
RECTIFIER  
RCP-1000-12  
RCP-1UI or RCP-1UT  
12V  
RCP-1000-24  
RCP-1000-48  
RACK SHELF  
OUTPUT VOLTAGE  
MAX. OUTPUT CURRENT  
24V  
48V  
OUTPUT  
180A  
120A  
2880W  
63A  
MAX. OUTPUT POWER Note.6 2160W  
3024W  
VOLTAGE RANGE  
Note.5 90 ~ 264VAC  
127 ~ 370VDC  
4.5A/230VAC  
FREQUENCY RANGE  
AC CURRENT (Typ.)PER MODULE  
LEAKAGE CURRENT  
AUXILIARY POWER  
47 ~ 63Hz  
INPUT  
8.5A/115VAC  
<3.5mA / 230VAC  
5V @ 0.3A  
10.5A/115VAC  
5.5A/230VAC  
11A/115VAC  
5.5A/230VAC  
By electrical signal or dry contact ON:short OFF:open  
Compensate voltage drop on the load wiring up to 0.5V.  
REMOTE ON-OFF CONTROL  
REMOTE SENSE  
Adjustment of output voltage is allowable to 90 ~ 110% of nominal output voltage. Please refer to the Function Manual.  
The isolated TTL signal out, Please refer to the Installation Manual  
The isolated TTL signal out, Please refer to the Installation Manual  
Logic " High" for over temperature warning, Please refer to the Installation Manual, isolated signal  
-20 ~ +60(Refer to "Derating Curve")  
OUTPUT VOLTAGE PROGRAMMABLE  
DC OK SIGNAL  
FUNCTION  
AC OK SIGNAL  
OVER TEMP WARNING  
WORKING TEMP.  
20 ~ 90% RH non-condensing  
WORKING HUMIDITY  
STORAGE TEMP., HUMIDITY  
-40 ~ +85, 10 ~ 95% RH  
ENVIRONMENT  
TEMP. COEFFICIENT  
VIBRATION  
0.02%/(0 ~ 50)  
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes  
UL60950-1, TUV EN60950-1 approved  
SAFETY STANDARDS  
WITHSTAND VOLTAGE  
ISOLATION RESISTANCE  
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.7KVDC  
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25/ 70% RH  
Parameter  
Standard  
Test Level / Note  
Conducted  
EN55022 (CISPR22) / EN55011 (CISPR11) Class B  
EN55022 (CISPR22) / EN55011 (CISPR11) Class B  
Radiated  
EMC EMISSION  
Harmonic Current  
Voltage Flicker  
EN55024 , EN61204-3, EN61000-6-2  
Parameter  
EN61000-3-2  
EN61000-3-3  
-----  
-----  
SAFETY &  
Standard  
Test Level / Note  
EMC  
(Note 4)  
ESD  
EN61000-4-2  
EN61000-4-3  
EN61000-4-4  
EN61000-4-5  
EN61000-4-6  
EN61000-4-8  
Level 3, 8KV air ; Level 2, 4KV contact  
Radiated  
Level 3  
EFT / Burst  
Level 3  
EMC IMMUNITY  
Level 4, 4KV/Line-Earth ; Level 3, 2KV/Line-Line  
Surge  
Conducted  
Level 3  
Level 4  
Magnetic Field  
>95% dip 0.5 periods, 30% dip 25 periods,  
>95% interruptions 250 periods  
Voltage Dips and Interruptions  
EN61000-4-11  
DIMENSION  
PACKING  
Rack 483.6*350.8*44(L*W*H)  
13.2Kg; 1pcs/13.2Kg/2.67CUFT  
OTHERS  
NOTE  
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25of ambient temperature.  
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. Under parallel  
operation of more than one rack connecting together, ripple of the output voltage may be higher than the SPEC at light load condition. It will go back to  
normal ripple level once the output load is more than 10%. .  
3. Tolerance : includes set up tolerance, line regulation and load regulation.  
4. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on  
a 720mm*360mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to  
perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com)  
5. Derating may be needed under low input voltages. Please check the derating curve for more details.  
6. Output of all the RCP-1000 modules are connected in parallel in the rack.  
File Name:RCP-1U Rack System-SPEC 2016-07-26  
1000 ~ 3000W 1U Distributed Power System  
RCP-1U Rack System  
Function Manual  
1. Remote ON/OFF Control  
The PSU can be turned ON/OFF together or separately by using the "Remote ON-OFF" function.  
1
8
15  
1
8
15  
Remote ON-OFF A  
Remote ON-OFF B  
Remote ON-OFF C  
Remote ON-OFF A  
Remote ON-OFF B  
Remote ON-OFF C  
Between Remote ON-OFF and -S Output  
RCP-1U  
System  
RCP-1U  
System  
Switch Open  
Switch Short  
OFF  
ON  
21  
21  
-S  
-S  
2. Voltage Drop Compensation  
2.1 Remote Sense  
The remote sense compensates voltage drop on the load wiring up to 0.5V.  
+V  
+S  
+V  
20  
21  
RCP-1U System  
LOAD  
-S  
-V  
-V  
Sense lines should be twisted in pairs  
2.2 Local Sense  
Notice : The +S,-S, on CN500 have to be connected to the +V,-V terminals locally in order to get the correct output voltage if the remote sensing is not used.  
22  
+V  
20  
+S  
RCP-1U System  
25  
21  
-V  
-S  
