M3LR-R4/B/Q [MSYSTEM]

Space-saving Signal Conditioners M3-UNIT Series;
M3LR-R4/B/Q
型号: M3LR-R4/B/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Space-saving Signal Conditioners M3-UNIT Series

文件: 总4页 (文件大小:137K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: M3LR  
Space-saving Signal Conditioners M3-UNIT Series  
POWER INPUT  
DC Power  
R4: 10 – 32 V DC  
RTD TRANSMITTER  
(field- and PC-configurable)  
(Operational voltage range 9 - 36 V, ripple 10 %p-p max.)  
Functions & Features  
• Accepts an RTD input and provides an isolated, linearized  
DC signal  
[1] CONFIGURATION OPTIONS  
A: PC and field configurable  
• Easy ‘One-Step Cal’ calibration using the front three  
control buttons without needing a PC; PC software is also  
usable.  
B: Field configurable  
[2] OPTIONS (multiple selections)  
Standards & Approvals  
• Both input and output type and range are configurable  
• Front control button function can be locked  
• Linearization and burnout  
blank: CE marking  
/UL: UL approval, CE marking  
Other Options  
18 (.71)  
blank: none  
/Q: Option other than the above (specify the specification)  
106  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
(4.17)  
/C02: Polyurethane coating  
110.5 (4.35)  
mm (inch)  
/C03: Rubber coating (UL not available)  
RELATED PRODUCTS  
MODEL: M3LR–R4/[1][2]  
• PC configurator software (model: M3CFG)  
Downloadable at M-System’s web site.  
A dedicated cable is required to connect the module to the  
PC. Please refer to the internet software download site or  
the users manual for the PC configurator for applicable  
cable types.  
ORDERING INFORMATION  
• Code number: M3LR-R4/[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. M3LR-R4/A/UL/Q)  
• Specify the specification for option code /Q  
(e.g. /C01)  
GENERAL SPECIFICATIONS  
• Orders will be shipped with default factory settings (3-wire  
Pt 100, 0 – 100°C input/4 – 20 mA output).  
Construction: Small-sized front terminal structure  
Connection: Euro type connector terminal  
(applicable wire size: 0.2 to 2.5 mm , stripped length 8 mm)  
2
Housing material: Flame-resistant resin (gray)  
Isolation: Input to output to power  
Overrange output: -15 to +115 %  
Zero adjustment: -15 to +15 % (front)  
Span adjustment: 85 to 115 % (front)  
Burnout: Upscale (default), downscale or no burnout  
selectable  
INPUT – Field-selectable  
RTD  
Pt 100, Pt 200, Pt 300, Pt 400, Pt 500, Pt 1000,  
Ni 100, Ni 120, Ni 508.4Ω, Ni-Fe 604,  
Cu 10 @25°C, Pt 50Ω, JPt 100  
OUTPUT – Field-selectable  
Current  
Linearization: Standard  
Status indicator LED: Tri-color (green/amber/red) LED;  
Blinking patterns indicate operation status of the  
transmitter.  
0 – 20 mA DC  
Voltage  
-2.5 – +2.5 V DC  
-10 – +10 V DC  
Configuration:  
PC Configurator: (Model: M3LRCFG) via Windows PC  
connected to th front jack.  
Programmable features include:  
M3LR SPECIFICATIONS  
ES-2662 Rev.13 Page 1/4  
http://www.m-system.co.jp/  
MODEL: M3LR  
• I/O type, number of wires and range  
• Zero and span adjustments  
INSTALLATION  
Power consumption  
DC: Approx. 3 W  
• Burnout action  
• User’s RTD table setting  
Operating temperature: -25 to +65°C (-13 to +149°F)  
Max. 55°C (131°F) for UL approval  
Operating humidity: 0 to 95 %RH (non-condensing)  
Mounting: DIN rail  
(max. 300 points, input resistance specified  
within 0 – 30 kΩ)  
(Refer to the instruction manual)  
‘One-Step Cal’ calibration: With I/O type and the full-scale  
range configured via the internal DIP switches, precise 0 %  
and 100 % ranges are calibrated via the front control  
buttons with a help of LED. Also I/O calibration and fine  
adjustment are available with a PC.  
Configurator connection: 2.5 dia. miniature jack;  
RS-232-C level  
Weight: 100 g (0.22 lb)  
PERFORMANCE  
Accuracy: See Table 1 and refer to calculation examples of  
overall accuracy.  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) of max.  
range at -5 to +55°C (23 to 131°F)  
Response time: ≤ 0.9 sec. (0 – 90 %)  
Burnout response: ≤ 10 sec.  
INPUT SPECIFICATIONS  
RTD: See Table 1.  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute  
(input to output or power to ground)  
500 V AC @ 1 minute (output to power)  
Number of wires: 2, 3 or 4 wires  
Excitation: ≤ 1.0 mA  
Allowable leadwire resistance: 20 Ω per wire  
Temperature range: See Table 1.  
OUTPUT SPECIFICATIONS  
■ DC Current  
CALCULATION EXAMPLES OF OVERALL ACCURACY  
CALCULATION EXAMPLES OF OVERALL ACCURACY IN %  
1) Pt 100, 0 – 500°C, 4 – 20 mA DC output  
Absolute value accuracy (Table 1): 0.15°C  
