MDP-EC/A33 [MSYSTEM]
Lightning Surge Protectors for Electronics Equipment M-RESTER;型号: | MDP-EC/A33 |
厂家: | M-SYSTEM |
描述: | Lightning Surge Protectors for Electronics Equipment M-RESTER |
文件: | 总3页 (文件大小:117K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: MDP-EC
Lightning Surge Protectors for
Electronics Equipment M-RESTER
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection: M4 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (black)
LIGHTNING SURGE PROTECTOR FOR EC-CABLE USE
Functions & Features
• Designed specifically for M-System’s 32-point
Transmission System EC-CABLE
INSTALLATION
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
• Protects the transmitter model ECT and the receiver ECR
from lightning surges entering through the twisted-pair
cables connecting the both modules
Weight:
• Applicable to transmission systems by current loops
• Absorbs surges only without affecting instrumentation
signal
120 g (0.26 lb), standard
145 g (0.32 lb), with DIN rail mounting adapter
• No interruption of signal by unplugging the protector
element
PERFORMANCE
Max. continuous operating voltage (Uc):
23.5 (.93)
Line to line: ±12 V
Line to earth: ±500 V
Voltage protection level (Up):
• @ 1 kV (100 A)
Lot.NO
N1430B
100
(3.94)
JPAN
Line to line: ±25 V
MADEIN
Line to earth: ±650 V
M•STER
MODEL
• @ 2 kV (1 kA)
Line to line: ±30 V
80 (3.15)
mm (inch)
Line to earth: ±800 V
Response time: ≤ 0.1 μsec.
Leakage current:
Line to line: ≤ 10 μA @ ±12 V DC
Line to earth: ≤ 10 μA @ ±140 V DC
Max. discharge current (Imax): 5000 A (8 / 20 μs)
MODEL: MDP–EC[1]
ORDERING INFORMATION
• Code number: MDP-EC[1]
Specify a code from below for [1].
(e.g. MDP-EC/A33/Q)
Nominal current (I ): 100 mA
N
Internal series resistance: 20 Ω ±10 % (including return)
Capacitance @ 1 MHz:
Line to line: ≤ 1000 pF
• Specify the specification for option code /Q
(e.g. /C01)
Line to earth: ≤ 100 pF
Surge protection: IEC 61643-21 Categories C1, C2
[1] OPTIONS (multiple selections)
DIN Rail Mounting Adapter
blank: Without
/A33: With adapter (model A-33)
Other Options
blank: none
/Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
MDP-EC SPECIFICATIONS
ES-8117 Rev.12 Page 1/3
http://www.m-system.co.jp/
MODEL: MDP-EC
CONNECTION EXAMPLES
ECT
MDP-EC
MDP-EC
ECR
3
4
P+
P–
S+
S–
S+
S–
P+
P–
3
4
1
G
G
1
(PROTECTED
EQUIPMENT)
(PROTECTED
EQUIPMENT)
GROUNDING
PROTECTED
EQUIPMENT
M-RESTER
G
G
GROUNDING
(100 ohms or less)
CROSSOVER WIRE
A crossover wire between M-RESTER ground and the ground or
metallic housing of the equipment is required for protection.
If the protected equipment has no ground terminal, ground the
M-RESTER only.
When the M-RESTER is mounted with DIN Rail Mounting Adapter,
connect the grounding wire to the mounting screw of the M-RESTER.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
■ STANDARD
80 (3.15)
2–5 (.20) dia.
23.5 (.93)
MTG HOLE
53 (2.09)
27 (1.06)
HEAD ELEMENT
P+
P–
BASE
4–M4 TERMINAL SCREW
S+
S–
GROUND TERMINAL (G)
(used as mounting bracket)
■ WITH DIN RAIL MOUNTING ADAPTER
8.5
(.33)
80 (3.15)
53 (2.09)
[3.3 (.13)]
27 (1.06)
23.5 (.93)
DIN RAIL
35mm wide
P+
P–
4–M4 TERMINAL SCREW
S+
S–
2–M4 MOUNTING SCREW
(used as ground terminal (G))
MDP-EC SPECIFICATIONS
ES-8117 Rev.12 Page 2/3
http://www.m-system.co.jp/
MODEL: MDP-EC
MOUNTING REQUIREMENTS unit: mm (inch)
2–M4 SCREW
25 (.97) min.
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
20 W
+ S
P +
ELEMENT
ZD
Discharge
Elements
TO CABLE
TO ECT / ECR
ZD
– S
P –
BASE
G
GROUND TERMINAL
(used as mounting attachment)
Specifications are subject to change without notice.
MDP-EC SPECIFICATIONS
ES-8117 Rev.12 Page 3/3
http://www.m-system.co.jp/
相关型号:
©2020 ICPDF网 联系我们和版权申明