3. Output Voltage Programming (or, PV / remote voltage programming / remote adjust / margin programming / dynamic voltage trim)  
(1)Output voltage can be trimmed between 90~110% of its rated value by the following method.  
(2)+S & +V, -S & -V also need to be connected on CN500.  
22  
+V  
+S  
20  
4
R1  
R2  
R1  
R2  
R1  
R2  
V-TRIM-A  
V-TRIM-B  
V-TRIM-C  
11  
18  
RCP-1U System  
LOAD  
21  
25  
-S  
-V  
3.1 RCP-1000-12  
Vout (%)  
Vout (%)  
100  
98  
96  
94  
92  
90  
110  
108  
106  
104  
102  
100  
R1 (Ω)  
min. 0.1W  
R2 (Ω)  
min. 0.1W  
180K  
240K  
350K  
560K  
1.2M  
NC  
NC  
300K  
120K  
62K  
31K  
13K  
File Name:RCP-1U Rack System-SPEC 2016-07-26  
1000 ~ 3000W 1U Distributed Power System  
RCP-1U Rack System  
3.2 RCP-1000-24  
Vout (%)  
Vout (%)  
100  
98  
96  
94  
92  
90  
110  
108  
106  
104  
102  
100  
R1 (Ω)  
min. 0.1W  
R2 (Ω)  
min. 0.1W  
560K  
750K  
1M  
1.6M  
3.3M  
NC  
NC  
330K  
130K  
62K  
30K  
10K  
3.3 RCP-1000-48  
Vout (%)  
Vout (%)  
100  
98  
96  
94  
92  
90  
110  
108  
106  
104  
102  
100  
R1 (Ω)  
min. 0.1W  
R2 (Ω)  
min. 0.1W  
1.3M  
1.7M  
2.4M  
3.6M  
7.6M  
NC  
NC  
345K  
140K  
70K  
36K  
15K  
4. I2C Bus Interface Option  
For the details of I2C option, please refer to the Installation Manual.  
File Name:RCP-1U Rack System-SPEC 2016-07-26  
1000 ~ 3000W 1U Distributed Power System  
RCP-1U Rack System  
Mechanical Specification (Rack System)  
Case No. 959A  
Unit:mm  
Fig1  
14  
1
25  
13  
ADDRESS  
SWITCH  
CN500  
-
+
14  
1
25  
LC NC LB NB LA NA  
13  
Mounting Bracket  
RCP-1UT  
10  
8
ADDRESS  
SWITCH  
CN500  
C
B
A
-
+
14  
1
25  
13  
RCP-1UI  
440  
1
1
1
1
1
1
22  
22  
Air flow  
direction  
Module C  
Module B  
Module A  
10.6  
DC OK AC OK  
DC OK AC OK  
466.2  
483.6  
DC OK AC OK  
Chassis of RCP-1U RACK  
Mounting Surface  
Mounting Screw  
Mounting Instruction  
Hole No. Recommended Screw Size  
MAX. Penetration Depth L  
Recommended mounting torque  
10Kgf-cm  
1
6mm  
M5  
L
File Name:RCP-1U Rack System-SPEC 2016-07-26  
1000 ~ 3000W 1U Distributed Power System  
RCP-1U Rack System  
IN/OUT Connector Pin No. Assignment(CN500) : D-Type Right Angle 25 positions(female type)  
14  
25  
13  
1
Pin No.  
Function  
Description  
1,8,15 RemoteON-OFF  
Each unit can separately turn the output on and off by electrical or dry contact between Remote ON-OFF A,B,C(pin 1,8,15) and -S(pin 21). Short: ON, Open:OFF.  
Low : When input voltage is 82Vrms +/-4V.  
High : When input voltage in82Vrms +/-4V.  
2,9,16  
AC-OK  
High : When Vout80%+/-5%.  
Low : When Vout 80%+/-5%  
3,10,17  
4,11,18  
DC-OK  
V-TRIM  
Connection for output voltage programming.  
High : When the internal temperature is within safe limit.  
Low : 10below the thermal shut down limit.  
5,12,19 T-ALARM  
Auxiliary voltage output, 4.3~5.3V, referenced to GND-AUX(pin 7).  
The maximum load current is 0.3A. This output has the built-in "Oring diodes" and is not controlled by the remote ON/OFF control.  
6
+5V-AUX  
Auxiliary voltage output GND.  
The signal return is isolated from the output terminals (+V & -V).  
7
GND-AUX  
CS  
Current sharing signal.  
When units are connected in parallel, the CS pins of the units should be connected to allow current balance between units.  
14  
20  
21  
22  
23  
24  
25  
+S  
-S  
Positive sensing for Remote Sense.  
Negative sensing for Remote Sense.  
+V  
Positive output voltage.  
Serial clock used in the I2C interface option. Refer to the Instruction Manual.  
Serial data used in the I2C interface option. Refer to the Instruction Manual.  
Negative output voltage.  
SCL  
SDA  
-V  
Installation Manual  
Please refer to the manual of RCP-1U system.  
File Name:RCP-1U Rack System-SPEC 2016-07-26  

相关型号:

RCP-1UI

UNIVERSAL AC INPUT / FULL RANGE
MEANWELL

RCP-2000

2000W Front End Power Supply
MEANWELL

RCP-2000-12

2000W Front End Power Supply
MEANWELL

RCP-2000-24

2000W Front End Power Supply
MEANWELL

RCP-2000-48

2000W Front End Power Supply
MEANWELL

RCP-26

CARD EJECTORS
RICHCO

RCP-29

CARD EJECTORS
RICHCO

RCP-36

CARD EJECTORS
RICHCO

RCP-39

CARD EJECTORS
RICHCO

RCP-3K1U-12

1000 ~ 3000W Front End Power System
MEANWELL

RCP-3K1U-24

1000 ~ 3000W Front End Power System
MEANWELL

RCP-3K1U-48

1000 ~ 3000W Front End Power System
MEANWELL