0.15°C ÷ 500°C × 100 = 0.03 % < 0.1%  
Output span 16 mA (20 – 4) ≥ 2 mA (max. span 20 mA ×  
0.1) ➠ No adding 0.2 %  
Maximum range: 0 – 20 mA DC  
Minimum span: 1 mA  
Conformance range: 0 – 24 mA DC  
(Negative overrange current below 0 mA is not available.)  
Offset: Lower range can be any specific value within the  
output range provided that the minimum span is  
maintained.  
➠ Overall accuracy = ±0.1 % of span  
2) Pt 100, 0 – 100°C, 2.0 – 2.5 V DC output  
Absolute value accuracy (Table 1): 0.15°C  
0.15°C ÷ 100°C × 100 = 0.15 % > 0.1 %  
Output span 0.5 V (2.5 – 2.0) ≤ 0.5 (max. span 5 V × 0.1) ➠  
Add 0.2 %  
Load resistance: Output drive 12 V maximum  
DC Voltage  
Narrow Spans  
Maximum range: -2.5 – +2.5 V DC  
Minimum span: 250 mV  
➠ Overall accuracy = 0.15 + 0.2 = ±0.35 % of span  
Conformance range: -3 – +3 V DC  
Wide Spans  
STANDARDS & APPROVALS  
EU conformity:  
Maximum range: -10 – +10 V DC  
Minimum span: 1 V  
EMC Directive  
Conformance range: -11.5 – +11.5 V DC  
Offset: Lower range can be any specific value within the  
output range provided that the minimum span is  
maintained.  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
RoHS Directive  
Approval:  
Load resistance: Output drive 1 mA maximum  
UL/C-UL general safety requirements  
(UL 61010-1, CAN/CSA-C22.2 No.1010-1)  
M3LR SPECIFICATIONS  
ES-2662 Rev.13 Page 2/4  
http://www.m-system.co.jp/  
MODEL: M3LR  
EXTERNAL VIEW  
FRONT VIEW  
SIDE VIEW  
LED1 (LD1)  
LED2 (LD2)  
LED3 (LD3)  
MODE Button  
UP Button  
10 11 12  
Configuration DIP SW  
7
8
9
4 3 2 1  
OFF  
ON  
DOWN Button  
SW1  
Configurator Jack  
SW2  
SW3  
8 7 6 5 4 3 2 1  
OFF  
ON  
4
5
6
4 3 2 1  
OFF  
ON  
The DIP switch setting is required to select output types before setting a precise output range using the PC configurator  
software.  
For detailed information on the configuration and calibration, refer to the instruction manual.  
INPUT TYPE, RANGE & ACCURACY  
INPUT TYPE, RANGE & ACCURACY  
TABLE 8  
°C  
°F  
RTD  
MIN.SPAN  
MAXIMUM RANGE  
ACCURACY*1  
MIN.SPAN  
MAXIMUM RANGE  
ACCURACY*1  
Pt 100 (JIS ’97, IEC)  
Pt 200  
Pt 300  
20  
20  
20  
-200 to +850  
-200 to +850  
-200 to +850  
0ꢀ15  
0ꢀ15  
0ꢀ15  
36  
36  
36  
-328 to +1562  
-328 to +1562  
-328 to +1562  
0ꢀ27  
0ꢀ27  
0ꢀ27  
Pt 400  
Pt 500  
Pt 1000  
20  
20  
20  
-200 to +850  
-200 to +850  
-200 to +850  
0ꢀ15  
0ꢀ15  
0ꢀ15  
36  
36  
36  
-328 to +1562  
-328 to +1562  
-328 to +1562  
0ꢀ27  
0ꢀ27  
0ꢀ27  
Pt 50Ω (JIS ’81)  
JPt 100 (JIS ’89)  
Ni 100  
20  
20  
20  
-200 to +649  
-200 to +510  
-80 to +260  
0ꢀ15  
0ꢀ15  
0ꢀ15  
36  
36  
36  
-328 to +1200  
-328 to +950  
-112 to +500  
0ꢀ27  
0ꢀ27  
0ꢀ27  
Ni 120  
20  
20  
20  
20  
-80 to +260  
-50 to +200  
-200 to +200  
-50 to +250  
0ꢀ15  
0ꢀ15  
0ꢀ15  
0ꢀ50  
36  
36  
36  
36  
-112 to +500  
-58 to +392  
-328 to +392  
-58 to +482  
0ꢀ27  
0ꢀ27  
0ꢀ27  
0ꢀ90  
Ni 508ꢀ4Ω  
Ni-Fe 604  
Cu 10 @25°C  
*1ꢀ Or 0ꢀ1ꢁ oꢂ ꢃspa, whichever iꢃ grepterꢀ  
Iꢂ the ꢃelected outsut ꢃspa equplꢃ to or aprrower thpa the oae-teath oꢂ the mpximum ꢃspa, pdd 0ꢀ2ꢁꢀ  
M3LR SPECIFICATIONS  
ES-2662 Rev.13 Page 3/4  
http://www.m-system.co.jp/  
MODEL: M3LR  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
10 11 12  
7
8
9
DIN RAIL  
35mm wide  
1
4
2
5
3
6
18 (.71)  
110.5 (4.35)  
[5 (.20)]  
• When mounting, no extra space is needed between units.  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
3
9
10  
7
STATUS  
CONTROL BUTTONS  
2-wire  
RTD  
3-wire  
RTD  
4-wire  
RTD  
DIP SW  
6
1
2
Isolation  
Output  
Computation  
Output  
Driver  
+
+
A
A
A
Low Drift  
Amplifier  
& Burnout  
OUTPUT  
POWER  
B
B
8
11  
12  
A
B
4
B
B
5
CONFIGURATOR  
JACK  
Specifications are subject to change without notice.  
M3LR SPECIFICATIONS  
ES-2662 Rev.13 Page 4/4  
http://www.m-system.co.jp/  

相关型号:

M3LR-R4/B/UL

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LT-R4/A

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LT-R4/A/Q

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LT-R4/A/UL

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LT-R4/B

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LT-R4/B/Q

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LT-R4/B/UL

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU-M2/A

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU-M2/A/Q

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU-M2/A/UL

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU-M2/B

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU-M2/B/Q

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM